Plan Review Notes
Plan Review Notes For Permit 06120458
Permit Number 06120458
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-26 15:05:21***APPROVED***
  
 1) IN ADDITION TO ELECTRONIC SUPERVISION, DOUBLE CHECK
 DETECTOR ASSEMBLY TO BE SECURED WITH CHAIN AND LOCK.
  
 2) FIRE HYDRANT SHALL BE LOCATED NOT FURTHER THAN 150'
 FROM FIRE DEPARTMENT CONNECTION.
  
 3) SYSTEM SHALL BE HYDROSTATICALLY TESTED AT 200 LBS
 FOR (2) HOURS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756