Text |
| 2007-03-24 11:39:19 | |
| | |
| | ****** UNSAT 2ND REVIEW****** |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE SEE MISSING DISCONNECT FOR THE NEW |
| | TANKLESS WATER HEATER PER 422.30,31. |
| | PLEASE SEE 110.26 FOR CLEARANCE. |
| | |
| | 2) NOTE: PLEASE SEE THE FBC 2004 R313.1.1 AS SMOKE |
| | ALARMS ARE REQUIRE INSIDE AND OUTSIDE ALL SLEEPING |
| | ROOMS. THE 2004 FBC W/ THE 2006 REVISION WAS CHANGED TO |
| | REQUIRE THESE EVEN WHEN NOT DOING WORK INSIDE THE |
| | EXISTING DWELLING. |
| | PLEASE SHOW ON A LAYOUT OF THE EXISTING DWELLING. THESE |
| | SHALL BE SHOWN AS SA FOR SMOKE ALARMS NOT SD. SMOKE |
| | DETECTORS ARE DEVICES WHICH ONLY DETECT THE SMOKE AND |
| | DO NOT SOUND AN ALARM. |
| | SEE NFPA-72 DEFINITIONS. |
| | PLEASE SEE NFPA-72 11.5.1.1.1, AND 11.8.3 FOR |
| | PLACEMENT. |
| | |
| | 3) NOTE: PLEASE SEE THE RECEPTACLE FOR THE WASHER AS IT |
| | IS WITHIN 6FT OF THE LAUNDRY SINK SHALL BE GFI |
| | PROTECTED EVEN IF THIS IS A DEDICATE DEVICE.PLEASE |
| | SEE THAT THIS IS REQUIRED FOR ALL RECEPTACLES WITHIN |
| | 6FT OF LAUNDRY TUB WHICH ARE 15/20AMP AND 125V. |
| | THIS HAS CHANGED IN THE 2005 NEC.210.8A7 |
| | |
| | |
| | ** PLEASE CALL TO OVER COMMENTS ONCE ALL OTHER TRADES |
| | ARE COMPLETED ON THEIR REVIEW. IF ALL OTHER TRADES ARE |
| | OK, THEN THIS MAY BE SET UP AS A * PROVISO* WHICH |
| | PERMITS ISSUANCE OF PERMIT AND REVISED PLANS WILL BE |
| | REQUIRED BEFORE INSPECTION. |
| | IF PLANS COME BACK WITH ANY COMMENTS FROM OTHER TRADES |
| | FOR ANY REASON, PLEASE MAKE CORRECTIONS AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-03-24 11:08:57 | FROM ZONING ON 3/21 |