| 2006-12-29 07:18:51 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE PLANS INDICATE A NEW SERVICE |
| | HOWEVER PLEASE CORRELATE AND COMPLETE AS NEEDED. |
| | PLEASE SEE RISER IS MISSING THE AIC RATINGS FOR ALL NEW |
| | SERVICE EQUIPMENT. 110.9 |
| | PLEASE SEE RISER SHOWS A 200A MAIN DISCONNECT PANEL |
| | WITH A FEED TO THE 125A PANEL B, YET THIS PANEL B IS |
| | ALSO BEING SHOWN BEING FED FROM THE METER ALSO? PLEASE |
| | CLARIFY. |
| | PLEASE SEE IF INDEED THIS 125A PANEL IS FED FROM THE |
| | MAIN PANEL, PLEASE COMPLETE RISER WITH THE FEEDERS, |
| | EQUIPMENT GROUNDING ETC. 215.5, 250.110, 250.24, |
| | 250.122 ETC |
| | PLEASE SEE MISSING THE LOCATION OF WHAT IS BEING SHOWN |
| | AS A NEW SERVICE. 110.26, 240.24, 408.7 ETC. |
| | |
| | 2) NOTE: PLEASE SEE THE LOAD CALCULATIONS ARE SUBMITTED |
| | FOR THE EXISTING DWELLING HOWEVER THE NEW LOADS |
| | INCLUDING THE NEW REQUIRED CIRCUIT FOR THE GDO/ GARAGE |
| | DOOR OPENER IS NOT INCLUDED IN THE CALCULATIONS. |
| | PLEASE SUBMIT THE PANEL SCHEDULE IN WHICH THESE WILL BE |
| | CIRCUITED FROM SHOWING THE MINIMUM BRANCH CIRCUIT SIZE |
| | WITH THE CONDUCTOR SIZE(S) AND THE OVER CURRENT |
| | PROTECTION ON CIRCUIT. |
| | |
| | 3) NOTE: PLEASE LIST THE 2005 NEC ON PLANS. PLEASE KNOW |
| | AS INFORMATIONAL PURPOSE THE STATE ADOPTED THE NEW |
| | REVISIONS TO THE 2004 FBC AND THE NEW NFPA-70 (NEC) |
| | 2005 AS OF DECEMBER 8, 2006. ALL PERMIT APPLICATIONS |
| | MADE AFTER THIS DATE WILL BE UNDER THESE NEW CODES. |
| | |
| | |
| | ** PLEASE KNOW THERE ARE SOME UNANSWERED QUESTIONS |
| | BASED ON THE RISER SUBMITTED. |
| | ** PLEASE CALL IF THERE ARE ANY QUESTIONS, COMMENTS OR |
| | IF ANY PART OF THESE NOTES ARE NOT CLEAR IN ANY WAY. |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |