| 2006-12-21 18:31:08 | ** UNSAT ** |
| | |
| | |
| | ** PLEASE SEE PLANS ARE BEING ROUTED TO PLUMBING FOR |
| | REVIEW AS ELECTRICAL AND PLUMBING WERE SUBMITTED |
| | TOGETHER. CALLED CATALFUMO REP TO LET THEM KNOW |
| | ELECTRICAL COMMENTS WERE ONLINE. |
| | |
| | 1) NOTE: PLEASE SEE 240.21C AS TAPPED CONDUCTORS ON THE |
| | SECONDARY SIDE OF THE TRANSFORMERS SHALL TERMINATE IN A |
| | SINGLE MEANS OF OVER CURRENT PROTECTION. |
| | PLEASE SEE ALL TAPS GOING INTO GUTTERS AS SHOWN ARE NOT |
| | PERMITTED. |
| | |
| | 2) NOTE: PLEASE INDICATE TWO GROUND RODS ON THE |
| | SECONDARY SIDE OF ALL TRANSFORMER FOR THE SD SYSTEM PER |
| | 250.20, 250.30, 250.56 |
| | |
| | 3) NOTE: PLEASE SEE MISSING COLD WATER AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. |
| | 250.50 |
| | |
| | 4) NOTE: PLEASE PROVIDE INFORMATION ON TYPE OF DB CABLE |
| | BEING INSTALLED. |
| | PLEASE SEE 590.4 |
| | CONDUCTORS SHALL BE PERMITTED WITHIN CABLE ASSEMBLIES |
| | OR WITHIN MULTI-CONDUCTOR CORDS OR CABLES OF A TYPE |
| | IDENTIFIED IN TABLE 400.4 FOR HARD USAGE OR EXTRA-HARD |
| | USAGE. |
| | PLEASE ALSO SEE SECTION WHICH SPEAKS OF CABLE. |
| | |
| | 5) NOTE: PLEASE SEE LOAD CALCULATIONS FOR MAIN 4 OF 5 |
| | ARE NOT COMPLETE. PLEASE THERE IS A PANEL WHICH FEEDS |
| | LIGHTING, CRANE LIGHTS ETC WHICH IS NOT FIGURED OR |
| | SHOWN. PLEASE ALSO SEE PREVIOUS COMMENTS WITH RESPECT |
| | TO TAPS. |
| | |
| | 6) NOTE: PLEASE SEE NO HAND DRAWN CHANGES MAY BE DONE |
| | TO PLANS WHICH ARE SIGNED, DATED AND SEALED BY AN |
| | ENGINEER. |
| | FS 471.025 |
| | |
| | 7) NOTE: PLEASE SEE POWER AS SHOWN WHICH WILL BE ON THE |
| | SECONDARY SIDES OF THE CITY HALL, LIBRARY AND GARAGE |
| | TRANSFORMER IS BEING SHOWN FOR FUTURE PANELS ETC, |
| | HOWEVER NO MEANS OF DISCONNECT AND OCP IS BEING SHOWN |
| | ON THE SECONDARY SIDE. |
| | PLEASE TERMINATE IN A SINGLE MEANS OF OCP WHICH LIMITS |
| | THE OCP ON THE CONDUCTORS, TRANSFORMER ETC. |
| | PLEASE SEE 240.21C ETC |
| | |
| | 8) NOTE: PLEASE SEE 250.66 FOR SIZING OF THE GROUNDING |
| | ELECTRODE CONDUCTOR(S) ON THE TRANSFORMER. MOST ARE |
| | OK. |
| | |
| | 9) NOTE: PLEASE SEE 450.3B FOR THE MAX OCP ON THE |
| | PRIMARY SIDE OF TRANSFORMERS. PLEASE SEE TRANS #1 AS |
| | THE OCP IS TOO HIGH. ( OR ) PLEASE SEE EXCEPTIONS AND |
| | PROVIDE INFORMATION ON THE TYPE OF UNIT BEING |
| | INSTALLED. |
| | |
| | 10) NOTE: PLEASE PROVIDE A LAYOUT/SITE PLANS WHICH |
| | INDICATES THE LOCATIONS OF ALL SERVICE EQUIPMENT BEING |
| | INSTALLED AND PROPOSED. |
| | FBC 106.1.2 ADMIN SECTION |
| | |
| | 11) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| | WORK FOR THE SERVICE AS SHOWN AND BEING PROPOSED SHALL |
| | INCLUDE ALL LABOR AND MATERIALS, EVEN IF MATERIALS WERE |
| | OWNER SUPPLIED. PLEASE KNOW IF NOT ADJUSTED FOR VALUE, |
| | ONE WILL BE ADJUSTED USING MARSHALL?S AND SWIFT GUIDE |
| | AS ADOPTED PER THE FBC 108.3 ADMIN SECTION. |
| | |
| | 12) NOTE: PLEASE SUPPLY INFORMATION ON TRAILERS BEING |
| | INSTALLED FOR LOADS. THE LOAD AS SHOWN ON RISER CAN NOT |
| | BE VERIFIED AS THE TRAILERS THEMSELVES ARE NOT |
| | PERMITTED. |
| | 220, 215.5, ETC |
| | |
| | 13) NOTE: PLEASE INDICATE CONTINUOUS LOADS AT 125%. |
| | PLEASE SEE LOAD AS SHOWN IS EXACTLY AT THE RATING OF |
| | THE SEC?S WHICH ARE BEING INSTALLED. PLEASE AS |
| | CONTINUOUS LOADS AND OTHER FACTORS HAVE NOT BEEN TAKEN |
| | OR SHOWN INTO CONSIDERATION THE SIZE OF THE SEC?S DO |
| | NOT SUPPLY ANY ROOM FOR ANY FUTURE LOADS.? |
| | 215.3, 230.42 , 310.16, 240.4, ETC |
| | |
| | 14) NOTE:PLEASE SEE RISER SEEMS TO IDENTIFY A |
| | "GROUND" "G" FROM FPL TO GUTTER AND FROM GUTTER TO ALL |
| | FIRST MEANS OF DISCONNECTS? PLEASE SEE THIS IS THE SAME |
| | SYMBOL BEING USED ON ALL OTHER LOCATIONS FOR GROUNDS |
| | ALSO. PLEASE CLARIFY AS THIS SHOULD BE SHOWN AS THE |
| | NEUTRAL OR "GROUNDED" CONDUCTOR AS THERE ARE NO |
| | EQUIPMENT GROUNDING CONDUCTORS BEFORE THE FIRST MEANS |
| | OF DISCONNECT. 250.6, 250.24B. |
| | PLEASE PROVIDE COMPLETE NEUTRAL LOAD CALCULATIONS AS |
| | THE NEUTRAL CONDUCTOR(S) FOR THE SERVICE ENTRANCE |
| | CONDUCTORS AND FEEDERS ARE SUBSTANTIALLY DECREASED. |
| | PLEASE INDICATE HOW AND WHERE THE LOAD FOR THE NEUTRAL |
| | WAS DERIVED AND SHOW ON PLANS IN ORDER TO VERIFY THE |
| | CORRECT SIZING OF THE CONDUCTORS AS SHOWN. |
| | |
| | 15) NOTE: PLEASE SEE LABELING OF MAINS SHALL BE AS |
| | FOLLOWS, 1 OF 5, 2 OF 5 ETC. |
| | PLEASE SEE RISER NOW SHOWS WHAT APPEARS TO BE A |
| | MISPRINT OF 105,205,305, ETC |
| | |
| | 16) NOTE: PLEASE SEE BASED ON THE NUMBER OF CONDUCTORS |
| | BEING SHOWN ON THE SECONDARY SIDE OF THE TRANSFORMER TO |
| | GUTTER THESE ARE ONLY SINGLE PHASE BEING BROUGHT TO |
| | GUTTERS??? |
| | PLEASE SEE PANEL FROM GUTTER WHICH INDICATES A THREE |
| | PHASE FEED?? |
| | PLEASE KNOW AS THIS TIME THE RISER IS VERY CONFUSING AS |
| | THREE PHASES ARE BEING BROUGHT TO TRANSFORMERS AND ONLY |
| | SINGLE PHASE BEING BROUGHT OUT? |
| | THERE ARE TOO MANY CODE SECTIONS TO PLACE FOR THIS |
| | NOTE, PLEASE SEE NEC 2005. |
| | |
| | 17) NOTE: PLEASE SEE THE MINIMUM SIZE OF THE GROUNDING |
| | ELECTRODE CONDUCTOR SHALL BE SIZED PER 250.66. |
| | |
| | ** PLEASE KNOW AS THERE ARE ITEMS ON RISER WHICH WILL |
| | BE CHANGING, THERE MAY BE COMMENTS ON FUTURE ELECTRICAL |
| | RISER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |