| 2006-12-21 10:00:48 | *** DENIED *** | | | 1) A MECHANICAL PERMIT WAS ALREADY ISSUED FOR THIS WORK | | | TO ACTION MECHANICAL, PERMIT # 06060520. THIS PERMIT | | | NEEDS TO BE CLOSED OR WILL NEED A CHANGE OF CONTRACTOR | | | WILL NEED TO BE FILED. | | | | | | 2) RETURN AIR TRANSFER GRILLS TO BEDROOMS ARE TO SMALL. | | | BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|