| Plan Review Notes For Permit 06120556 |
| Permit Number |
06120556 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-05 12:30:57 | *** DENIED *** | | | 1) COOLING LOAD CALCULATIONS ARE CALLING FOR 36,429 | | | SENSIBLE BTU'S (ESTIMATED 4 TONS), THE MECHANICAL PLANS | | | ARE CALLING FOR A 2.5 TON A/C SYSTEM WHICH IS TO SMALL, | | | THE PLANS CAN NOT CALL FOR LESS THAN THE COOLING LOAD | | | CALCULATIONS, SEE 2004 FBC 13-607.1.ABC.1.1. | | | | | | 2) PART OF THE ENERGY CALCULATIONS IS MISSING, PLEASE | | | CORRECT. | | | | | | 3)ENERGY CALCULATIONS NEED TO BE SIGNED BY | | | OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 4) RETURN AIR NEEDS TO BE PROVIDED FOR THE OFFICE, SEE | | | 2004 FBC/M 601.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|