| Plan Review Notes For Permit 06120402 |
| Permit Number |
06120402 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-26 09:01:47 | DENIED; | | | 1. CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED TO | | | BE IN THE TITLE BLOCK SEE FAC 61G15-23.002. | | | 2. SANITARY RISER DIAGRAM DOES NOT MATCH FLOOR PLAN. | | | A. MISSING PLUMBING FIXTURE (LAVATORY) | | | B. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE | | | 3" SECTION 406.3 | | | C. ALL BATHROOMS HAVE TUBS NOT SHOWERS. | | | D. PLEASE INDICATE IF EACH UNIT HAS IT'S OWN | | | SEWER CONNECTION. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|