Plan Review Notes
Plan Review Notes For Permit 06120446
Permit Number 06120446
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-26 15:51:58** 2ND PROVISO **
  
 IF PLANS COME BACK FOR ANY COMMENTS FROM OTHER TRADES ,
 PLEASE CORRECT AT THIS TIME.
  
  
 ** CONDITION ISSUED FOR PERMIT ISSUANCE WHICH MUST BE
 DONE BEFORE FIRST ROUGH ELECTRICAL INSPECTION.
  
 1) NOTE: PLEASE SEE THE EXISTING DWELLING MUST MEET THE
 FBC R313 FOR THE EXISTING SLEEPING ROOMS INSIDE AND
 OUTSIDE TO BE BROUGHT UP TO CODE FOR SMOKE ALARM
 DEVICES.
 PLANS NEED TO SHOW IF THESE ARE NEW OR EXISTING MEETING
 THE CURRENT NFPA-72 11.5.1.1, 11.8.3
 PLEASE ALSO KNOW THAT THESE WILL ALSO BE REQUIRED TO
 MEET NEC 210.12 FOR ARC FAULT PROTECTION.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]