| Date |
Text |
| 2007-05-21 08:58:48 | *** DENIED *** |
| | 1) SEE TITLE BLOCK ON PLANS SHOW THE WRONG JOB ADDRESS, |
| | PLEASE CORRECT. |
| | |
| | 2) AS NOTED IN LAST TWO REVIEWS 3-12-07 NOTE #3 AND |
| | 12-19-07 NOTE #2. PLEASE SEE THE COOLING LOAD |
| | CALCULATIONS ARE CALLING FOR 13,331 SENSIBLE BTU'S, THE |
| | MECHANICAL PLANS ARE CALLING FOR 24,800 SENSIBLE BTU'S, |
| | THE PLANS CAN ONLY CALL FOR 15% MORE SENSIBLE BTU'S |
| | THAN THE COOLING LOAD CALCULATIONS, SEE 2004 FBC |
| | 13-607.1.ABC.1.1 (12-8-06 REVISION). PLEASE CORRECT. |
| | |
| | 3) AS NOTED IN LAST REVIEW 3-12-07 NOTE #5. SEE ENERGY |
| | CALCULATIONS #15 IS TAKING THE CF (CEILING FAN) CREDIT, |
| | ELECTRICAL PLANS SHOW FUTURE FANS, CREDIT MAY NOT BE |
| | TAKEN FOR FUTURE WORK, SEE 2004 FBC 13-607.2.A.3.1. |
| | PLEASE CORRECT. |
| | |
| | 4) ENERGY CALCULATIONS ARE FOR 2292 SQUARE FEET (BOTH |
| | UNITS) BUT LINES 12, 13, AND 14 SHOW ONLY ONE A/C |
| | SYSTEM, ONE HEATER AND ONE WATER HEATER, . WILL NEED TO |
| | SHOW TWO OF EACH OR SUBMIT TWO SEPARATE ENERGY |
| | CALCULATIONS FOR EACH UNIT AND CORRECT TOTAL SQUARE |
| | FEET, PLEASE CORRECT. |
| | |
| | 5) ENERGY CALCULATIONS LINE 12 SHOWS 29,200 TOTAL |
| | COOLING BTU'S., MECHANICAL PLANS EQUIPMENT LISTING |
| | SHOWS 33,200 TOTAL COOLING BTU'S., THE TWO MUST |
| | COINCIDE PLEASE CORRECT. |
| | |
| | 6) ENERGY CALCULATIONS LINE 13 SHOWS 34.000 TOTAL |
| | HEATING BTU'S., MECHANICAL PLANS SHOW 24,000 TOTAL |
| | HEATING BTU'S., THE TWO MUST COINCIDE PLEASE CORRECT. |
| | |
| | 7) PLEASE SEE ELECTRICAL REVIEW NOTE #1 AS THIS ALSO |
| | APPLIES TO THE MECHANICAL REVIEW. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |