Plan Review Notes
Plan Review Notes For Permit 06120465
Permit Number 06120465
Review Stop B
Sequence Number 2
Notes
Date Text
2007-03-27 17:41:37DENIED BY BUILDING (2ND REVIEW)
  
 1) ALL OF THE ROOF SHEATHING IS REQUIRED TO BE FASTENED
 WITH 8D RING SHANK NAILS. PLEASE REVISED NOTES ON A2 TO
 SPECIFY 8D RING SHANK NAILS.
  
 2) THE DRAINAGE PLAN IS REQUIRED TO SHOW THAT THE
 SURFACE DRAINAGE WILL BE ROUTED TO THE STORM DRAIN OR
 OTHER APPROVED COLLECTION POINT AND NOT ONTO ADJACENT
 LOTS.
  
 3)SHOW COMPLIANCE WITH R310.4 FOR EMERGENCY EGRESS
 WHEN STORM PANELS ARE INSTALLED.
 R310.4 REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 4) THE DESIGN PRESSURE FOR THE SELECTED FIRESTONE
 MODIFIED ROOF SYSTEM IS 52.5 PSF, WHICH IS TOO LOW FOR
 ROOF ZONES 2 AND 3. SUBMIT RAS 117 CALCULATIONS FOR
 INCEASED FASTENER DENSITIES FOR THESE AREAS AS ALLOWED
 BY GENERAL LIMITATION NUMBER 7 ON PAGE 34 OF THE NOA.
  
 5) GLASS BLOCK INSTALLED WITH MORTAR IN ACCORDANCE WITH
 FBC SECTION 2110 IS NOT REQUIRED TO BE PROTECTED WITH
 STORM PANELS.
  
 6) THE STORM PANEL INSTALLATION SCHEDULE SUBMITTED
 CONTAINS SOME ERRORS. THE CALK-IN ANCHORS ARE REQUIRED
 TO HAVE A 7/8 " EMBEDMENT, NOT 1/8". THE EDGE DISTANCE
 REFERS TO THE SPACE BETWEEN THE EDGE OF THE OPENING AND
 THE STORM PANEL ANCHORS. THE FASTENER SPACING IS
 RELATED TO THE EDGE DISTANCE. SEE THE ANCHOR SPACING
 TABLES IN THE PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  