Plan Review Notes
Plan Review Notes For Permit 06120556
Permit Number 06120556
Review Stop P
Sequence Number 2
Notes
Date Text
2007-04-07 11:13:22DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHT 1 TOILET ROOM SHALL BE ACCESSIBLE. SHOW THE
 FOLLOWING:
 A. OK
 B. OK
 C. OK
 D. OK
 E. 11-4.19.4 EXPOSED PIPES & SURFACES - ***NOT
 ADDRESSED
 F. 11-4.19.5 FAUCETS - ***NOT ADDRESSED
  
 4. OK
 5. OK
 6. OK
 7. OK.
  
 8. TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED, AND
 DEPENDING ON THE OCCUPANCY, A SERVICE SINK MAY BE
 REQUIRED.-OK, BUT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS AS WELL AS SECTION
 11-4.15.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 9. SUBMIT A SANITARY RISER DIAGRAM. SHOW ALL PIPE
 SIZES, TRAPS AND VENTS. SECTION 106.3.5.1.3.-OK,
 BUT THE DRINKING FOUNTAIN IS NOT VENTED. SECTION
 901.2.1.
  
 10. OK
 11. OK
  
 **********NEW COMMENT***********
  
 1B. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE BUILDING. IF EXISTING PLEASE INDICATE ON THE
 PLUMBING PLAN. SECTION 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]