| 2006-12-17 16:22:02 | *** UNSAT *** |
| | |
| | *** PLEASE KNOW DUE TO THE PLANS NOT BEING COMPLETE AT |
| | THIS TIME AND ALSO THE FOLLOWING COMMENTS FOR PLANS |
| | SUBMITTED, THERE MAY BE COMMENTS ON NEXT REVIEW WHICH |
| | ARE NOT ON THIS REVIEW. |
| | **DUE TO THE EXTENT OF THE ELECTRICAL COMMENTS AND |
| | OTHER COMMENTS BASED ON LICENSING, ONE SET OF THE |
| | ELECTRICAL PLANS ARE BEING RETAINED BY THIS OFFICE. |
| | |
| | 1) NOTE:PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002 FOR MISSING LICENSING INFORMATION |
| | REQUIRED. PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER AND SOME SHEETS ARE NOT COMPLETE |
| | WITH OTHER INFORMATION AS REQUIRED. |
| | FLORIDA STATUTES 471.023 |
| | PLEASE ALSO SEE 61G15-23.001 FOR MINIMUM SIZE OF SEAL. |
| | THE SIZE AS SHOWN ON PLANS DO NOT APPEAR TO BE LARGE |
| | ENOUGH? |
| | PLEASE SEE PLANS SEEM TO BE SIGNED WITH AN INITIAL OF |
| | SOME SORT. IF THIS IS INDEED THE LEGAL SIGNATURES OF |
| | THE DESIGNER OF RECORD PLEASE PROVIDE A SIGNED, DATED |
| | AND SEALED LETTER WITH STATEMENT OF LEGAL SIGNATURE. |
| | PLEASE BE SURE LETTER IS PROPERLY NOTARIZED UNDER |
| | FLORIDA STATUTES 117.05. |
| | PLEASE KNOW THIS LETTER WILL BE PLACED IN OUR SIGNATURE |
| | FILE FOR ANY FUTURE REFERENCE AS NEEDED AND WILL NOT BE |
| | NEED TO ROVIDE LETTER ON FUTURE PROJECTS. |
| | ** PLEASE KNOW, THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADE REVIEWS WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| | ON PLANS. |
| | NFPA-70 2005, 2002 NFPA-72 |
| | PLEASE KNOW BASED ON THE FACT THAT THE PLANS WERE |
| | SUBMITTED FOR PERMITTING AFTER THE DATE OF DEC 8TH, |
| | 2006, THE PLANS SHALL BE DESIGNED UNDER THE 2005 NEC. |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PLANS SUBMITTED. |
| | PLANS AND PERMIT APPLICATION IS FOR A DUPLEX DWELLING |
| | UNIT TO BE BUILT, (NOT YET APPROVED OR DISAPPROVED BY |
| | ZONING) YET RISER SHOWS SINGLE METER AND PLANS SHOW |
| | TWO? |
| | PLEASE SEE RISER AS SHOWN MAY NOT FEED PANELS AS SHOWN. |
| | PLEASE SEE 240.21C FOR TAPPED CONDUCTORS. |
| | PLEASE SEE THE SIZE OF THE METER CAN, CAN NOT BE |
| | VERIFIED AS NO LOAD CALCULATIONS WERE SUBMITTED. FBC |
| | 106.1.2, 106.3.5.4(PARA 8) ADMIN SECTION. THERE ARE |
| | CURRENTLY MANY SECTIONS BESIDES THE ONES NOTED BELOW |
| | WHICH COULD NOT BE ALL TYPED IN THIS REVIEW. |
| | |
| | 4) NOTE: PLEASE SEE 250.6, 250.24B AS NO EQUIPMENT |
| | GROUNDING CONDUCTORS ARE PERMITTED BEFORE THE FIRST |
| | MEANS OF DISCONNECT. |
| | |
| | 5) NOTE: PLEASE SEE 250.66 AS THE SIZE OF SERVICE MAY |
| | CHANGE WHICH WILL DICTATE THE SIZE OF THE GROUNDING |
| | ELECTRODE CONDUCTOR. |
| | |
| | 6) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR SERVICE |
| | MAINS PER 110.9. |
| | PLEASE SEE THE RATING AS SHOWN ON PANEL SCHEDULE WAS |
| | NOTED, HOWEVER NEEDED FOR MAIN(S). |
| | |
| | 7) NOTE: PLEASE COMPLETE AND SUBMIT A COMPLETE PANEL |
| | SCHEDULE WITH ALL MINIMUM REQUIRED DEDICATED LOADS AS |
| | WELL AS COMPLETED LOAD CALCULATIONS BASED ON MINIMUM |
| | REQUIREMENTS FROM THE NEC. |
| | PLEASE SEE 220.40, 220.82, 220.52, 220.54, 220.60, ETC, |
| | ETC. |
| | FBC ADMIN SECTION 106.3.5.4 |
| | |
| | 8) NOTE: PLEASE SEE 210.52D, 210.11C3,A S NO OTHER |
| | LOADS ARE PERMITTED ON THE DEDICATED BATH CIRCUIT(S). |
| | |
| | 9) NOTE: PLEASE SEE 210.52C1 FOR MISSING REQUIRED GFI'S |
| | ALONG KITCHEN COUNTER SPACE. |
| | MISSING MINIMUM VA 220.52 |
| | |
| | 10) NOTE: PLEASE SEE MISSING REQUIRED CIRCUITING FOR |
| | DINING ROOM RECEPTS PER 210.52B1, 210.11C1, AND 220. |
| | 52B. |
| | |
| | 11) NOTE: PLEASE SEE 210.8A6, AS ALL RECEPTS ALONG |
| | KITCHEN COUNTER SPACE SHALL BE SHOWN AS GFI. |
| | |
| | 12) NOTE: PLEASE SEE 410.8 AS THE PC LIGHTING IN |
| | CLOSETS ARE NOT PERMITTED AS SHOWN. THEY DO NOT MEET |
| | MINIMUM CLEARANCES. |
| | |
| | 13) NOTE: PLEASE SEE MISSING RECEPTS PER 210.52 FOR |
| | WALL SPACES. |
| | |
| | 14) NOTE: PLEASE SEE ALL SMOKE DEVICES SHALL BE SHOWN |
| | AS DEFINED IN NFPA-72. PLEASE SEE IF THESE DEVICES AS |
| | SHOWN ARE PART OF A LOW VOLTAGE ALARM SYSTEM WHICH |
| | CONTAINS HORN/ALARM DEVICES THEN THE SD AS SHOWN FOR |
| | SMOKE DETECTOR IS OK. IF THESE DEVICES AS SHOWN ARE |
| | DETECT AND SOUND AN ALARM, THEN THEY SHALL BE SHOWN AS |
| | SA FOR SMOKE ALARMS. |
| | PLEASE ALSO SEE NFPA-72 11.5.1.1, 11.8.3 FOR LOCATIONS |
| | REQUIRED INSIDE AND OUTSIDE ALL SLEEPING ROOMS. PLEASE |
| | SEE SOME ROOMS DO NOT INDICATE THE DEVICE OUTSIDE THE |
| | SLEEPING ROOM, YET INDICATE TWO DEVICES INSIDE ROOM? |
| | PLEASE SEE OTHER ROOMS WHICH DO INDICATE A DEVICE |
| | OUTSIDE ROOM, BUT STILL INDICATE TWO OR MORE INSIDE?? |
| | |
| | 15) NOTE: PLEASE SEE MISSING DISCONNECTS FOR ALL A/C |
| | EQUIPMENT. PLEASE SEE 440.11. |
| | PLEASE SEE AHU CLOSET APPEARS TO SHOW TWO RECEPTS. |
| | PLEASE KNOW AS PER 422.31, AHU?S SHALL NOT BE PLUGGED |
| | IN. |
| | |
| | 16) NOTE: PLEASE SEE 422.31 FOR DISCONNECTING MEANS |
| | REQUIRED FOR WATER HEATER(S). |
| | |
| | 17) NOTE: PLEASE CLARIFY ROOMS WHICH INDICATE A J-BOX |
| | FOR "PUT-FAN" AS STATED ON PLANS. PLEASE CLARIFY WHAT |
| | THIS IS? SYMBOL LEGEND DOES NOT ELABORATE ON THIS. |
| | |
| | 18) NOTE: PLEASE KNOW SEPARATE PLANS, AND PERMIT |
| | APPLICATIONS REQUIRED FOR LOW VOLTAGE , PHONE, CATV OR |
| | BURGLAR ALARM SYSTEMS. |
| | |
| | ** PLEASE KNOW SERVICE AND PROPOSED STRUCTURE MAY BE |
| | GREATLY AFFECT BY ANY POSSIBLE ZONING COMMENTS FOR |
| | SERVICE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |