| Date |
Text |
| 2007-02-27 12:14:01 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. A NEW NOC WITH THE NEW |
| | CONTRACTOR'S NAME IS REQUIRED. |
| | |
| | 2) THE STRUCTURE IS 22'X 37' WHICH IS 814 SQFT. |
| | PLEASE REVISE SHEET A1. |
| | |
| | 3) THE WRONG ENERGY CALCULATION FORM WAS SUBMITTED. |
| | THIS IS A SINGLE FAMILY RESIDENCE. THE STRUCTURE IS 814 |
| | SQUARE FEET. |
| | |
| | 4) SPECIFY THE CEILING INSULATION ON THE PLANS. SPECIFY |
| | R VALUE. |
| | |
| | 5) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. |
| | ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 |
| | INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| | |
| | 6) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| | GRADE. |
| | CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND |
| | ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT |
| | ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY |
| | VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) |
| | ELSEWHERE |
| | |
| | 7) SHOW COMPLIANCE WITH SECTION 704 |
| | INSPECTION FOR TERMITES |
| | IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES (152 MM). |
| | EXCEPTIONS: |
| | 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS |
| | THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE |
| | MASONRY FOUNDATION SIDEWALL. |
| | 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE |
| | INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH |
| | RAMPS ONLY. |
| | 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO |
| | AND GARAGE SLABS AND ENTRY AREAS. |
| | 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES, |
| | THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR |
| | FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY. |
| | 5.MASONRY VENEERS. |
| | |
| | 8)SHOW COMPLIANCE WITH SECTION R319 PROTECTION |
| | AGAINST DECAY |
| | R319.1 LOCATION REQUIRED. |
| | IN AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY |
| | TABLE R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE |
| | THE USE OF AN APPROVED SPECIES AND GRADE OF LUMBER, |
| | PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3, |
| | C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2 |
| | AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK |
| | LOCUST, OR CEDARS. |
| | 5.WOOD SIDING, SHEATHING AND WALL FRAMING ON THE |
| | EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN |
| | 6 INCHES (152 MM) FROM THE GROUND. |
| | |
| | 9)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST |
| | TERMITES AND DECAY. CONDENSATE LINES AND ROOF |
| | DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY FROM |
| | THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND PIPING, |
| | TAIL EXTENSIONS OR SPLASH BLOCKS. GUTTERS WITH DOWN |
| | SPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS |
| | THAN 6 INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE |
| | END RAKES OR ON A ROOF ABOVE ANOTHER ROOF. |
| | |
| | 10)SECTION A-B ON S1 SHOULD SPECIFY CDX (EXTERIOR |
| | GRADE) PLYWOOD. PLEASE CORRECT. |
| | |
| | 11) PLEASE SPECIFY THAT THE NEW STUCCO IS TO BE APPLIED |
| | OVER METAL LATH WITH AN ACCEPTABLE MOISTURE BARRIER. |
| | SEE ASTM C 926, ASTM C 1063 AND FBC R703. |
| | |
| | 12)SPECIFY THE REQUIRED SOIL BEARING CAPACITY OF THE |
| | SOIL ON THE PLANS. |
| | |
| | 13) SECTION R806 |
| | ROOF VENTILATION |
| | |
| | 14) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 / |
| | 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM |
| | OPENINGS. |
| | |
| | 15)ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE |
| | WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC |
| | RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL |
| | BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT |
| | 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT |
| | INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS |
| | SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 |
| | MPH OR GREATER DESIGNWIND SPEEDS IN ACCORDANCE WITH |
| | FIGURE R803.2.3.1. REVISE NOTE ON S1. |
| | |
| | 16) SPECIFY THE SPACING OF THE ROOF TRUSSES ON THE |
| | PLANS. IF THE ROOF TRUSSES ARE 24" OC AND THE WALL STUD |
| | SPACING IS 16" OC, THE TS12 STRAPS THAT ARE SPECIFIED |
| | FROM THE STUDS TO THE TRUSSES WILL NOT WORK. |
| | |
| | 17) THE SIMPSON TS12 STRAPS THAT ARE SPECIFIED HAVE NO |
| | VALUE SPECIFIED IN THE CATALOG FOR LATERAL LOADS. |
| | |
| | 18) THE TRUSS DRAWINGS ARE REQUIRED TO HAVE THE |
| | ORIGINAL SIGNATURE OF THE TRUSS ENINEER. PHOTO COPIED |
| | SIGNATURES OR STAMPS ARE NOT ACCEPTABLE. SEE FS 471. |
| | |
| | 19)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 20) SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF |
| | COVERING. INDICATE WHICH ONE OF THE APPROVED ASSEMBLIES |
| | LISTED IN THE PRODUCT APPROVAL WILL BE INSTALLED. |
| | INDICATE THE FASTENING OPTION AND DESIGN PRESSURE THAT |
| | WILL BE USED. CIRCLE THE APPROPRIATE ITEMS ON THE |
| | PRODUCT APPROVALS. IF ENHANCED FASTENING IS REQUIRED |
| | FOR PERIMETER OR CORNER AREAS, SUBMIT RAS 117 |
| | CALCULATIONS. |
| | |
| | 21) GLAZED OPENINGS ARE REQUIRED TO HAVE IMPACT |
| | PROTECTION PER R301.2.1.2. THE PLANS INDICATE THAT THIS |
| | WILL BE DONE BY OTHERS UNDER A SEPARATE PERMIT. PLEASE |
| | NOTE THAT ADDITIONAL FEES WILL BE REQUIRED AND THIS |
| | PERMIT CAN NOT BE FINALED UNTIL THE STORM PANELS HAVE |
| | BEEN INSTALLED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |