| 2007-03-09 19:00:58 | ** UNSAT 2ND REVIEW ** |
| | |
| | |
| | ** PLEASE SEE THERE ARE MANY COMMENTS FROM THE PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH |
| | SEVERAL NEW COMMENTS DUE TO CHANGES IN THE PLANS |
| | SUBMITTED. |
| | |
| | ** PLEASE KNOW A RESPONSE LETTER FROM THE DESIGN |
| | PROFESSIONAL IS MOST HELPFUL IN THE REVIEW PROCESS. |
| | |
| | *** PLEASE ALSO KNOW DUE TO THE PLANS NOT BEING |
| | COMPLETE AT THIS TIME AND THE FOLLOWING COMMENTS FOR |
| | PLANS SUBMITTED, THERE MAY BE COMMENTS ON NEXT REVIEW |
| | WHICH ARE NOT ON THIS REVIEW. |
| | **DUE TO THE EXTENT OF THE ELECTRICAL COMMENTS AND |
| | OTHER COMMENTS BASED ON LICENSING, ONE SET OF THE |
| | ELECTRICAL PLANS ARE ONCE AGAIN BEING RETAINED. PLEASE |
| | SEE NEW COMMENTS ADDED TO THIS REVIEW AND COMMENT WITH |
| | RESPECT TO FLORIDA STATUTES FOR REPEAT COMMENTS. |
| | |
| | 1) NOTE:PLEASE SEE THIS MOSTLY THE SAME COMMENT. ONLY |
| | A NEW SEAL WAS USED WHEN PLANS WERE SIGNED AND SEALED. |
| | PLEASE SEE THAT THE MISSING CA # IS STILL NOT ON ANY |
| | TITLE BLOCKS. PLEASE SEE THE PRINTED NAME IS NOT THE |
| | SAME AS IN SEAL. PLEASE SEE NO LETTER FOR SIGNATURE |
| | VERIFICATION WAS SUBMITTED. PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 FOR MISSING LICENSING |
| | INFORMATION REQUIRED. PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER AND SOME SHEETS ARE NOT COMPLETE |
| | WITH OTHER INFORMATION AS REQUIRED. |
| | FLORIDA STATUTES 471.023 |
| | PLEASE SEE PLANS SEEM TO BE SIGNED WITH AN INITIAL OF |
| | SOME SORT. IF THIS IS INDEED THE LEGAL SIGNATURES OF |
| | THE DESIGNER OF RECORD PLEASE PROVIDE A SIGNED, DATED |
| | AND SEALED LETTER WITH STATEMENT OF LEGAL SIGNATURE. |
| | PLEASE BE SURE LETTER IS PROPERLY NOTARIZED UNDER |
| | FLORIDA STATUTES 117.05. |
| | PLEASE KNOW THIS LETTER WILL BE PLACED IN OUR SIGNATURE |
| | FILE FOR ANY FUTURE REFERENCE AS NEEDED AND WILL NOT BE |
| | NEED TO PROVIDE LETTER ON FUTURE PROJECTS. |
| | ** PLEASE KNOW, THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADE REVIEWS WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE SEE ONLY THE 2005 NEC WAS ADDED TO |
| | PLANS. PLEASE SEE THE CODES WHICH WERE REQUESTED FOR |
| | OTHERS WERE NOT ADDED. PLEASE SEE THAT ALL PLANS SHALL |
| | STATE THE CODE IN WHICH THEY ARE DESIGNED UNDER. THIS |
| | IS SUBMITTED UNDER THE NEW CODES. 2004 FBC W/ THE 2006 |
| | REVISIONS. |
| | |
| | PLEASE SEE THE FOLLOWING CODES SHALL BE STATED ON |
| | PLANS. |
| | NFPA-70 2005, 2002 NFPA-72 |
| | PLEASE KNOW BASED ON THE FACT THAT THE PLANS WERE |
| | SUBMITTED FOR PERMITTING AFTER THE DATE OF DEC 8TH, |
| | 2006, THE PLANS SHALL BE DESIGNED UNDER THE 2005 NEC. |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PLANS SUBMITTED. |
| | PLEASE SEE PLANS DO NOT INDICATE GROUPING OF MAINS AS |
| | RISER SEEMS TO SHOW. PLEASE SEE MISSING SERVICE |
| | ENTRANCE CONDUCTORS FOR NEW RISER. |
| | PLEASE SEE THE RISER AS SHOWN IS NOT CODE COMPLIANT |
| | WITH SEVERAL SECTIONS OF THE NEC. PLEASE SEE OTHER |
| | COMMENTS RELEVANT TO THE RISER. |
| | THIS IS ONE *BUILDING* BY DEFINITION IN THE FBC AND |
| | ONLY ONE SERVICE PER 230.2 WILL BE GRANTED. PLANS SHOW |
| | TWO DIFFERENT LOCATIONS/SERVICE METERS. |
| | 230.70, 230.72, 240.4, 310.16, 310.15B6, ETC. PLEASE |
| | SEE THE SIZE OF THE METER CAN, CAN NOT BE VERIFIED AS |
| | NO LOAD CALCULATIONS WERE SUBMITTED. FBC 106.1.2, |
| | 106.3.5.4(PARA 8) ADMIN SECTION. THERE ARE CURRENTLY |
| | MANY SECTIONS BESIDES THE ONES NOTED BELOW WHICH COULD |
| | NOT BE ALL TYPED IN THIS REVIEW. |
| | |
| | 4) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| | REVIEW. |
| | PLEASE SEE 250.6, 250.24B AS NO EQUIPMENT GROUNDING |
| | CONDUCTORS ARE PERMITTED BEFORE THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 5) NOTE: THIS IS THE SAME COMMENT FROM PREVIOUS REVIEW. |
| | PLEASE SEE AS THE SERVICE IS NOT COMPLETE AND THE |
| | SERVICE ENTRANCE CONDUCTORS ARE NOT SHOWN REVIEW FOR |
| | CODE COMPLIANCE CAN NOT BE DONE. BASED ON THE SIZE OF |
| | THE GEC AS SHOWN IT DOES NOT MEET THE SECTION OF THE |
| | CODE PREVIOUSLY GIVEN. |
| | PLEASE SEE 250.66 AS THE SIZE OF SERVICE MAY CHANGE |
| | WHICH WILL DICTATE THE SIZE OF THE GROUNDING ELECTRODE |
| | CONDUCTOR. |
| | |
| | 6) NOTE: NO, PLEASE SEE ONLY THE BRACE RATING AND |
| | BRANCH CIRCUIT RATING IS BEING SHOWN. |
| | PLEASE SUBMIT THE AIC RATINGS FOR SERVICE MAINS PER |
| | 110.9. |
| | PLEASE SEE THE RATING AS SHOWN ON PANEL SCHEDULE WAS |
| | NOTED, HOWEVER NEEDED FOR MAIN(S). |
| | |
| | 7) NOTE:THIS IS THE SAME COMMENT. PANEL SCHEDULE IS |
| | COMPLETELY BLANK FOR LOAD CALCULATIONS AND FOR LOAD ON |
| | SERVICE FOR EACH PANEL AND SERVICE AS SHOWN ON RISER. |
| | PLEASE COMPLETE AND SUBMIT A COMPLETE PANEL SCHEDULE |
| | WITH ALL MINIMUM REQUIRED DEDICATED LOADS AS WELL AS |
| | COMPLETED LOAD CALCULATIONS BASED ON MINIMUM |
| | REQUIREMENTS FROM THE NEC. |
| | PLEASE SEE 220.40, 220.82, 220.52, 220.54, 220.60, ETC, |
| | ETC. |
| | FBC ADMIN SECTION 106.3.5.4 |
| | |
| | 8) NOTE: THIS IS THE SAME COMMENT AS THE PANEL SCHEDULE |
| | STILL INDICATE THE DEDICATE BATH RECEPTACLE CIRCUIT ON |
| | WITH GARAGE RECEPTACLES. PLEASE SEE PLANS AS PLANS DO |
| | NOT INDICATE ANY KIND OF GARAGE?? |
| | PLEASE SEE 210.52D, 210.11C3, AS NO OTHER LOADS ARE |
| | PERMITTED ON THE DEDICATED BATH CIRCUIT(S). |
| | |
| | 9) NOTE: THIS IS THE SAME COMMENT. |
| | PLEASE SEE 210.52C1 FOR MISSING REQUIRED GFI'S ALONG |
| | KITCHEN COUNTER SPACE. |
| | MISSING MINIMUM VA 220.52 |
| | |
| | 10) NOTE:THIS IS THE SAME COMMENT.PLEASE SEE THAT |
| | THE PANEL SCHEDULE INDICATES THE DINING ROOM |
| | RECEPTACLES ON WITH LIGHTING AND MANY OTHER AREAS WHICH |
| | ARE NOT PERMITTED. |
| | NO INFORMATION WAS SUBMITTED. |
| | PLEASE SEE MISSING REQUIRED CIRCUITING FOR DINING ROOM |
| | RECEPTS PER 210.52B1, 210.11C1, AND 220. 52B. |
| | |
| | 11) NOTE:THIS COMMENT WILL REMAIN AS NOTED ABOVE IN |
| | NOTE #9 THERE ARE RECEPTACLES ALONG KITCHEN COUNTER |
| | SPACE WHICH ARE STILL MISSING. |
| | PLEASE SEE 210.8A6, AS ALL RECEPTS ALONG KITCHEN |
| | COUNTER SPACE SHALL BE SHOWN AS GFI. |
| | |
| | 12) NOTE: THIS COMMENT REMAINS AS THE MINIMUM |
| | CLEARANCES IN SOME OF THE CLOSETS ARE NOT MET. PLEASE |
| | SEE 410.8 AS THE PC LIGHTING IN CLOSETS ARE NOT |
| | PERMITTED AS SHOWN. THEY DO NOT MEET MINIMUM |
| | CLEARANCES. |
| | |
| | 13) NOTE: PLEASE GO OVER PLANS AS SCALE STILL SEEMS TO |
| | SHOW SOME NOT SPACED PER 210.52 |
| | PLEASE SEE MISSING RECEPTS PER 210.52 FOR WALL |
| | SPACES. |
| | |
| | 14) NOTE:THIS COMMENT IS FROM PREVIOUS REVIEW. PLEASE |
| | SEE ALL SMOKE DEVICES ARE STILL BEING SHOWN AS *SMOKE |
| | DETECTORS* AND SYMBOL LEGEND EVENS STATES AND SHOWS |
| | THESE BEING 110V UNITS WHICH THESE WOULD BE *SMOKE |
| | ALARMS* |
| | PLEASE SEE ALL SMOKE DEVICES SHALL BE SHOWN AS DEFINED |
| | IN NFPA-72. PLEASE SEE IF THESE DEVICES AS SHOWN ARE |
| | PART OF A LOW VOLTAGE ALARM SYSTEM WHICH CONTAINS |
| | HORN/ALARM DEVICES THEN THE SD AS SHOWN FOR SMOKE |
| | DETECTOR IS OK. IF THESE DEVICES AS SHOWN ARE DETECT |
| | AND SOUND AN ALARM, THEN THEY SHALL BE SHOWN AS SA FOR |
| | SMOKE ALARMS. |
| | PLEASE ALSO SEE NFPA-72 11.5.1.1, 11.8.3 FOR LOCATIONS |
| | REQUIRED INSIDE AND OUTSIDE ALL SLEEPING ROOMS. PLEASE |
| | SEE SOME ROOMS DO NOT INDICATE THE DEVICE OUTSIDE THE |
| | SLEEPING ROOM, YET INDICATE TWO DEVICES INSIDE ROOM? |
| | PLEASE SEE OTHER ROOMS WHICH DO INDICATE A DEVICE |
| | OUTSIDE ROOM, BUT STILL INDICATE TWO OR MORE INSIDE?? |
| | |
| | 15) NOTE: THIS COMMENT IS THE SAME. NO CORRECTION WAS |
| | MADE. |
| | PLEASE SEE MISSING DISCONNECTS FOR ALL A/C EQUIPMENT. |
| | PLEASE SEE 440.11. |
| | PLEASE SEE AHU CLOSET APPEARS TO SHOW TWO RECEPTS. |
| | PLEASE KNOW AS PER 422.31, AHU'S SHALL NOT BE PLUGGED |
| | IN. |
| | |
| | 16) NOTE: THIS IS THE SAME COMMENT. |
| | PLEASE SEE 422.31 FOR DISCONNECTING MEANS REQUIRED FOR |
| | WATER HEATER(S). |
| | |
| | 17) NOTE: OK. |
| | |
| | 18) NOTE: OK. |
| | |
| | ** NEW NOTES** |
| | |
| | 19) NOTE: PLEASE SEE SEVERAL ELECTRICAL DEVICES ON |
| | PLANS WHICH ARE MISSING CIRCUITING. THERE ARE MANY |
| | ITEMS WHICH NEED CIRCUITING TO REVIEW FOR CODE |
| | COMPLIANCE. |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 20) NOTE: PLEASE SEE MISSING ARC FAULT PROTECTION FOR |
| | ALL OUTLETS IN BEDROOMS. 210.12 THIS IS NOT ONLY |
| | REQUIRED FOR RECEPTACLES. |
| | |
| | 21) NOTE: PLEASE SEE SOME RECEPTACLES ARE NOT BEING |
| | SHOWN SWITCHING THE ENTIRE RECEPTACLES WHICH IS OK, |
| | HOWEVER AS NOTED ABOVE PER 210.52, THEN RECEPTACLES |
| | WOULD BE REQUIRED IN ADDITION FOR GENERAL PURPOSE. |
| | |
| | 22) NOTE: PLEASE SEE PLANS APPEAR TO NOW HAVE ONE NEW |
| | RECEPTACLE FOR WHAT APPEARS TO BE FOR THE DISHWASHER |
| | AND DISPOSAL BUT IT IS UNCLEAR AS ONE UNIT SHOWS THIS |
| | OUTLET AS GFI AND THE OTHER NOT GFI PROTECTED. PLEASE |
| | SEE 210.4, IF THESE ARE ON THE SAME YOKE/DEVICE THEN A |
| | 2-POLE BREAKER IS REQUIRED. |
| | PLEASE ALSO SHOW AND IDENTIFY THE RECEPTACLE FOR THESE |
| | ON PLANS. |
| | |
| | 23) NOTE: PLEASE SHOW ALL ROOM AND AREA DESIGNATIONS ON |
| | PLANS IN ORDER TO REVIEW SOME CIRCUITING FOR CODE |
| | COMPLIANCE. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 24) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR |
| | CODE COMPLIANCE. |
| | PLEASE KNOW THAT DUE TO THE AMOUNT OF ELECTRICAL |
| | COMMENTS PLANS WILL BE RETAINED BY THIS OFFICE. PLEASE |
| | KNOW PLANS WILL BE SUBMITTED TO THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS FOR REVIEW ITEMS ON PLANS AND |
| | MISSING LICENSE AS REQUIRED UNDER THE FLORIDA STATUTES |
| | AND FLORIDA ADMINISTRATIVE CODE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |