| 2007-02-06 19:11:02 | *****DENIED***** |
| | |
| | |
| | 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE, |
| | SHALL BE REFERENCED. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE |
| | OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE, OR |
| | THE VICINITY OF THE STRUCTURE (INCLUDING FIRE LANES). |
| | |
| | 05.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE |
| | EXTERIOR ELEVATION FRONTING NORTHWOOD ROAD.AS PER |
| | WEST PALM BEACH CODE, NUMERALS SHALL BE NO LESS THAN 6" |
| | IN HEIGHT AND 1" IN WIDTH. |
| | |
| | 06.INDICATE THE OCCUPANCY TYPE FOR THIS STRUCTURE. |
| | I.E. BUSINESS, MERCANTILE, ASSEMBLY, ETC. |
| | |
| | 07.AS BASED UPON THE OCCUPANCY CLASSIFICATION, AN |
| | EXIT SIGN LIGHT (WITH BATTERY BACK-UP CAPABILITY) THAT |
| | IS READILY VISIBLE FROM ANY DIRECTION MAY BE REQUIRED. |
| | THE REQUIREMENT OF AN EXIT SHALL NOT APPLY TO EXISTING |
| | BUILDINGS, PROVIDED THAT THE OCCUPANCY CLASSIFICATION |
| | DOES NOT CHANGE. |
| | |
| | 08.ARE THERE ANY FIRE SPRINKLER AND/OR FIRE ALARM |
| | SYSTEM FOR THIS STRUCTURE?IF SO, HOW WILL THEY BE |
| | AFFECTED BY THE SCOPE OF WORK? |
| | |
| | 09.INDICATE LOCATION OF THE 2A:10BC FIRE |
| | EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL DISTANCE |
| | REQUIREMENT. |
| | |
| | 10.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR |
| | WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, |
| | AND IN ALL OTHER AREAS. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED |
| | |
| | |