2007-03-25 10:46:53 
  
 ****** UNSAT 2ND REVIEW******
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS BASED ON
 CHANGES ON PLANS.
  
  
 1) NOTE:PLEASE SEE THE ENERGY CALCULATIONS NEED TO BE
 SEALED SO THAT THE SEAL IS CLEAR AND VISIBLE WITH ALL
 INFORMATION ON SAID SEAL AS REQUIRED PER FAC
 61G15-23.001, FS 471.025
 THIS IS THE SAME COMMENT FROM PREVIOUS REVIEW, AS THE
 SAME SHEETS WERE SUBMITTED BACK WHICH ARE DATED OCT OF
 06.
 PLEASE SEE THE NEXT COMMENT.
  
 2) NOTE:RESPONSE MENTIONS THIS CONTAINS 2-8INCH BLOCK
 WALLS WHICH DOES NOT NECESSARILY DEFINE THIS AS
 SEPARATE *BUILDING* BY DEFINITION. THIS IS THE RATE
 WALL ALONG WITH THE STRUCTURE WHICH MUST BE COLLAPSIBLE
 ON BOTH SIDES WITHOUT AFFECTING THE STRUCTURAL
 INTEGRITY OF THE OTHER STRUCTURE. PLEASE CLARIFY THIS
 ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE THE
 SAME METHOD *A* WHICH DOES NOT PROVIDE THE INPUT DATA
 REPORT WHICH IS REQUIRED AS NOTED ON PAGE ONE OF THE
 SHEETS. PLEASE ALSO SEE THAT THE PLANS SEEM TO BE
 TAKING PRESCRIPTIVE METHODS OF *C* AND ALSO TABLE *C*?
  
 PLEASE SEE THE EXTERIOR LIGHTING SHALL CORRELATE WITH
 THE EXTERIOR LIGHTING ON PLANS.
 PLEASE CLARIFY THAT THIS IS ONE INDIVIDUAL BUILDING AS
 DEFINED IN THE FBC FIRST, THEN PLEASE COORDINATE THE
 METHODS.
 PLEASE SEE THE LIGHTING AS SHOWN ON PLANS IS TO
 CORRELATE WITH THE INPUT DATA REPORT. PLEASE ALSO SEE
 13-415.2.ABC.1.2 SUB PARAGRAPH 3.
  
 ** AS NOTED ON PREVIOUS REVIEW. IF THIS IS PART OF A
 BUILDING IN EXCESS OF 5KSQ FT THEN THE REQUIREMENTS OF
 13-415.1.ABC.1.1, .1.2 AND .1.3 SHALL BE MET. PLEASE
 KNOW HOWEVER INFORMATION FOR 13-415.2 IS REQUIRED AS
 THE LIGHTING PERFORMANCE LEVELS NEED TO BE STATED TO
 MEET THE NEW REQUIREMENTS.
 THE SURVEY SUBMITTED LENDS TO THAT THIS IS SEPARATE
 BUILDING WHICH SHOWS A PROPERTY LINE, HOWEVER WALL
 RATINGS ARE NOT CLEAR AND STRUCTURAL ELEMENTS ARE NOT
 CLEAR AT THIS TIME.
 PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES TO
 BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION ON
 PLANS.
 NOT ENOUGH INFORMATION ON LIGHTING ALLOWANCES IS
 PROVIDED.
  
 3) NOTE: PLEASE SUBMIT AND SHOW ALL CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE WHICH IS REQUIRED
 TO BE SUBMITTED. PLEASE SEE SOME CIRCUITS ARE MISSING
 CIRCUITING, ALTHOUGH MOST WERE DONE. THE PLANS ARE
 REDLINED WITH SOME OF THE CIRCUITING MISSING. 408.4,
 310.16, 240.4
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 4) NOTE: PLEASE SEE THE RISER IS NOW SHOWING NEW
 CONDUCTORS WHICH HAVE INCREASED FROM THE PREVIOUS PLANS
 HOWEVER THE SERVICE ENTRANCE CONDUCTORS AND FEEDERS ARE
 NOT LARGE ENOUGH. PLEASE SEE 310.16 FOR SIZING. MAY NOT
 USE 310.15B6 AS THIS IS NOT RESIDENTIAL.
 310.16, 240.4, ETC
 5) NOTE: ONLY NOTED, THE SEPARATE SERVICE WILL DEPEND
 ON THE *SEPARATE BUILDING DEFINITION* SEEMS TO BE OK.
  
 7) NOTE: PLEASE SEE THE PLANS NOW NOTE AND SHOW
 EMERGENCY AND EXIT LIGHTS , YET THE NOTE ON THE PLANS
 MENTIONS CIRCUITING TO BE PER 700.12E, AND THESE ARE ON
 A SEPARATE CIRCUIT? PLEASE SEE TEXT TAKEN FROM NEC.
 **THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.**
 PLEASE KNOW IF TRYING TO MEET THE EXCEPTION THE LOCK ON
 DEVICE SHALL BE AN INTEGRAL PART OF THE BREAKER, NOT
 ONE THAT ONLY SNAPS INTO PLACE OR CAN BE EASILY REMOVED
 OR FALL OFF WHEN PANEL COVER IS REMOVED.
 110.3, 90.4.
  
 8) NOTE: PLEASE 220.43B FOR LOADS TO BE SHOWN FOR TRACK
 LIGHTING. PLEASE SEE THE PLANS INDICATE 18FT OF TRACK
 AND AT 200VA PER FT, HOWEVER THIS WOULD BE 3600VA,
 PLANS SHOW 1800VA.
 PLEASE CORRECT.
  
 9) NOTE: PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE
 SHOWN AT 125%, BUT THIS IS ONLY THE CONTINUOUS LOADS.
 PLEASE SEE SOME OF THE LOADS AT THE TOP OF THE LOAD
 CALCULATIONS ARE SHOWN, BUT NOT ALL AS REQUIRED IN THE
 CALCULATIONS.
 PLEASE SEE SOME LOADS LIKE THE REFRIGERATOR AND THE
 WATER COOLER AND THE CU DO NOT NEED TO BE SHOWN AT
 125%.
 PLEASE CALL TO GO OVER IF NEED BE.
 215.3, 230.42 ETC.
 220.
  
 10) NOTE: PLEASE SEE 600.5, AS THIS REQUIRES A SIGN
 CIRCUIT AND LOADS TO BE SHOWN FOR THIS CIRCUIT
 ACCORDINGLY. PLEASE SEE THIS CIRCUIT IS NOT PERMITTED
 TO CONTAIN ANY OTHER LOADS ON THIS DEDICATE CIRCUIT
 INCLUDING OUTSIDE/EXTERIOR LIGHTING.
  
 11) NOTE: PLEASE VERIFY THE OVER CURRENT
 PROTECTION/WIRE SIZES AND THE SIZE OF THE WATER HEATER.
 THIS UNIT IS BEING SHOWN AS A 20GALLON UNIT WITH 40AMP
 OCP AND #8 CONDUCTORS.
 PLEASE SEE 422.13 AS THE MINIMUM LOADS, OCP, BRANCH
 CIRCUIT IS TO BE FIGURED AT 125%,BUT SECTION 422.11E3
 DOES LIMIT THE OCP AT 150%.
 PLEASE ADJUST THE OCP AND LOADS. IF THERE ARE
 QUESTIONS, PLEASE CALL.
 PLEASE SEE THE NEC HANDBOOK AS THIS GIVES THIS
 INFORMATION.
  
 12) NOTE: PLEASE VERIFY THE MAXIMUM OCP FOR THE AIR
 HANDLER UNIT, SHOWS 60A OCP ON AN 8KW UNIT. PLEASE SEE
 MANUFACTURES SPECS. (MOST LIKELY 50AMP). THIS WOULD
 AVOID REVISING AT ALTER DATE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717