| 2006-12-20 10:51:41 | DENIED BY BUILDING | | | | | | 1) SPECIFY THE FASTENING OPTION THAT WILL BE USED TO | | | INSTALL THE ROOFING SYSTEM. CIRCLE THE APPROPRIATE ONE | | | ON THE PRODUCT APPROVAL. | | | | | | 2) NEITHER OF THE TWO FASTENING OPTIONS LISTED ON PAGE | | | 17 OF THE PRODUCT APPROVAL HAVE SUFFICENT PRESSURES FOR | | | ALL ROOF ZONES. LIMITATION 7 ON PAGE 20 ALLOWS ENHANCED | | | FASTENING WITH SIGNED AND SEALED RAS 117 CALCULATIONS | | | FROM A FLORIDA REGISTERED ENGINEER, ARCHITECT OR ROOF | | | CONSULTANT. SUBMIT SIGNED AND SEALED CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|