| Plan Review Notes For Permit 06120431 |
| Permit Number |
06120431 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-26 13:20:46 | ***DENIED*** | | | | | | 1) WPB AMENDMENTS TO FBC 2004 EDITION REQUIRES WORK | | | VALUED AT GREATER THAN $5000.00 TO BE SIGNED, DATED AND | | | SEALED BY PROFESSIONAL ENGINEER. | | | | | | 2) SMOKE DUCT DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 3) FIRE ALARM THAT SUPERVISES A SPRINKLER SYSTEM TO BE | | | UL CERTIFIED FOR CENTRAL STATION SERVICE. CERTIFICATE | | | REQUIRED PRIOR TO OR AT THE TIME OF FINAL INSPECTION OF | | | FIRE ALARM SYSTEM. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | (561) 805-6722 OR 804-4756 |
|