| 2007-08-16 10:57:55 | 2004 FBC |
| | ENCLOSE CARPORT TO FLORIDA ROOM |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE NOTICE OF COMMENCEMENT HAS EXPIRED AND WILL BE |
| | NEED TO BE RE-RECORDED BEFORE THE PERMIT IS ISSUED. |
| | THIS CAN BE DONE AFTER THE PLANS HAVE BEEN APPROVED BY |
| | ALL THE TRADES. |
| | THE WORK ON THE PROJECT IS REQUIRED TO START WITHIN 90 |
| | DAYS OF THE DATE THE PERMIT IS ISSUED. |
| | |
| | 2) BEFORE A PERMIT TO CONSTRUCT CAN BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION. |
| | 233-5025 IS THE CO. IMPACT FEE DEPARTMENT'S NUMBER. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R 302.1 AND 302.2 FROM |
| | COMMENTS NUMBER 3 AND 4 OF THE PREVIOUS REVIEW. SPECIFY |
| | ON THE SITE PLAN ON SHEET 2 THAT THERE ARE NO |
| | STRUCTURES WITHIN 6' OF THE CARPORT ON THE ADJACENT LOT |
| | AT THE SIDE WITH THE 4' 7-1/2 " DISTANCE TO THE |
| | PROPERTY LINE OR SPECIFY ONE HOUR FIRE RATED WALLS WITH |
| | NO OPENINGS. |
| | |
| | 4) SHOW COMPLIANCE WITH R403.1.4 WHICH REQUIRES ALL |
| | EXTERIOR FOOTINGS TO BE A MINIMUM OF 12 INCHES BELOW |
| | GRADE. |
| | |
| | 5) SHOW COMPLIANCE WITH R404.1.6 WHICH REQUIRES THE |
| | CONCRETE FOUNDATION WALL TO EXTEND 6 INCHES ABOVE ABOVE |
| | THE ADJACENT FINISH GRADE. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC RESIDENTIAL SECTION 704, |
| | WHICH REQUIRES A MINIMUM 6 INCH INSPECTION SPACE |
| | BETWEEN THE FINISH GRADE AND THE EXTERIOR STUCCO |
| | VENEER. THE EXCEPTIONS ALLOW A 4 INCH INSPECTION SPACE |
| | ABOVE PATIO SLABS AND ENTRY AREAS. |
| | |
| | 7) SPECIFY THE PROPOSED FINISH FLOOR ELEVATION AT THE |
| | ENCLOSED CARPORT AND THE EXISTING RESIDENCE. FBC* |
| | 106.1.2 |
| | |
| | 8) IF VAPOR RETARDER REQUIRED BY R506.2.3 CAN NOT BE |
| | INSTALLED, THE SLAB WILL BE REQUIRED TO BE TREATED WITH |
| | A WATERPROOF SEALER. |
| | |
| | 9) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED |
| | BY THE OWNER/AGENT PER FBC CHAPTER 13. |
| | |
| | 10) THE WALL SECTIONS ON SHEET 4 SPECIFIES R-30 |
| | INSULATION BETWEEN THE 2 X 6 ROOF JOISTS. THE R-VALUE |
| | FOR 5-1/2" INSULATION IS R-19. PLEASE REVISE THE WALL |
| | SECTIONS AND THE ENERGY CALC. FORM FOR THE SINGLE |
| | ASSEMBLY FRAME CEILING. |
| | |
| | 11)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |