Plan Review Notes
Plan Review Notes For Permit 06120556
Permit Number 06120556
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-04-11 17:10:35*****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED.CAPS INDICATE
 HOW COMMENTS ARE TO BE ADDRESSED
  
  
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO SHEET D-1
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. ADD
 TO SHEET D-1
  
 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE, OR
 THE VICINITY OF THE STRUCTURE (INCLUDING FIRE LANES).
 ADD TO SHEET D-1
  
 05.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 EXTERIOR ELEVATION FRONTING NORTHWOOD ROAD.AS PER
 WEST PALM BEACH CODE, NUMERALS SHALL BE NO LESS THAN 6"
 IN HEIGHT AND 1" IN WIDTH.INSERT THE ADDRESS NUMBER,
 SHEET A-2, FRONT ELEVATION
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722