| 2007-01-02 09:00:02 | *** DENIED *** |
| | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 2) PLEASE SUBMIT TWO COPY'S OF THE ENERGY CALCULATIONS |
| | AND MANUAL J CAL'S. |
| | |
| | 3) PLEASE SHOW LOCATION OF CLOTHES DRYER VENT |
| | TERMINATION ON MECHANICAL PLANS, INFORMATIONAL VENT MAY |
| | NOT DISCHARGE NEAR THE A/C CONDENSER UNIT, PER 2004 |
| | FBC/M 501.2 . |
| | |
| | 4) DOOR TO LAUNDRY ROOM NEEDS TO BE LOUVERED OR A GRILL |
| | NEEDS TO BE INSTALLED FOR RETURN AIR, PLEASE SHOW ON |
| | MECHANICAL PLANS. |
| | |
| | 5) RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS TO BE |
| | LARGER THAN 12". BALANCED RETURN AIR MAY BE ACHIEVED |
| | BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |