2007-05-02 16:39:58*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 4-5-07 NOTE #3, ENERGY
 CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER
 2004 FBC 13-600.3.ABC.2.
  
 2) NEED OUTSIDE AIR CALCULATIONS, THE CALCULATIONS MAY
 BE PROVISO-ED IF YOU AGREE TO 354 CFM'S OUTSIDE AIR,
 AND THE ENERGY CAL'S ARE SIGNED, IF OTHER REVIEWS
 REQUIRE PLANS TO BE REDONE THEN PLEASE ADD THE OUTSIDE
 AIR CAL'S. TO THE REVISED MECHANICAL PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.