| Plan Review Notes For Permit 06120405 |
| Permit Number |
06120405 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-18 14:54:59 | *** DENIED *** | | | 1) VALUE ON PERMIT APPLICATION MUST INCLUDE ALL | | | MATERIALS AND LABOR, PLEASE CORRECT VALUE OR WE WILL | | | NEED TO ADJUST IT USING MARSHALL & SWIFT BUILDING COST | | | REPORT, PER 2004 FBC WPB AMEND. 108.3. | | | | | | 2) PLEASE SUBMIT TWO COPY'S OF PLANS, ONLY ONE WAS | | | SUBMITTED. | | | | | | 3) PLEASE SUBMIT DETAILED MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR ROOF | | | TOP CONDENSER STANDS. | | | | | | 4) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-600.1.C.2. | | | | | | 5) NEED TO FILE A NOTICE OF COMMENCEMENT, PER F. S. | | | 713.13 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|