| 2007-06-29 15:30:58 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 SECTION 424.2 OR R4101 SWIMMING POOLS ** |
| | FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A **NO** IS IF THE COMMENT WAS NOT FULLY ADDRESSED |
| | AND/OR FURTHER EXPLANATION OR CHANGES IN PLANS OR |
| | DOCUMENTS ARE STILL NEEDED. THIS REVIEWER WILL TRY TO |
| | BETTER EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN **OK** WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A **NO/OK** MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1. **OK** |
| | |
| | 2. **NO/OK** FBC-2004 SEC. 424.6.6 OR FBC-2004 |
| | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. PLEASE |
| | SUBMIT AN ENGINEERED TABLE FOR "VENT |
| | PIPE MAXIMUM LENGTH" INDICATING PUMP |
| | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH |
| | OF THE 1-1/2" PVC VENT PIPE, FROM |
| | WHERE IT STARTS TO WHERE IT ENDS UP, |
| | COMPLYING WITH THE THREE SECOND RELEASE. |
| | NOTE: THE RESUBMITTED TABLE IS OK FOR THE 1-1/2 HP |
| | FEATURE BUT DOES NOT PROVIDE FOR THE 2-1/2 HP |
| | RECIRCULATING PUMP.THE RESUBMITTED TABLE ONLY GOES TO |
| | 2 HP. |
| | |
| | 3 **NO** FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT) |
| | NOTE: THE RESUBMITTED MANUFACTURER SHEETS DO NOT |
| | INDICATE AN INDICATION OF A RECOGNIZED TESTING AGENCY. |
| | ALSO AN ONLINE SEARCH FOR A LISTING OF THE HEAT PUMP |
| | CAME UP UNSUCCESSFUL. |
| | |
| | 4 **OK** |
| | |
| | 5. **OK** |
| | |
| | 6. **OK** |
| | |
| | END OF COMMENTS: |
| | |