Plan Review Notes
Plan Review Notes For Permit 06120465
Permit Number 06120465
Review Stop E
Sequence Number 5
Notes
Date Text
2007-11-09 12:33:30** PROVISO **
  
 1) NOTE:PLANS SUBMITTED FOR REVISION #3 DO NOT
 INDICATE THE SCOPE OF WORK FOR DELETION OF TANK-LESS
 WATER HEATER. AS PER OWNER AND SPOKE TO ARCHITECT, THE
 TANK-LESS WATER HEATER ALONG WITH WASHER, DRYER AND
 SINK ARE NO LONGER IN SCOPE OF WORK TO BE DONE. NO
 ROUGH IN OR STUB OUTS FOR THESE ITEMS.
 ** PLANS WILL STILL NEED TO BE REVISED FOR ALL ITEMS AS
 PANEL SCHEDULE AND PLANS STILL CALL FOR WORK TO BE
 DONE, NOT ALL WAS DELETED. *EXAMPLE TANK-LESS WH.
  
 2) NOTE: THE PREVIOUS STAMPED PLANS STILL CONTAIN AN
 ATTACHMENT FOR THE EXISTING DWELLING TO COMPLY WITH FBC
 R313 AND NFPA-72 11.5.1.1.1 FOR SMOKE ALARMS.
  
 ** THESE ABOVE ITEMS SHALL ALL BE REVISED ON PLANS AND
 SUBMITTED FOR REVIEW AND STAMPING BEFORE FINAL
 INSPECTIONS.
 PLANS MUST BE ON SITE FOR ALL INSPECTIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTIONS SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717