Plan Review Notes
Plan Review Notes For Permit 06120539
Permit Number 06120539
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-29 15:30:58DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 SECTION 424.2 OR R4101 SWIMMING POOLS **
 FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A **NO** IS IF THE COMMENT WAS NOT FULLY ADDRESSED
 AND/OR FURTHER EXPLANATION OR CHANGES IN PLANS OR
 DOCUMENTS ARE STILL NEEDED. THIS REVIEWER WILL TRY TO
 BETTER EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN **OK** WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A **NO/OK** MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **NO/OK** FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 NOTE: THE RESUBMITTED TABLE IS OK FOR THE 1-1/2 HP
 FEATURE BUT DOES NOT PROVIDE FOR THE 2-1/2 HP
 RECIRCULATING PUMP.THE RESUBMITTED TABLE ONLY GOES TO
 2 HP.
  
 3 **NO** FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 NOTE: THE RESUBMITTED MANUFACTURER SHEETS DO NOT
 INDICATE AN INDICATION OF A RECOGNIZED TESTING AGENCY.
 ALSO AN ONLINE SEARCH FOR A LISTING OF THE HEAT PUMP
 CAME UP UNSUCCESSFUL.
  
 4 **OK**
  
 5. **OK**
  
 6. **OK**
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  