| 2007-01-14 08:37:19 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE FLORIDA STATUTES 481.229, 481.221, |
| | PLANS ARE NOT PERMITTED TO BE DONE BY A DESIGNER UNLESS |
| | LICENSED UNDER THE SECTIONS AS NOTED AT A MINIMUM. |
| | PLEASE SEE THAT THE PLANS SHALL BE DONE BY AN ARCHITECT |
| | AT A MINIMUM. PLEASE SEE THE ELECTRICAL PLANS ARE NOT |
| | SIGNED, DATED OR SEALED BY A RESPONSIBLE PERSON |
| | LICENSED UNDER FS 481 OR 471. |
| | PLEASE CONTACT THE FLORIDA BOARD OF ARCHITECTS OR THE |
| | STATE?S LEGAL COUNSEL TO THE BOARD IF THERE ARE |
| | QUESTIONS REGARDING THE SCOPE OF WORK PERMITTED. |
| | CONTACT INFORMATION IS AVAILABLE IF NEEDED. |
| | THIS IS A COMMERCIAL SPACE FOR PUBLIC USE AND THE |
| | VALUE EXCEEDS $25K. |
| | ** THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS |
| | MADE BY ANY OTHER REVIEWER(S). ONE COPY OF PLANS ARE |
| | BEING RETAINED BY THIS OFFICE. |
| | |
| | 2) NOTE: PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| | PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. |
| | PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| | DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| | RELEVANT. |
| | 2006 REVISIONS TO THE 2004 FBC. |
| | 2005 NFPA-70 |
| | PLEASE SEE THE OTHER CODES WHICH ARE REQUIRED TO BE |
| | STATED ON PLANS FOR ELECTRICAL ARE: |
| | 2002 NFPA-72 AND 2003 NFPA-101. |
| | |
| | 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS NEED TO BE |
| | SEALED SO THAT THE SEAL IS CLEAR AND VISIBLE WITH ALL |
| | INFORMATION ON SAID SEAL AS REQUIRED PER FAC |
| | 61G15-23.001, FS 471.025 |
| | |
| | 4) NOTE: PLEASE CLARIFY THAT THIS IS ONE INDIVIDUAL |
| | BUILDING AS DEFINED IN THE FBC. PLEASE SEE DEFINITIONS |
| | AS IF THIS IS PART OF A "BUILDING" WHICH IS LARGER THAN |
| | 5K SQ FT THEN THE REQUIREMENTS OF 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3 SHALL BE MET. |
| | PLEASE KNOW HOWEVER INFORMATION FOR 13-415.2 IS |
| | REQUIRED AS THE LIGHTING PERFORMANCE LEVELS NEED TO BE |
| | STATED TO MEET THE NEW REQUIREMENTS. |
| | THE SURVEY SUBMITTED LENDS TO THAT THIS IS SEPARATE |
| | BUIDLING WHICH SHOWS A PROPERTY LINE, HOWEVER WALL |
| | RATINGS ARE NOT CLEAR AND STRUCTURAL ELEMENTS ARE NOT |
| | CLEAR AT THIS TIME. |
| | PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES TO |
| | BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION ON |
| | PLANS. |
| | NOT ENOUGH INFORMATION ON LIGHTING ALLOWANCES IS |
| | PROVIDED. |
| | |
| | 5) NOTE: PLEASE SUBMIT AND SHOW ALL CIRCUITING ON PLANS |
| | AND CORRELATE WITH A PANEL SCHEDULE WHICH IS REQUIRED |
| | TO BE SUBMITTED. |
| | PLEASE SEE THAT SOME ITEMS FOR CODE COMPLIANCE CAN NOT |
| | BE VERIFIED AT THIS TIME. |
| | 408.4, 310.16, 240.4 |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | |
| | 6) NOTE: PLEASE SEE THE RISER IS MISSING THE SERVICE |
| | ENTRANCE CONDUCTORS AS REQUIRED. |
| | 310.16, 240.4, ETC |
| | PLEASE SEE THAT THE 1/0'S WHICH ARE BEING SHOWN TO THE |
| | PANEL DO NOT MEET MINIMUM CODE FOR SIZE OF THE SERVICE |
| | AS SHOWN. |
| | PLEASE SEE 310.16, 240.4 FOR MINIMUM SIZES REQUIRED. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE SEE PLANS STATE THE SERVICE MAY CONTAIN |
| | AN OPTIONAL METER MAIN PANEL OUTSIDE, THIS IS OK; |
| | HOWEVER PLEASE KNOW THAT IF THIS IS THE OPTION TAKEN, |
| | PLANS WILL BE REQUIRED TO BE REVISED TO SHOW ACTUAL |
| | INSTALLATION(S). |
| | |
| | 8) NOTE: PLEASE SEE THE PLANS ALSO MENTIONS OPTIONAL |
| | EXIT LIGHTS AND THE SECTION GIVEN ON THE FBC DOES NOT |
| | PRESENT AN EXCEPTION TO THIS. PLEASE EXPLAIN RATIONAL |
| | FOR TRYING TO MEET AN EXCEPTION AND STATE WHAT SECTIONS |
| | GIVE THIS. PLEASE SEE THE SECTION GIVEN STATES THAT |
| | ILLUMINATION SHALL BE PROVIDED. |
| | PLEASE SEE NFPA-101 7.8 AND 7.9 AS MEANS OF EGRESS |
| | LIGHTING IS REQUIRED TO THE PUBLIC RIGHT OF WAY. (FLOOR |
| | AREAS 1FT CANDLE MIN). |
| | PLEASE SEE NOTES FROM THE FIRE MARSHAL'S REVIEW AND |
| | BUILDING REVIEW WHICH MAY EXTEND TO THIS. |
| | PLEASE KNOW IN EITHER CASE THE EM/EXT LIGHT SHALL BE |
| | CIRCUITED PER 700.12E. |
| | |
| | 9) NOTE: PLEASE SEE NOTES ON PLANS MENTIONS A FIRE |
| | ALARM SYSTEM SHALL BE INSTALLED. PLEASE KNOW THAT EVEN |
| | THOUGH THIS WILL BE UNDER A SEPARATE PERMIT, THE BASE |
| | SYSTEM SHALL BE SHOWN AT THIS TIME WITH ALL LEVELS FOR |
| | STROBES INTENSITIES AND SOUNDING LEVELS STATED ON |
| | PLANS. |
| | PLEASE SEE FBC 11-4.28.1,.2,AND .3(4) FOR MINIMUM |
| | LEVELS WHEN A FA SYSTEM IS INSTALLED. |
| | |
| | 10) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | THIS SPACE BASED ON A COMMERCIAL BUILDING. |
| | PLEASE SEE NEC 220.12, 220.14, 220.43(A) & (B), 220.44 |
| | ETC. |
| | PLEASE ALSO SEE THAT ALL CONTINUOUS LOADS SHALL BE |
| | SHOWN AT 125% 215.3, 230.42 ETC. |
| | PLEASE SEE THE LOADS AS SHOWN FOR THE LIGHTING SHALL BE |
| | SIZED BASED ON THE MAXIMUM LEVELS FOR A 15A CIRCUIT. |
| | PLEASE SEE THE 15AMP CIRCUITS ARE BEING SHOWN WITH |
| | LOADS OF 2KW ON EACH WHICH EXCEEDS THE RATINGS OF |
| | THESE. |
| | (TYPICAL MAX 1440VA 15A/1920VA 20A) HOWEVER PLEASE SEE |
| | THE CODE SECTIONS GIVEN FOR PERMITTED LOADS. ALSO NEC |
| | 210 |
| | |
| | 11) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES |
| | PER 210.62 AND LOADS PER 220.43. |
| | |
| | 12) NOTE: PLEASE SEE 600.5FOR THE SIZE AND LOADS |
| | REQUIRED TO BE FIGURED FOR THE SIGN CIRCUIT(S). |
| | |
| | 13) NOTE: PLEASE SEE EXTERIOR SPACE IS BEING NOTED AS A |
| | SHOW ROOM IN A PERGOLA AREA; PLEASE STATE WET LOCATIONS |
| | FOR FIXTURE, BOXES AND WIRING METHODS. |
| | FBC 106.1.2 |
| | NEC 300 |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |