| 2007-03-19 19:03:03 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTES. |
| | |
| | 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY SEC. R401.3 |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 3- ENGINEER TO PROVIDE ALL HIS INFORMATION IN THE TITLE |
| | BLOCK AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES AND |
| | FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| | INCLUDING ENGINEERING FIRM'S CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | ***NOTE: ENGINEER'S NAME DOESN'T MATCH ENGINEER'S NAME |
| | SHOWN ON EMBOSSED SEAL. |
| | |
| | 4- SHEET SP-1: |
| | A) REVISE ALL DRIVEWAY AND APPROACH NOTES. CONTACT |
| | CITY OF WEST PALM BEACH ENGINEERING DEPARTMENT AT |
| | (561)494-1040 FOR CITY STANDARDS. |
| | |
| | B) REVISE SIZE OF PARKING SPACES.NUMBER AND SIZE |
| | OF PARKING SPACES DON'T MATCHNOTES AT BOTTOM OF |
| | SHEET. THERE IS NOT ENOUGH ROOM TO BACK UP.CHECK |
| | SPECIFIED SIZES: 14'-0" X 18'-0"?. SEE ZONING |
| | COMMENTS. |
| | |
| | C) SHOW ALL BUILDING SETBACKS TO VERIFY COMPLIANCE |
| | WITH SEC. R302 2004 FLORIDA RESIDENTIAL CODE AND TABLE |
| | 704.8 2004 FBC. |
| | |
| | D) CLEARLY IDENTIFY PROPERTY LINES.SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- PROVIDE SOIL TEST REPORT (2 COPIES). |
| | |
| | 6- SHEET S-1: |
| | A) COLUMN SCHEDULE AND TYPICAL NOTES IN FOUNDATION |
| | PLANS DON'T MATCH.REVISE AS REQUIRED. |
| | |
| | B) 4" DROP IS SHOWN ON MASTER BEDROOM WINDOW INSTEAD |
| | OF BEING SHOWN FOR ENTRY DOOR. REVISE AS REQUIRED. |
| | |
| | C) FOUNDATION NOTES AND SPECIFICATIONS SHOWN ON |
| | FOUNDATION PLAN FOR WIRE MESH SIZE DON'T MATCH. REVISE |
| | AS REQUIRED. |
| | |
| | D) DETAIL F2 DOESN'T APPLY TO THIS PROJECT.THIS IS |
| | NOT WOOD FRAMING. SEE TYPE OF INTERIOR BEARING WALL. |
| | |
| | E) FOOTING SCHEDULE SHOWS FOOTING F2 WITH 3 #5 BARS |
| | AT THE BOTTOM, WHILE DETAIL F2 SHOWS 2 #5 AT BOTTOM AND |
| | 1 #5 AT TOP. REVISE AS REQUIRED. |
| | |
| | F) CLARIFY FOOTING SIZE F2. FOOTING SCHEDULE CALLS |
| | FOR 24"X12", WHILE INTERIOR BEARING WALL SECTION ON |
| | SHEET A-4 CALLS FOR 12" X 24".WHICH DIMENSION IS THE |
| | WIDTH AND WHICH IS THE DEPTH OF THE FOOTING. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | G) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS |
| | PROJECT TO AVOID CONFUSIONS/CONFLICTS AND EXPEDITE |
| | REVIEW PROCESS. |
| | |
| | H) DETAIL F1: SPECIFY FOOTING EMBEDMENT BELOW GRADE |
| | TO VERIFY COMPLIANCE WITH SEC. R403.1.4 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | I) WINDOW DETAIL: |
| | * WHY SHOWING SHUTTERS DETAILS IF WINDOW NOTES ON |
| | SHEET A-1 CALLS FOR IMPACT GLASS?. |
| | ** WHY SHUTTER DETAIL SHOWS ATTACHMENT OF SHUTTER |
| | TRACK TO CONCRETE SLAB IF THIS IS A WINDOW DETAIL? *** |
| | REVISE BUCK DETAIL. SEE SEC. R613.6.2 2004 FLORIDA |
| | RESIDENTIAL CODE FOR PROPER WAY OF ATTACHING BUCKS. |
| | |
| | J) ENGINEER TO PROVIDE CALCULATIONS SHOWING HOW |
| | VERTICAL REINFORCING SHOWN IN FOUNDATION PLAN WILL |
| | PROVIDETHE REQUIRED LATERAL SUPPORT OF THIS BUILDING. |
| | SEE PLANS FOR VERTICAL REINFORCEMENT SPACING. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004 AND SEC. 1609 FBC |
| | 2004. |
| | |
| | K) DIMENSIONS SHOWN ON FOUNDATION PLANAND |
| | LOCATIONS OF COLUMNS DON'T MATCH REVISE AS REQUIRED. |
| | |
| | 7- SHEET A-1: |
| | A) PROVIDEDIMENSIONSFOR ENTRY PORCH TO DETERMINE |
| | TOTAL PORCH AREA.BUILDING PERMIT VALUATION WILL BE |
| | ESTIMATED AFTER SQUARE FOOTAGE ISCLARIFIED. |
| | |
| | B) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL. SPECIFY |
| | ALL BUCK FASTENERS AND SEESEC. R613.6.2 2004 FLORIDA |
| | RESIDENTIAL CODE FOR PROPER BUCK INSTALLATION. BUCK |
| | NEEDS TO PROVIDE FULL SUPPORT TO THE WINDOW/DOOR. |
| | |
| | C) SOME ROOMS DON'T HAVE COMPLETE SPECS FOR SIZE OF |
| | AND TYPE OF WINDOWS.PROVIDE COMPLETE INFORMATION. |
| | ALSO, SIZE OF WINDOWS ARE NOT DONE TO SCALE AND DON'T |
| | MATCH EXTERIOR ELEVATIONS EITHER.REVISE AS REQUIRED. |
| | |
| | 8- SHEET A-2: |
| | A) CLARIFY NOTE REGARDING BAHAMA SHUTTERS ON 14TH |
| | STREET ONLY. ALL ELEVATIONS SHOW COLONIAL SHUTTERS. |
| | INFORMATION IS MISLEADING. |
| | |
| | C) ELEVATIONS DON'T MATCH FLOOR PLAN.SEE REVISED |
| | FLOOR PLAN FOR SIZE OF WINDOWS. REVISE AS REQUIRED. |
| | |
| | D) PROVIDE COMPLETE STRUCTURAL INFORMATION FOR |
| | OVERHANG ABOVE ENTRY AREA. PROVIDE COMPLETE STRUCTURAL |
| | SECTION/DETAIL WITH COMPLETE SPECIFICATIONS, |
| | DIMENSIONS, HEIGHT, ETC.SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | E) WINDOW SCHEDULE DOESN'T MATCH FLOOR PLAN. REVISE |
| | AS REQUIRED. |
| | |
| | 9- SHEET A-3: |
| | A) PROVIDE ONLY THE INFORMATION THAT IS RELEVANT TO |
| | THIS PROJECT. THERE ARE A LOT OF NOTES AND TABLES THAT |
| | DON'T APPLY TO THIS PROJECT. |
| | |
| | B) PIGGY BACK TRUSS DETAIL: |
| | * IS THIS THE DETAIL FOR ENTRY PORCH? |
| | ** WHERE ARE THE RIGHT HAND SIDE TRUSSES SUPPORTED |
| | ON?. THERE IS NOT BEAM TO SUPPORT THEM.DETAIL IS |
| | INCOMPLETE AND WRONG. PROVIDE COMPLETE SECTION DETAIL. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | C) TRUSS CONNECTOR SCHEDULE AND CONNECTORS SPECIFIED |
| | ON ROOF FRAMING PLAN DON'T MATCH. REVISE AS REQUIRED. |
| | |
| | D) REVISE NUMBER AND TYPE OF FASTENERS SPECIFIED ON |
| | TRUSS CONNECTOR SCHEDULE. SEE CURRENT CATALOG FOR |
| | UPDATED INFORMATION. OTHERWISE, ENGINEER TO PROVIDE |
| | COMPLETE ENGINEERING ANALYSIS SHOWING WHY CONNECTORS |
| | ARE DIFFERENT THAN THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | E) MANUFACTURER FOR CONNECTORS SPECIFIED ON ROOF |
| | FRAMING PLAN IS OUT OF BUSINESS. REVISE AS REQUIRED. |
| | |
| | F) CLEARLY IDENTIFY TRUSSES FOR WHICH UPLIFT |
| | PRESSURES WERE CALCULATED. |
| | |
| | G) ENGINEER TO COORDINATE ALL NOTES AND CHARTS SHOWN |
| | ON THIS DRAWINGS. THERE IS A LOT OF MIXED INFORMATION |
| | THAT NEEDS TO BE COORDINATED.SEE 2004 FLORIDA |
| | RESIDENTIAL CODE AND ALLINFORMATION SUBMITTED IN THIS |
| | SHEET.PROVIDE ONLY THE REQUIRED INFORMATION.SEE |
| | SECTIONS . R301 2004 FLORIDA RESIDENTIAL CODE. ALSO, |
| | SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE |
| | FOR MINIMUM REQUIREMENTS FOR ROOF SHEATHING. REVISE AND |
| | COORDINATE ALL INFORMATION IN SHEET A-3 TO MATCH. |
| | |
| | H) PNEUMATIC FASTENING SCHEDULE: PROVIDE ONLY THE |
| | INFORMATION THAT APPLIES TO THIS PROJECT.CHECK/REVISE |
| | SPACING FOR BUCK DETAILS FASTENING. INFORMATION DOESN'T |
| | MATCH. ALSO, COORDINATE WITH PROVIDED BUCK DETAIL. |
| | |
| | I) ROOF FRAMING PLAN CALLS DWELLING SEPARATION WALL |
| | A "FIRE WALL".SEEFBC 2004 FOR CORRECT DEFINITION |
| | FOR "FIRE WALL" AND REVISE AS REQUIRED. |
| | |
| | J) PROVIDE COMPLETE SECTION THRU DWELLING SEPARATION |
| | WALL TO SHOW COMPLIANCE WITH SEC. R317.1 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | K) REVISE ATTIC VENTILATION CALCULATIONS AND NOTES |
| | SEE SEC. R806 2004 FLORIDA RESIDENTIAL CODE FOR PROPER |
| | INFORMATION. |
| | |
| | L) ROOF FRAMING PLAN DOESN'T MATCH EXTERIOR |
| | ELEVATIONS. SEE ENTRY PORCH. REVISE AS REQUIRED. |
| | |
| | |
| | 10- PRIOR TO SUBMITTAL TO THIS OFFICE BRING PLANS FOR |
| | HISTORICAL APPROVAL AFTER CORRECTIONS ARE DONE TO THE |
| | PLANS. |
| | |
| | 11- SHEET A-4: |
| | A) REVISE INTERIOR BEARING WALL TO MATCH FLOOR PLAN. |
| | REVISE SIZE OF FOOTING, WALL CONSTRUCTION, ETC. |
| | * WHAT'S THE BEAM SHOWN ON TOP OF WALL? |
| | ** HOW ARE TRUSSES RESTING ON THIS WALL. SEE ROOF |
| | FRAMING PLAN. |
| | *** WHAT'STHE HOOK SHOWN AT THE BOTTOM OF WALL |
| | CONNECTING TO FOOTING. PROVIDECOMPLETE SPECS. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | B) SPECIFY FIREBLOCKING ON INTERIOR BEARING WALL |
| | SECTION AS REQUIRED BY SEC. R602.8 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | C PROVIDE DETAIL/SPECS FOR DWELLING SEPARATION AT |
| | ATTIC AREA. SEC. R317.1 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | D) PROVIDE ALL DESIGN CRITERIA, INCLUDING ALL WIND |
| | LOADS, AND LIVE AND DEAD LOADS. REFERENCE 2004 FLORIDA |
| | RESIDENTIAL CODE,WHICH IS THE CODE THAT REGULATES |
| | THIS BUILDING, NOT SECTIONS 1606 OF FBC 2004. SEE SEC. |
| | R301 AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | REVISE AS REQUIRED. INCLUDE ALL ATTIC LIVE LOADS. |
| | |
| | E) PLYWOOD NAILING NOTES TO MATCH INFORMATION ON |
| | SHEET A-3 AFTER APPROPRIATE REVISIONS ARE DONE. |
| | |
| | F) TYPICAL WALL SECTION: |
| | *WHAT IS 2"X4" STRIP?. IS IT FIREBLOCKING?. ALSO, |
| | VERIFY SIZE WITH SIZE OF FURRING STRIPS FOR DRYWALL |
| | INSTALLATION. |
| | **WHAT IS 325# SHINGLES? |
| | *** ROOF SHEATHING SIZE AND TYPE TO MATCH |
| | INFORMATION ON SHEET A-3 AFTER APPROPRIATE REVISIONS |
| | ARE DONE. |
| | **** TRUSS CONNECTOR TO MATCH INFORMATION ON SHEET |
| | A-3 AFTER APPROPRIATE REVISIONS ARE DONE. |
| | ***** SPECIFY FOOTING MIN. DEPTH AS REQUIRED BY SEC. |
| | R 403.1.4 2004 FLORIDA RESIDENTIAL CODE. |
| | ****** SPECIFY MINIMUM FINISH FLOOR AS REQUIRED BY |
| | SEC. R404.1.6 2004 FLORIDA RESIDENTIALCODE. |
| | |
| | G) TRUSS/ WOOD CONNECTOR SCHEDULE DOESN'T APPLY TO |
| | THIS PROJECT AND IS USING CONNECTORS THAT NO LONGER |
| | EXIST. COMPANY IS OUT OF BUSINESS. |
| | ALSO, ROOFTILE INFORMATION DOESN'T APPLY. |
| | |
| | |
| | 12- ENERGY CALCULATIONS: |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. |
| | |
| | B) THIS IS NOT A SINGLE FAMILY DETACHED BUILDING. |
| | SEE CHAPTER 13 2004 FBC FOR PROPER TYPE OF BUILDING. |
| | AND, NEED ENERGY CALCULATIONS FOR EACH DWELLING.SEE |
| | DEFINITIONS ON SUBCHAPTER13-2 OF 2004 FBC. REVISE AS |
| | REQUIRED.SEE SEC. 15-101.2.5.1 FBC 2004. |
| | |
| | C) IF CALCULATIONS ARE NOT DONE FOR WORST CASE |
| | SCENARIO, THEN THEY SHALL BE DONE ON ACTUAL BUILDING |
| | ORIENTATION.ENERGY CALCULATIONS SUBMITTED ARE NOT FOR |
| | WORST CASE SCENARIO AND BUILDING ORIENTATION DON'T |
| | MATCH ACTUAL BUILDING ORIENTATION. SEE SURVEY AND |
| | REVISE AS REQUIRED. |
| | |
| | D) OVERHANG LENGTH AND HEIGHT ARE INCORRECT.THEY |
| | CAN'T BE ZERO. REVISE AS REQUIRED. |
| | |
| | 13- ENERGY CALCULATIONS ARE TAKINGTHE CEILING FAN |
| | CREDIT. THEREFORE NEED TO SPECIFY CEILING FAN SIZE IN |
| | ALL ROOMS AS REQUIRED BY TABLE 13-607.1.A.1 FBC 2004. |
| | |
| | 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) SINGLE HUNG WINDOWS.TWO DIFFERENT PRODUCT |
| | APPROVALS WERE SUBMITTED. ONLY THE ONE FOR LARGE |
| | MISSILE IMPACT CAN BE USED FOR OPENINGS BELOW 30'-0" |
| | HIGH. PROVIDE 2 COPIES. |
| | |
| | B) SHINGLES. |
| | |
| | C) BAHAMA SHUTTERS AND COLONIAL SHUTTERS SHOWN ON |
| | EXTERIOR ELEVATIONS. AND PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED INSTALLATION SCHEDULE SAMPLE. |
| | PROVIDE ALL REQUIRED INFORMATION. |
| | |
| | D) PRECAST LINTELS. |
| | |
| | E) ENTRY DOORS. |
| | |
| | F) REAR DOORS. |
| | |
| | G) ALL STRUCTURAL SIMPSON OR USP CONNECTORS |
| | SPECIFIED ON PLANS ANDDETAILS. |
| | |
| | |
| | 15- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 16- DUPLEX REQUIRES TWO SEPARATE ADDRESSESAND PLANS |
| | NEED TO BE REVISED SHOWING CORRECT ADDRESS.PLEASE |
| | CONTACT LILLY URSU AT (561)822-1239 TO GET CORRECT |
| | ADDRESS. |
| | |
| | 17- PROVIDE SURVEYS (TWO) SHOWING REVISED PARKING |
| | SPACES.NOTE: ORIGINAL SEAL AND SIGNATURE. |
| | |
| | 18- ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE |
| | REGARDING REVIEW OF DESIGN PROFESSIONAL DOCUMENTS. |
| | |
| | |
| | ***NOTE: |
| | ONE COPY OF PLANS WILL BE SEND TO THE BOARD OF |
| | ENGINEERS FOR THEIR REVIEW. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |