| Plan Review Notes For Permit 06120501 |
| Permit Number |
06120501 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-19 08:10:22 | DENIED BY BUILDING | | | | | | 1) THE MAXIMUM DESIGN PRESSURE FOR THE SYSTEM INDICATED | | | ON THE PRODUCT APPROVAL IS -52.5, WHICH IS TOO LOW FOR | | | THE PERIMETER AND CORNER ZONES ROOF ZONES FOR A | | | BUILDING WITH A 12' MEAN ROOF HEIGHT. ENHANCED | | | FASTENING IS REQUIRED. SEE LIMITATION NUMBER 7. SUBMIT | | | RAS 117 CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|