2007-02-05 17:34:42DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SUBMIT AN EXISTING FLOOR PLAN SHOWING THE EXTENT OF
 THE DEMOLITION.SECTION 106.1
  
 2. INDICATE THE OCCUPANCE OF THE SPACE SO THAT MINIMUM
 FACILITIES CAN BE DETERMINED. TABEL 403.1.
  
 3. SHT 1 TOILET ROOM SHALL BE ACCESSIBLE. SHOW THE
 FOLLOWING:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 C. 11-4.19.2 HEIGHT & CLEARANCES
 D. 11-4.19.3 CLEAR FLOOR SPACE
 E. 11-4.19.4 EXPOSED PIPES & SURFACES
 F. 11-4.19.5 FAUCETS
  
 4. THE WATER CLOSET SHALL BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. (FIG. 28).
  
 5. THE LAV SHALL BE A MINIMUM 15" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. (30" MINIMUM BETWEEN THE
 CENTERLINE OF THE W/C TO THE CENTERLINE OF THE LAV.).
 SECTION 405.3.1.
  
 6. THE TOILET ROOM SHALL SHOW AN UNOBSTRUCTED TURNING
 AREA. SECTION 11-4.22.3.
  
 7. THE TOILET ROOM DOOR SHALL NOT SWING INTO THE FLOOR
 SPACE REQUIRED FOR ANY DIXTURE. SECTION 11-4.23.2.
  
 8. TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED, AND
 DEPENDING ON THE OCCUPANCY, A SERVICE SINK MAY BE
 REQUIRED.
  
 9. SUBMIT A SANITARY RISER DIAGRAM. SHOW ALL PIPE
 SIZES, TRAPS AND VENTS. SECTION 106.3.5.1.3
  
 10. SUBMIT A WATER RISER DIAGRAM. SHOW ALL PIPE SIZES,
 VALVES, AND, IF REQUIRED, WATER HAMMER ARRESTORS.
 SECTIONS 106.3.5.1.3 & 604.9.
  
 11. THE WALLS OF ALL PUBLIC RESTROOMS SHAL BE SMOOTH,
 HARD & NONABSORBENT. SECTION 1210.2PLEASE SUBMIT A
 FINISH SCHEDULE INDICATING THE FINISH OF THE RESTROOM.
 SECTION 106.1.1.
  