| 2007-01-22 09:15:11 | *** DENIED *** |
| | 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE CORRECT. |
| | |
| | 2) SEE ENERGY CALCULATIONS TOTAL COOLING BTU'S 264,000, |
| | AND PLANS ARE SHOWING 8 UNITS AT 59,000 = 472,000 TOTAL |
| | BTU'S, THE TWO MUST COINCIDE, PLEASE CORRECT. |
| | |
| | 3) PLEASE SUBMIT MANUAL J CALCULATIONS FOR MODEL "A" |
| | ONE UNIT ONLY 2081 SQUARE FEET, AND MODEL "B" ONE UNIT |
| | ONLY 2157 SQUARE FEET. |
| | |
| | 4) FORTH BEDROOM OPTION IS MISSING FROM MECHANICAL |
| | PLANS PAGE M-2, PLEASE CORRECT. |
| | |
| | 5) SEE PAGE M-2 FIRST FLOOR PLAN POWER ROOM #102, |
| | EXHAUST UP TO ATTIC, EXHAUST AIR MUST DISCHARGE TO THE |
| | OUTDOORS, SEE 2004 FBC/M 501.2. PLEASE CORRECT. |
| | |
| | 6) SEE PAGE M-1 FIRST FLOOR PLAN, THE CLOTHES DRYER |
| | VENT MAY NOT DISCHARGE ON TO THE A/C CONDENSER UNIT, |
| | SEE 2004 FBC/M 401.5.2. PLEASE CORRECT. |
| | |
| | 7) RETURN AIR TRANSFER DUCTS TO ALL ROOM ARE |
| | UNDER-SIZED, BALANCED RETURN AIR MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |