2007-01-02 14:13:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 PLAN REVIEW ONLY;
  
 1. ADDRESS FOR CAMP, DRESSER & MCKEE DOES NOT REFLECT
 THE ADDRESS ON THE DBPR WEBSITE. PLEASE CLARIFY. ALL
 TITLE BLOCKS SHALL INDICATE THE ADDRESS PER FAC
 61G1-16.004(1) & FS 481.025. (SEE ATTACHED SHEET FROM
 DBPR WEBSITE).
  
 2. SHT M-3 INDICATES A 2" PVC SUPPLY TO A "HB". PER THE
 ABBREVIATION SHEET THAT WOULD BE A HOSE BIBB. PLEASE
 CLARIFY THAT A 2" SUPPLY IS REQUIRED FOR THE "HB" AND
 THAT THE "HB" IS A HOSE BIBB. ALSO IF IT IS A HOSE
 BIBB, A SHUT OFF VALVE IS REQUIRED ON THE SUPPLY LINE
 TO EACH HOSE BIBB. SECTIONS 106.1.1 AND 606.1(2).
  
 3. SHT M-3 INDICATES PVC TO THE RPZV BACKFLOW AND ON TO
 THE VAPEX UNITS 1 & 2. CLARIFICATION IS REQUIRED, AS
 PVC PIPE IS NOT APPROVED FOR DISTRIBUTION PIPING INSIDE
 THE STRUCTURE. PLEASE INDICATE IF THE PIPING IS INSIDE
 THE STRUCTURE OR OUTSIDE. SECTION 106.1.1 AND TABLE
 605.4.
  
 4. SHT CD-2 DETAIL J. THE CITY WPB STANDARD FOR THE
 BACKFLOW CALLS FOR BALL VALVES. DETAIL J INDICATES GATE
 VALVES. PLEASE CHANGE DETAIL TO CORRELATE WITH THE CITY
 UTILITY STANDARD.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]