Plan Review Notes
Plan Review Notes For Permit 06120556
Permit Number 06120556
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-14 08:37:19** UNSAT **
  
 1) NOTE: PLEASE SEE FLORIDA STATUTES 481.229, 481.221,
 PLANS ARE NOT PERMITTED TO BE DONE BY A DESIGNER UNLESS
 LICENSED UNDER THE SECTIONS AS NOTED AT A MINIMUM.
 PLEASE SEE THAT THE PLANS SHALL BE DONE BY AN ARCHITECT
 AT A MINIMUM. PLEASE SEE THE ELECTRICAL PLANS ARE NOT
 SIGNED, DATED OR SEALED BY A RESPONSIBLE PERSON
 LICENSED UNDER FS 481 OR 471.
 PLEASE CONTACT THE FLORIDA BOARD OF ARCHITECTS OR THE
 STATE?S LEGAL COUNSEL TO THE BOARD IF THERE ARE
 QUESTIONS REGARDING THE SCOPE OF WORK PERMITTED.
 CONTACT INFORMATION IS AVAILABLE IF NEEDED.
 THIS IS A COMMERCIAL SPACE FOR PUBLIC USE AND THE
 VALUE EXCEEDS $25K.
 ** THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER REVIEWER(S). ONE COPY OF PLANS ARE
 BEING RETAINED BY THIS OFFICE.
  
 2) NOTE: PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER.
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC.
 2005 NFPA-70
 PLEASE SEE THE OTHER CODES WHICH ARE REQUIRED TO BE
 STATED ON PLANS FOR ELECTRICAL ARE:
 2002 NFPA-72 AND 2003 NFPA-101.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS NEED TO BE
 SEALED SO THAT THE SEAL IS CLEAR AND VISIBLE WITH ALL
 INFORMATION ON SAID SEAL AS REQUIRED PER FAC
 61G15-23.001, FS 471.025
  
 4) NOTE: PLEASE CLARIFY THAT THIS IS ONE INDIVIDUAL
 BUILDING AS DEFINED IN THE FBC. PLEASE SEE DEFINITIONS
 AS IF THIS IS PART OF A "BUILDING" WHICH IS LARGER THAN
 5K SQ FT THEN THE REQUIREMENTS OF 13-415.1.ABC.1.1,
 .1.2 AND .1.3 SHALL BE MET.
 PLEASE KNOW HOWEVER INFORMATION FOR 13-415.2 IS
 REQUIRED AS THE LIGHTING PERFORMANCE LEVELS NEED TO BE
 STATED TO MEET THE NEW REQUIREMENTS.
 THE SURVEY SUBMITTED LENDS TO THAT THIS IS SEPARATE
 BUIDLING WHICH SHOWS A PROPERTY LINE, HOWEVER WALL
 RATINGS ARE NOT CLEAR AND STRUCTURAL ELEMENTS ARE NOT
 CLEAR AT THIS TIME.
 PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES TO
 BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION ON
 PLANS.
 NOT ENOUGH INFORMATION ON LIGHTING ALLOWANCES IS
 PROVIDED.
  
 5) NOTE: PLEASE SUBMIT AND SHOW ALL CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE WHICH IS REQUIRED
 TO BE SUBMITTED.
 PLEASE SEE THAT SOME ITEMS FOR CODE COMPLIANCE CAN NOT
 BE VERIFIED AT THIS TIME.
 408.4, 310.16, 240.4
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 6) NOTE: PLEASE SEE THE RISER IS MISSING THE SERVICE
 ENTRANCE CONDUCTORS AS REQUIRED.
 310.16, 240.4, ETC
 PLEASE SEE THAT THE 1/0'S WHICH ARE BEING SHOWN TO THE
 PANEL DO NOT MEET MINIMUM CODE FOR SIZE OF THE SERVICE
 AS SHOWN.
 PLEASE SEE 310.16, 240.4 FOR MINIMUM SIZES REQUIRED.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE PLANS STATE THE SERVICE MAY CONTAIN
 AN OPTIONAL METER MAIN PANEL OUTSIDE, THIS IS OK;
 HOWEVER PLEASE KNOW THAT IF THIS IS THE OPTION TAKEN,
 PLANS WILL BE REQUIRED TO BE REVISED TO SHOW ACTUAL
 INSTALLATION(S).
  
 8) NOTE: PLEASE SEE THE PLANS ALSO MENTIONS OPTIONAL
 EXIT LIGHTS AND THE SECTION GIVEN ON THE FBC DOES NOT
 PRESENT AN EXCEPTION TO THIS. PLEASE EXPLAIN RATIONAL
 FOR TRYING TO MEET AN EXCEPTION AND STATE WHAT SECTIONS
 GIVE THIS. PLEASE SEE THE SECTION GIVEN STATES THAT
 ILLUMINATION SHALL BE PROVIDED.
 PLEASE SEE NFPA-101 7.8 AND 7.9 AS MEANS OF EGRESS
 LIGHTING IS REQUIRED TO THE PUBLIC RIGHT OF WAY. (FLOOR
 AREAS 1FT CANDLE MIN).
 PLEASE SEE NOTES FROM THE FIRE MARSHAL'S REVIEW AND
 BUILDING REVIEW WHICH MAY EXTEND TO THIS.
 PLEASE KNOW IN EITHER CASE THE EM/EXT LIGHT SHALL BE
 CIRCUITED PER 700.12E.
  
 9) NOTE: PLEASE SEE NOTES ON PLANS MENTIONS A FIRE
 ALARM SYSTEM SHALL BE INSTALLED. PLEASE KNOW THAT EVEN
 THOUGH THIS WILL BE UNDER A SEPARATE PERMIT, THE BASE
 SYSTEM SHALL BE SHOWN AT THIS TIME WITH ALL LEVELS FOR
 STROBES INTENSITIES AND SOUNDING LEVELS STATED ON
 PLANS.
 PLEASE SEE FBC 11-4.28.1,.2,AND .3(4) FOR MINIMUM
 LEVELS WHEN A FA SYSTEM IS INSTALLED.
  
 10) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 THIS SPACE BASED ON A COMMERCIAL BUILDING.
 PLEASE SEE NEC 220.12, 220.14, 220.43(A) & (B), 220.44
 ETC.
 PLEASE ALSO SEE THAT ALL CONTINUOUS LOADS SHALL BE
 SHOWN AT 125% 215.3, 230.42 ETC.
 PLEASE SEE THE LOADS AS SHOWN FOR THE LIGHTING SHALL BE
 SIZED BASED ON THE MAXIMUM LEVELS FOR A 15A CIRCUIT.
 PLEASE SEE THE 15AMP CIRCUITS ARE BEING SHOWN WITH
 LOADS OF 2KW ON EACH WHICH EXCEEDS THE RATINGS OF
 THESE.
 (TYPICAL MAX 1440VA 15A/1920VA 20A) HOWEVER PLEASE SEE
 THE CODE SECTIONS GIVEN FOR PERMITTED LOADS. ALSO NEC
 210
  
 11) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES
 PER 210.62 AND LOADS PER 220.43.
  
 12) NOTE: PLEASE SEE 600.5FOR THE SIZE AND LOADS
 REQUIRED TO BE FIGURED FOR THE SIGN CIRCUIT(S).
  
 13) NOTE: PLEASE SEE EXTERIOR SPACE IS BEING NOTED AS A
 SHOW ROOM IN A PERGOLA AREA; PLEASE STATE WET LOCATIONS
 FOR FIXTURE, BOXES AND WIRING METHODS.
 FBC 106.1.2
 NEC 300
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  