Plan Review Notes For Permit 06120539
Permit Number 06120539
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-03 14:08:18DENIED
 REFERENCE: FBC-2004 SEC. 424.2 OR FBC-2004 SEC. R4101
 SWIMMING POOLS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1) COMPLY WITH FBC-2004 SEC 424.2, OR
 FBCR-2004 SEC R4101 PRIVATE SWIMMING
 POOLS. (PLEASE ADD TO NOTES)
  
 2) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
  
 3) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 4) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 5) PLEASE IDENTIFY THE VACUUM, SKIMMER, AND FEATURE
 PUMP MAIN DRAINS IN POOL AND PLEASE ADD FEATURE PUMP TO
 POOL DATA.
  
 6) PLEASE NOTE ON RESUBMITTAL IF HEAT PUMP IS GAS OR
 ELECTRIC.
  
 ***IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  