Text |
| 2007-02-15 15:01:02 | *****DENIED***** |
| | |
| | |
| | 01.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK |
| | WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH |
| | SUBMITTED PLAN SHEET. |
| | |
| | 02.PLEASE SUBMIT THE FOLLOWING INFORMATION: |
| | *CONSTRUCTION TYPE* OCCUPANCY TYPE*BUILDING HEIGHT |
| | * BUILDING SQUARE FOOTAGE *INTERIOR FINISH |
| | CLASSIFICATIONS * ANY OTHER PERTINENT INFORMATION TO |
| | ASSIST IN THE PLAN REVIEW. |
| | |
| | 03.WILL THE STRUCTURE HAVE A FIRE ALARM AND/OR FIRE |
| | SPRINKLER SYSTEM?IF SO, PROVIDE A LAYOUT OF THE FIRE |
| | PROTECTION SYSTEM(S) FOR REVIEW. |
| | |
| | 04.NFPA 101 - 2003 EDITION AND THE FORIDA FIRE |
| | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. |
| | |
| | 05.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 06.THE CONSTRUCTION OPERATION AND /OR THE STOCKING OF |
| | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE |
| | OR HINDER EMERGENCY ACCESS RESPONSE TO THE SAID |
| | PROPERTY OR THE VICINITY THEREOF. |
| | |
| | 07.THE SITE PLAN (SHEET A-1) DOES NOT SHOW ANY FIRE |
| | HYDRANTS.INDICATE THE LOCATION OF FIRE HYDRANT(S) |
| | WITHIN 300 FEET OF THE STRUCTURE.PLEASE BE ADVISED |
| | THAT AN ADDITIONAL HYDRANT MAY BE REQUIRED IF THIS |
| | DISTANCE IS GREATER THAN 500 FEET. |
| | |
| | 08IT APPEARS THAT THIS STRUCTURE WILL BE SETBACK |
| | FROM EMBASSY DRIVE.IF THIS TRUE, AS PER WEST PALM |
| | BEACH CODE, A MONUMENT SIGN OR MARQUEE SHALL POST THE |
| | ADDRESS RANGE FOR THE DEVELOPMENT.THESE NUMBERS SHALL |
| | BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| | WIDTH. |
| | |
| | 09.PLEASE INDICATE ON PLANS THAT ALL FIRE RATED DOORS |
| | (103,108,111) SHALL BE EQUIPPED WITH SELF CLOSING |
| | DEVICES AND SHALL POSTIVELY CLOSE UPON RELEASE. |
| | |
| | 10.ON THE APPROPIATE EXTERIOR ELEVATION SHEET, |
| | DISPLAY THE ADDRESS FOR THE UNITS. |
| | |
| | 11.PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE |
| | TIED INTO A FIRE ALARM SYSTEM.SMOKE ALARMS (SA), ON |
| | THE OTHER HAND, RECEIVE THEIR OPERATING POWER FROM THE |
| | BUILDING ELECTRICAL SYSTEM.SEE ELECTRICAL SHEETS. |
| | |
| | 12.SMOKE ALARMS ARE TO BE ARRANGED SO THAT THE |
| | OPERATION OF ANY SMOKE ALARMSHALL CAUSE THE ALARM IN |
| | ALL SMOKE ALARMS WITHIN THE DWELLING UNIT TO SOUND. |
| | |
| | 13.A FIRE HYDRANT IS SHOWN ON SHEET LP-1 BUT NOT ON |
| | SHEET A-1.IS THIS AN EXISTING HYDRANT OR A PROPOSED |
| | HYDRANT TO BE INSTALLED? |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |