| Date |
Text |
| 2006-12-28 18:43:53 | |
| | ** UNSAT ** |
| | |
| | |
| | ** PLEASE KNOW ANY REFERENCES TO THE FBC CHAPTER 1 IN |
| | THE FOLLOWING NOTES THE ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE COMPLETE PANEL SCHEDULE WHICH WILL |
| | PROVIDE DESIGNATIONS TO ROOM/AREAS AT A MINIMUM. IE: |
| | BEDRM #1, LIVING RM LTS, ETC. |
| | 408.4, 310.16 |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER |
| | THE NEW 2005 NEC. |
| | THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON |
| | ELECTRICAL SHEETS. |
| | 2005 NFPA-2005 (SHOWN) |
| | 2002 NFPA-72 |
| | PLANS MAY NOT REFERENCE LATEST EDITION AS THE STATE OF |
| | FLORIDA ONLY JUST ADOPTED THE NEW REVISIONS TO THE 2004 |
| | FBC AND THE 2005 NECAS OF 12/8/06 |
| | |
| | 3) NOTE:PLEASE SEE MISSING WHAT APPEARS TO BE A |
| | COUNTER TOP GFI RECEPT ABOVE THE AREA WHERE THE |
| | DISHWASHER IS LOCATED. |
| | PLEASE SEE 210.52C1 |
| | |
| | 4) NOTE: PLEASE SEE FBC 2004 13-606.1.ABC.1.2.4 WHICH |
| | REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. |
| | PLEASE NOTE ON PLANS ACCORDINGLY. |
| | |
| | 5) NOTE: PLEASE VERIFY CONDUIT TYPE AND CONDUIT FILL ON |
| | THE 1 1/2 INCH CONDUIT WITH THE CONDUCTORS AS SHOWN. |
| | PLEASE SEE THE ONE CONDUIT IS MISSING THE EQUIPMENT |
| | GROUNDING CONDUCTOR AS NOTED IN NOTE #10 BELOW. PLEASE |
| | SEE IF THIS IS PVC AND SOME PART WILL BE SCHEDULE 80, |
| | ALL SHALL BE FIGURED ON SCHEDULE 80 CONDUIT. |
| | SEE TABLE IN CHAPTER 9 |
| | |
| | 6) NOTE: PLEASE SEE THAT THE PLANS SHALL BARE THE |
| | PRINTED NAME, DATE AND SIGNATURE OF THE PERSON TAKING |
| | RESPONSIBILITY OF THE PLANS. PLEASE SEE ONLY THE |
| | PRINTED NAME IS BEING SHOWN. |
| | FBC 106.1.2, FS 481.221, 471.025 |
| | |
| | 7) NOTE: PLEASE SEE WATER HEATER IS BEING SHOWN AS |
| | HAVING A RECEPT FOR THE CONNECTION. PLEASE SEE 422.31, |
| | 422.32 AS THIS SHALL BE A HARDWIRED UNIT WITH OR |
| | WITHOUT A DISCONNECT DEPENDING ON THE LOCATION OF PANEL |
| | ETC. |
| | |
| | 8) NOTE: PLEASE SEE 210.8A1, AS THE RECEPT(S) LOCATED |
| | WITHIN THE BATHROOM AREAS AND WITHIN 3FT OF THE SINK |
| | SHALL BE GFI ALSO. PLEASE SHOW. |
| | |
| | 9) NOTE: PLEASE SEE 210.8A6 AS ALL THE KITCHEN COUNTER |
| | SPACE RECEPTS SHALL BE SHOWN AS GFI. |
| | |
| | 10) NOTE: PLEASE SEE RISER AS THE EQUIPMENT GROUNDING |
| | CONDUCTOR IS MISSING FROM THE MAIN TO THE SUB PANEL. |
| | 250.24B, 250.110, 250.122 |
| | |
| | 10) NOTE: PLEASE CORRELATE SERVICE, PLEASE SEE PANEL |
| | SCHEDULE IS SHOWN AS 150AMPS YET THE RISER SHOWS THIS |
| | AS 200AMP WITH A MAIN CIRCUIT BREAKER. |
| | PLEASE ALSO SEE THE RISER MENTIONS PANEL IN GARAGE, YET |
| | THE PANEL ON PLANS APPEAR TO BE IN A LAUNDRY ROOM AND |
| | THERE IS NO GARAGE. |
| | PLEASE ADJUST AND CORRELATE PLANS. |
| | 106.1.2, 106.3.5.4, FBC ADMIN SECT |
| | |
| | 11) NOTE: PLEASE CORRELATE A/C LOADS. PLEASE SEE PANEL |
| | SCHEDULE SHOWS 7.5KW AND 10KW. WHICH ONE? |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE SEE 210.52 FOR SEVERAL MISSING |
| | REQUIRED RECEPTACLE FOR WALL SPACES 2FT OR MORE. PLEASE |
| | SEE COMMENT #15, AS THEY MAY BE OK, IF THE INTENTION IS |
| | FOR THESE TO BE 1/2 SWITCHED. |
| | |
| | 13) NOTE: PLEASE CORRELATE LOAD ON IRRIGATION PUMP ON |
| | PANEL SCHEDULE WITH THAT OF THE LOAD SHOWN ON LOAD |
| | CALCULATIONS. |
| | PLEASE ALSO SEE THE CIRCUIT IS BEING SHOWN ON A 1-POLE |
| | 30A CIRCUIT? |
| | |
| | 14) NOTE:PLEASE CLARIFY IF THE LOAD ON THE POOL PUMP |
| | IS SHOWN AT THE CONTINUOUS DUTY AS ON LOAD CALCULATIONS |
| | OR PLEASE SHOW AT 125%.ALSO SHOWN ON A 120V 1-POLE |
| | 30A CIRCUIT? |
| | 215.3, 230.42 |
| | |
| | 15) NOTE: PLEASE SEE 210.70 AND LS 101 7.8, PLEASE SEE |
| | THE PLANS AS THERE ARE MANY ANY WHICH WILL BE REQUIRED |
| | TO CONTAIN A LIGHT FIXTURE OF SOME KIND BEFORE FINAL OR |
| | OTHER EXCEPTION FOR SWITCHED RECEPT ETC. |
| | PLEASE SEE THE NEW ROOM SHALL CONTAIN A METHOD OF |
| | CONTROLLING LIGHTING FOR INGRESS INTO THE NEW ROOM FROM |
| | THE OUTSIDE. PLEASE SEE THIS CAN BE DONE WITH A 3-WAY |
| | OR OTHER OPTION. |
| | 210.70 , LS 101 7.8 |
| | PLEASE SEE SEVERAL AREAS WHICH INDICATE THE ENTIRE |
| | RECEPT BEING SWITCHED. PLEASE KNOW THIS IS OK, HOWEVER |
| | IF SWITCHING THE ENTIRE RECEPT, THEN AN ADDITIONAL |
| | RECEPT WILL BE REQUIRED PER 210.52. IF ONLY SWITCHING |
| | HALF, PLEASE ADJUST SYMBOL. |
| | PLEASE ADJUST PLANS AS NEEDED. |
| | |
| | |
| | 16) NOTE: * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |