| 2007-03-25 10:46:53 | |
| | |
| | ****** UNSAT 2ND REVIEW****** |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS BASED ON |
| | CHANGES ON PLANS. |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE ENERGY CALCULATIONS NEED TO BE |
| | SEALED SO THAT THE SEAL IS CLEAR AND VISIBLE WITH ALL |
| | INFORMATION ON SAID SEAL AS REQUIRED PER FAC |
| | 61G15-23.001, FS 471.025 |
| | THIS IS THE SAME COMMENT FROM PREVIOUS REVIEW, AS THE |
| | SAME SHEETS WERE SUBMITTED BACK WHICH ARE DATED OCT OF |
| | 06. |
| | PLEASE SEE THE NEXT COMMENT. |
| | |
| | 2) NOTE:RESPONSE MENTIONS THIS CONTAINS 2-8INCH BLOCK |
| | WALLS WHICH DOES NOT NECESSARILY DEFINE THIS AS |
| | SEPARATE *BUILDING* BY DEFINITION. THIS IS THE RATE |
| | WALL ALONG WITH THE STRUCTURE WHICH MUST BE COLLAPSIBLE |
| | ON BOTH SIDES WITHOUT AFFECTING THE STRUCTURAL |
| | INTEGRITY OF THE OTHER STRUCTURE. PLEASE CLARIFY THIS |
| | ON PLANS. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE THE |
| | SAME METHOD *A* WHICH DOES NOT PROVIDE THE INPUT DATA |
| | REPORT WHICH IS REQUIRED AS NOTED ON PAGE ONE OF THE |
| | SHEETS. PLEASE ALSO SEE THAT THE PLANS SEEM TO BE |
| | TAKING PRESCRIPTIVE METHODS OF *C* AND ALSO TABLE *C*? |
| | |
| | PLEASE SEE THE EXTERIOR LIGHTING SHALL CORRELATE WITH |
| | THE EXTERIOR LIGHTING ON PLANS. |
| | PLEASE CLARIFY THAT THIS IS ONE INDIVIDUAL BUILDING AS |
| | DEFINED IN THE FBC FIRST, THEN PLEASE COORDINATE THE |
| | METHODS. |
| | PLEASE SEE THE LIGHTING AS SHOWN ON PLANS IS TO |
| | CORRELATE WITH THE INPUT DATA REPORT. PLEASE ALSO SEE |
| | 13-415.2.ABC.1.2 SUB PARAGRAPH 3. |
| | |
| | ** AS NOTED ON PREVIOUS REVIEW. IF THIS IS PART OF A |
| | BUILDING IN EXCESS OF 5KSQ FT THEN THE REQUIREMENTS OF |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 SHALL BE MET. PLEASE |
| | KNOW HOWEVER INFORMATION FOR 13-415.2 IS REQUIRED AS |
| | THE LIGHTING PERFORMANCE LEVELS NEED TO BE STATED TO |
| | MEET THE NEW REQUIREMENTS. |
| | THE SURVEY SUBMITTED LENDS TO THAT THIS IS SEPARATE |
| | BUILDING WHICH SHOWS A PROPERTY LINE, HOWEVER WALL |
| | RATINGS ARE NOT CLEAR AND STRUCTURAL ELEMENTS ARE NOT |
| | CLEAR AT THIS TIME. |
| | PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES TO |
| | BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION ON |
| | PLANS. |
| | NOT ENOUGH INFORMATION ON LIGHTING ALLOWANCES IS |
| | PROVIDED. |
| | |
| | 3) NOTE: PLEASE SUBMIT AND SHOW ALL CIRCUITING ON PLANS |
| | AND CORRELATE WITH A PANEL SCHEDULE WHICH IS REQUIRED |
| | TO BE SUBMITTED. PLEASE SEE SOME CIRCUITS ARE MISSING |
| | CIRCUITING, ALTHOUGH MOST WERE DONE. THE PLANS ARE |
| | REDLINED WITH SOME OF THE CIRCUITING MISSING. 408.4, |
| | 310.16, 240.4 |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | |
| | 4) NOTE: PLEASE SEE THE RISER IS NOW SHOWING NEW |
| | CONDUCTORS WHICH HAVE INCREASED FROM THE PREVIOUS PLANS |
| | HOWEVER THE SERVICE ENTRANCE CONDUCTORS AND FEEDERS ARE |
| | NOT LARGE ENOUGH. PLEASE SEE 310.16 FOR SIZING. MAY NOT |
| | USE 310.15B6 AS THIS IS NOT RESIDENTIAL. |
| | 310.16, 240.4, ETC |
| | 5) NOTE: ONLY NOTED, THE SEPARATE SERVICE WILL DEPEND |
| | ON THE *SEPARATE BUILDING DEFINITION* SEEMS TO BE OK. |
| | |
| | 7) NOTE: PLEASE SEE THE PLANS NOW NOTE AND SHOW |
| | EMERGENCY AND EXIT LIGHTS , YET THE NOTE ON THE PLANS |
| | MENTIONS CIRCUITING TO BE PER 700.12E, AND THESE ARE ON |
| | A SEPARATE CIRCUIT? PLEASE SEE TEXT TAKEN FROM NEC. |
| | **THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES.** |
| | PLEASE KNOW IF TRYING TO MEET THE EXCEPTION THE LOCK ON |
| | DEVICE SHALL BE AN INTEGRAL PART OF THE BREAKER, NOT |
| | ONE THAT ONLY SNAPS INTO PLACE OR CAN BE EASILY REMOVED |
| | OR FALL OFF WHEN PANEL COVER IS REMOVED. |
| | 110.3, 90.4. |
| | |
| | 8) NOTE: PLEASE 220.43B FOR LOADS TO BE SHOWN FOR TRACK |
| | LIGHTING. PLEASE SEE THE PLANS INDICATE 18FT OF TRACK |
| | AND AT 200VA PER FT, HOWEVER THIS WOULD BE 3600VA, |
| | PLANS SHOW 1800VA. |
| | PLEASE CORRECT. |
| | |
| | 9) NOTE: PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE |
| | SHOWN AT 125%, BUT THIS IS ONLY THE CONTINUOUS LOADS. |
| | PLEASE SEE SOME OF THE LOADS AT THE TOP OF THE LOAD |
| | CALCULATIONS ARE SHOWN, BUT NOT ALL AS REQUIRED IN THE |
| | CALCULATIONS. |
| | PLEASE SEE SOME LOADS LIKE THE REFRIGERATOR AND THE |
| | WATER COOLER AND THE CU DO NOT NEED TO BE SHOWN AT |
| | 125%. |
| | PLEASE CALL TO GO OVER IF NEED BE. |
| | 215.3, 230.42 ETC. |
| | 220. |
| | |
| | 10) NOTE: PLEASE SEE 600.5, AS THIS REQUIRES A SIGN |
| | CIRCUIT AND LOADS TO BE SHOWN FOR THIS CIRCUIT |
| | ACCORDINGLY. PLEASE SEE THIS CIRCUIT IS NOT PERMITTED |
| | TO CONTAIN ANY OTHER LOADS ON THIS DEDICATE CIRCUIT |
| | INCLUDING OUTSIDE/EXTERIOR LIGHTING. |
| | |
| | 11) NOTE: PLEASE VERIFY THE OVER CURRENT |
| | PROTECTION/WIRE SIZES AND THE SIZE OF THE WATER HEATER. |
| | THIS UNIT IS BEING SHOWN AS A 20GALLON UNIT WITH 40AMP |
| | OCP AND #8 CONDUCTORS. |
| | PLEASE SEE 422.13 AS THE MINIMUM LOADS, OCP, BRANCH |
| | CIRCUIT IS TO BE FIGURED AT 125%,BUT SECTION 422.11E3 |
| | DOES LIMIT THE OCP AT 150%. |
| | PLEASE ADJUST THE OCP AND LOADS. IF THERE ARE |
| | QUESTIONS, PLEASE CALL. |
| | PLEASE SEE THE NEC HANDBOOK AS THIS GIVES THIS |
| | INFORMATION. |
| | |
| | 12) NOTE: PLEASE VERIFY THE MAXIMUM OCP FOR THE AIR |
| | HANDLER UNIT, SHOWS 60A OCP ON AN 8KW UNIT. PLEASE SEE |
| | MANUFACTURES SPECS. (MOST LIKELY 50AMP). THIS WOULD |
| | AVOID REVISING AT ALTER DATE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |