| Plan Review Notes For Permit 06120514 |
| Permit Number |
06120514 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-25 17:07:15 | *****DENIED***** | | | | | | | | | NOT ENOUGH INFORMATION ON THE PROPOSED SCOPE OF WORK TO | | | CONDUCT AN ADEQUATE FIRE FIRE PLAN REVIEW.PLEASE BE | | | ADVISED THAT: | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.CONSTRUTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER WITH EMERGENCY RESPONSE ACCESS TO | | | THE SAID PROPERTY OR VICINITY THEREOF. | | | | | | 3.ACCESS TO FIRE HYDRANTS, FIRE DEPARTMENT | | | CONNECTIONS, OR ANY OTHER FIRE PROTECTION EQUIPMENT | | | SHALL BE MAINTAINED AT ALL TIMES. | | | | | | 4.PROVIDE ONE OR MORE DEDICATED FIRE EXTINGUISHERS | | | THAT HAVE A MINIMUM CAPABILITY OF 40:BC LOCATED WITHIN | | | 100 FEET OF THE WORK AREA. | | | | | | 5.CUTTING/WELDING OPERATIONS USED IN THE SCOPE OF | | | WORK SHALL COMPLY WITH NFPA 51B. | | | | | | | | | TO EXPEDITE THE FIRE PLAN REVIEW PROCESS,SEE OTHER | | | PLAN REVIEW COMMENTS AND INCLUDE A RESPONSE LETTER | | | INDICATING HOW/WHERE EACH OF THE ABOVE ITEMS WERE | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|