Plan Review Notes
Plan Review Notes For Permit 06120514
Permit Number 06120514
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-25 17:07:15*****DENIED*****
  
  
 NOT ENOUGH INFORMATION ON THE PROPOSED SCOPE OF WORK TO
 CONDUCT AN ADEQUATE FIRE FIRE PLAN REVIEW.PLEASE BE
 ADVISED THAT:
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.CONSTRUTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER WITH EMERGENCY RESPONSE ACCESS TO
 THE SAID PROPERTY OR VICINITY THEREOF.
  
 3.ACCESS TO FIRE HYDRANTS, FIRE DEPARTMENT
 CONNECTIONS, OR ANY OTHER FIRE PROTECTION EQUIPMENT
 SHALL BE MAINTAINED AT ALL TIMES.
  
 4.PROVIDE ONE OR MORE DEDICATED FIRE EXTINGUISHERS
 THAT HAVE A MINIMUM CAPABILITY OF 40:BC LOCATED WITHIN
 100 FEET OF THE WORK AREA.
  
 5.CUTTING/WELDING OPERATIONS USED IN THE SCOPE OF
 WORK SHALL COMPLY WITH NFPA 51B.
  
  
 TO EXPEDITE THE FIRE PLAN REVIEW PROCESS,SEE OTHER
 PLAN REVIEW COMMENTS AND INCLUDE A RESPONSE LETTER
 INDICATING HOW/WHERE EACH OF THE ABOVE ITEMS WERE
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW