Plan Review Notes
Plan Review Notes For Permit 06120446
Permit Number 06120446
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-31 14:15:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE APPLICATION.
 233-5025
  
 3) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL.
 EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING
 LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE
 PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4
 INCHES (102 MM).
 PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND
 SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL
 PROTECTION BASED ON LOCATION ON THE LOT. THE ADDITION
 IS LESS THAN 6 FEET FROM THE PROPERTY LINE ON ONE SIDE.
 PROVIDE A SITE PLAN WHICH INDICATES THE DISTANCE TO
 STRUCTURE ON THE ADJACENT PROPERTY AT THIS LOCATION.
  
 4)R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
  
 5)SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 6)SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 7) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES,
 THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 8)INDICATE THE FINISH FLOOR ELEVATION OF THE EXISTING
 HABITABLE SPACE AND THE FINISH FLOOR OF THE ENCLOSED
 CARPORT. FBC* 106.1.2.
  
 9) SPECIFY THE CEILING HEIGHT IN THE ENCLOSED CARPORT.
 SEE 601.3 (4) FBC EXISTING BUILDING CODE AND R 305.
  
 10) SHOW COMPLIANCE WITH R506.2.3 VAPOR RETARDER. A 6
 MIL (0.006 INCH; 152 ?M) POLYETHYLENE OR APPROVED VAPOR
 RETARDER WITH JOINTS LAPPED NOT LESS THAN 6 INCHES (152
 MM) SHALL BE PLACED BETWEEN THE CONCRETE FLOOR SLAB AND
 THE BASE COURSE OR THE PREPARED SUBGRADE WHERE NO BASE
 COURSE EXISTS.
 EXCEPTION: THE VAPOR RETARDER MAY BE OMITTED:
 1.FROM GARAGES, UTILITY BUILDINGS AND OTHER
 UNHEATED ACCESSORY STRUCTURES.
 2.FROM DRIVEWAYS, WALKS, PATIOS AND OTHER FLATWORK
 NOT LIKELY TO BE ENCLOSED AND HEATED AT A LATER DATE.
 3.WHERE APPROVED BY THE BUILDING OFFICIAL, BASED
 ON LOCAL SITE CONDITIONS.
  
 11)SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
  
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM
 OPENINGS. CONTINOUS SOFFIT VENTS WILL BE NEEDED IN
 ORDER TO PROVIDE VENTILATION TO RAFTER SPACES.
  
 12)R703.6.1 EXTERIOR USE OF PORTLAND CEMENT PLASTER
 SHALL COMPLY WITH THE APPLICATION REQUIREMENTS OF ASTM
 C 926.ASTM C 926 REQUIRES STUCCO TO BE 7/8" THICK
 WHEN APPLIED VERTICALLY OVER A METAL PLASTER BASE.
  
 13) SPECIFY THE CONNECTORS FOR THE ROOF RAFTERS TO THE
 EXTERIOR FRAME WALLS AND BEAM. SEE R301.1 FOR CONTINOUS
 LOAD PATH.
  
 14)ON SHEET 1 THE BUILDING HEIGHT LESS THAN 60 FEET
 STATEMENT REFERS TO THE SBC. PLEASE CORRECT TO FBC.
  
 15) THE FOUNDATION PLAN ON SHEET 2 SPECIFIES SECTIONS
 A, B AND C ON 3. THESE SECTIONS ARE LOCATED ON SHEET 4.
 PLEASE CORRECT.
  
 16)THE DOOR NOTE ON THE FOUNDATION HAS AN ARROW
 POINTING TO WHAT APPEARS TO BE THE ANCHOR BOLT
 LOCATIONS. PLEASE CLARIFY.
  
 17) THE WHITE OUT ON SEVERAL OF THE SHEETS IS NOT
 ALLOWED ON SIGNED AND SEALED DRAWINGS. SEE FS 471.025.
  
 18)CHECK THE WIND PRESSURES FOR THE OPENING ON SHEET
 1. THE NEGATIVE AND POSITIVE DESIGN OPENING PRESSURES
 APPEAR TO BE REVERSED. THE NEGATIVE PRESSURES SHOULD BE
 HIGHER THAN THE POSITIVE ONES. THE NEGATIVE PRESSURE
 FOR THE WINDOW OPENINGS IN WALL ZONE 4 IS MORE THAN
 SPECIFIED. SEE TABLE R301.2(2).
  
 19) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE ON
 THE WRONG FORMS.THE REQUIRED FORM IS 600C-04 R FOR
 SOUTH CLIMATE ZONES 7, 8 AND 9. THE FORMS ARE REQUIRED
 TO BE SIGNED BY THE PREPARER AND THE OWNER/AGENT.
  
 20)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 21)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 22)THE PRODUCT APPROVAL FOR THE EXTERIOR CONTAINS
 THREE DIFFERENT NOAS. SUBMIT TWO COPIES OF PRODUCT
 APPROVAL FOR THE DOOR THAT WILL BE INSTALLED.
  
 23) THE PRODUCT APPROVAL FOR THE TRACO SERIES 2100
 WINDOW IS MISSING THE FIRST PAGE OF THE DRAWINGS WHICH
 SPECIFIES THE DESIGN PRESSURES. THE STATE WEBSITE LISTS
 NOA # 05-0729.03 FOR THIS WINDOW. THE FL# IS 6585.
 SUBMIT COMPLETE PRODUCT APPROVALS.
  
 24) R301.2.1.2 INTERNAL PRESSURE.
 WINDOWS IN BUILDINGS LOCATED IN WIND-BORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WIND-BORNE DEBRIS OR THE BUILDING SHALL BE DESIGNED AS
 A PARTIALLY ENCLOSED BUILDING IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING . SUBMIT PRODUCT
 APPROVALS FOR THE STORM PANELS. SPECIFY THE OPENINGS
 THAT WILL BE SHUTTERED, THE FASTENER TYPE AND SPACING,
 THE CONNECTION TYPES, EDGE DISTANCE, ETC.
  
 25) PROVIDE THE FIRM LICENSE NUMBER OF THE
 ARCHITECTURAL/DESIGN FIRM LISTED IN THE TITLE BLOCK OF
 THE PLANS AS REQUIRED BY STATE STATUTES FS 471 AND
 481.
  
 26) ADDRESS COMMENT OF OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714