| 2007-01-29 18:59:15 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTES. |
| | |
| | 2- PAY IMPACT FEES TO PALM BEACH COUNTY. BRING BACK |
| | STAMPED DRAWINGS AND COPY OF PAID RECEIPT. |
| | |
| | 3- PROVIDE TRUSS DRAWINGS FOR REVIEW PRIOR TO |
| | INSTALLATION. SEE SEC. R802.10 2004 FLORIDA RESIDENTIAL |
| | CODE FOR ALL REQUIRED INFORMATION ON TRUSS DRAWINGS. |
| | ALSO, DESIGNER OF RECORD TO REVIEW AND APPROVE THEM |
| | PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 4- PROVIDE DRAINAGE PLANS AS REQUIRED BY SEC. R401.3 |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- ENGINEER TO PROVIDE ALL HIS INFORMATION IN THE TITLE |
| | BLOCK AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES AND |
| | FLORIDA ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| | INCLUDING ENGINEERING FIRM'S CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | |
| | |
| | 6- SHEET SP-1:A) REVISE ALL DRIVEWAY AND APPROACH |
| | NOTES. CONTACT CITY OF WEST PALM BEACH ENGINEERING |
| | DEPARTMENT AT (561)494-1040 FOR CITY STANDARDS. |
| | |
| | B) DRAINAGE CAP CALCS HAVE NOTHING TO DO WITH |
| | PROJECT. |
| | |
| | C) REVISE SIZE OF PARKING SPACES. |
| | |
| | D) PAVEMENT DETAILS DON'T APPLY TO THIS JOB. |
| | |
| | E) FLOOR PLAN IS CALLED EXISTING SITE PLAN. THIS IS |
| | THE PROPOSED SITE PLAN. REVISE AS REQUIRED. |
| | |
| | F) CLARIFY WHY BACKFLOW PREVENTER IS SHOWN FOR ONE |
| | UNIT ONLY? |
| | |
| | 7- PROVIDE SOIL TEST REPORT (2 COPIES). |
| | |
| | 8- SHEET S-1:A) FOOTING SCHEDULE AND FOOTING TYPICAL |
| | NOTES SHOWN ON FOUNDATION PLAN DON'T MATCH.REVISE AS |
| | REQUIRED. |
| | |
| | B) COLUMN SCHEDULE AND TYPICAL NOTES IN FOUNDATION |
| | PLANS DON'T MATCH EITHER. REVISE AS REQUIRED. |
| | |
| | C) ENGINEER TO SPECIFY CONCRETE SLABS JOINTS AS |
| | REQUIRED BY SEC. R506.2.4 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | D) 4" DROP IS SHOWN ON MASTER BEDROOM WINDOW INSTEAD |
| | OF BEING SHOWN FOR ENTRY DOOR. REVISE AS REQUIRED. |
| | |
| | E) CORRECT WORDING IN CONCRETE SLAB SPECS IS 6 MIL |
| | VISQUEEN (NOT JISQUEEN) REVISE AS REQUIRED. |
| | |
| | F) DETAIL F1 CALLS FOR WELDED WIRE MESH SPECS ON |
| | FOUNDATION NOTES. WHERE ARE THE FOUNDATION NOTES? |
| | |
| | G) DETAIL F2 DOESN'T APPLY TO THIS PROJECT.THIS IS |
| | NOT WOOD FRAMING. SEE TYPE OF INTERIOR BEARING WALL. |
| | AND,SPECIFY SIZE OF FOOTING ACCORDINGTO TYPE OF |
| | WALL TO BE SUPPORTED. SEC. 106.1.2CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | H) DETAIL F2 SHOWS 3 RE-BARS, WHILE FOOTING SCHEDULE |
| | CALLS FOR 2 RE-BARS. REVISE AS REQUIRED. |
| | |
| | I) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS |
| | PROJECT TO AVOID CONFUSIONS/CONFLICTS AND EXPEDITE |
| | REVIEW PROCESS. |
| | |
| | 9- SHEET A-1:A) PROVIDE CALCULATIONS AND DIMENSIONS |
| | SHOWING HOW102SF OF COVERED ENTRY WAS ACHIEVED? PLANS |
| | DON'T PROVIDE ENOUGH INFORMATION TO VERIFY SQUARE |
| | FOOTAGE.BUILDING PERMIT VALUATION WILL BE ESTIMATED |
| | AFTER SQUARE FOOTAGES ARE CLARIFIED. |
| | |
| | B) SPECIFY ATTIC ACCESS SIZE. SEC. R807 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | C) DRAWINGS ARE INCOMPLETE: MISSING SIZE OF ENTRY |
| | DOORS,CLOSET DOORS, ETC. |
| | |
| | D) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL. SPECIFY |
| | ALL BUCK FASTENERS AND SEESEC. R613.6.2 2004 FLORIDA |
| | RESIDENTIAL CODE FOR PROPER BUCK INSTALLATION. BUCK |
| | NEEDS TO PROVIDE FULL SUPPORT TO THE WINDOW/DOOR. |
| | |
| | 10- SHEET A-2:A) SPECIFY CALCULATED DESIGN PRESSURES |
| | FOR ENTRY DOORS. SEC. R301 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | B) CLARIFY NOTE REGARDING BAHAMA SHUTTERS ON 14TH |
| | STREET ONLY. ALL ELEVATIONS SHOW COLONIAL SHUTTERS. |
| | |
| | C) ELEVATIONS DON'T MATCH FLOOR PLAN.SOME ROOMS |
| | HAVE DOUBLE WINDOWS MULLED TOGETHER. REVISE AS |
| | REQUIRED. |
| | |
| | D) PROVIDE COMPLETE STRUCTURAL INFORMATION FOR |
| | OVERHANG ABOVE ENTRY AREA. PROVIDE COMPLETE STRUCTURAL |
| | SECTION/DETAIL WITH COMPLETE SPECIFICATIONS, |
| | DIMENSIONS, HEIGHT, ETC.SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | E) WINDOW SCHEDULE DOESN'T MATCH FLOOR PLAN. REVISE |
| | AS REQUIRED. |
| | |
| | 11- SHEET A-3:A) PROVIDE ONLY THE INFORMATION THAT IS |
| | RELEVANT TO THIS PROJECT. THERE ARE A LOT OF NOTES AND |
| | TABLES THAT DON'T APPLY TO THIS PROJECT. |
| | |
| | B) REVISE CODE INFORMATION.CODE THAT APPLIES TO |
| | THIS PROJECT IS 2004 FLORIDA RESIDENTIAL CODE. WHEN |
| | REFERENCINGASCE7,THEN, THE CORRECT EDITION IS |
| | 2002, NOT 2005. REVISE AS REQUIRED. |
| | |
| | C) TRUSS CONNECTOR SCHEDULE AND CONNECTORS SPECIFIED |
| | ON ROOF FRAMING PLAN DON'T MATCH. REVISE AS REQUIRED. |
| | |
| | D) REVISE NUMBER AND TYPE OF FASTENERS SPECIFIED ON |
| | TRUSS CONNECTOR SCHEDULE. SEE CURRENT CATALOGUE FOR |
| | UPDATED INFORMATION. OTHERWISE, ENGINEER TO PROVIDE |
| | COMPLETE ENGINEERING ANALYSIS SHOWING WHY CONNECTORS |
| | ARE DIFFERENT THAN THOSE TESTED AND PUBLISHED BY THE |
| | MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | E) MANUFACTURER FOR CONNECTORS SPECIFIED ON ROOF |
| | FRAMING PLAN IS OUT OF BUSINESS. REVISE AS REQUIRED. |
| | |
| | F) CLEARLY IDENTIFY TRUSSES FOR WHICH UPLIFT |
| | PRESSURES WERE CALCULATED. |
| | |
| | G) PROVIDE COMPLETE STRUCTURAL DETAILS/SPECS FOR |
| | ROOF ABOVE ENTRY DOORS. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | H) ENGINEER TO COORDINATE ALL NOTES AND CHARTS SHOWN |
| | ON THIS DRAWINGS. THERE IS A LOT OF MIXED INFORMATION |
| | THAT NEEDS TO BE COORDINATED.SEE 2004 FLORIDA |
| | RESIDENTIAL CODE AND ALLINFORMATION SUBMITTED IN THIS |
| | SHEET.PROVIDE ONLY THE REQUIRED INFORMATION.SEE |
| | SECTIONS . R301 2004 FLORIDA RESIDENTIAL CODE. ALSO, |
| | SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE |
| | FOR MINIMUM REQUIREMENTS FOR ROOF SHEATHING. REVISE AND |
| | COORDINATE ALL INFORMATION IN SHEET A-3 TO MATCH. |
| | |
| | I) PNEUMATIC FASTENING SCHEDULE: PROVIDE ONLY THE |
| | INFORMATION THAT APPLIES TO THIS PROJECT.CHECK/REVISE |
| | SPACING FOR BUCK DETAILS FASTENING. INFORMATION DOESN'T |
| | MATCH. ALSO, COORDINATE WITH PROVIDED BUCK DETAIL. |
| | |
| | J) ROOF FRAMING PLAN CALLS DWELLING SEPARATION WALL |
| | A "FIRE WALL".SEEFBC 2004 FOR CORRECT DEFINITION |
| | FOR "FIRE WALL" AND REVISE AS REQUIRED. |
| | |
| | K) PROVIDE COMPLETE SECTION TRUH DWELLING SEPARATION |
| | WALL TO SHOW COMPLIANCE WITH SEC. R317.1 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | L) REVISE ATTIC VENTILATION CALCULATIONS AND NOTES |
| | SEE SEC. R806 2004 FLORIDA RESIDENTIAL CODE FOR PROPER |
| | INFORMATION. |
| | |
| | |
| | 12- PRIOR TO SUBMITTAL TO THIS OFFICE BRING PLANS FOR |
| | HISTORICAL APPROVAL AFTER CORRECTIONS ARE DONE TO THE |
| | PLANS. |
| | |
| | 13- SHEET A-4:A) REVISE INTERIOR BEARING WALL TO |
| | MATCH FLOOR PLAN. REVISE SIZE OF FOOTING, WALL |
| | CONSTRUCTION, ETC. |
| | |
| | B) SPECIFY FIREBLOCKING ON INTERIOR BEARING WALL |
| | SECTION AS REQUIRED BY SEC. R602.8 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | B) PROVIDE DETAIL/SPECS FOR DWELLING SEPARATION AT |
| | ATTIC AREA. SEC. R317.1 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) PROVIDE ALL DESIGN CRITERIA, INCLUDING ALL WIND |
| | LOADS, AND LIVE AND DEAD LOADS. REFERENCE 2004 FLORIDA |
| | RESIDENTIAL CODE,WHICH IS THE CODE THAT REGULATES |
| | THIS BUILDING, NOT SECTIONS 1606 OF FBC 2004. SEE SEC. |
| | R301 AND TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | REVISE AS REQUIRED. |
| | |
| | D) PLYWOOD NAILING NOTES TO MATCH INFORMATION ON |
| | SHEET A-3 AFTER APPROPRIATE REVISIONS ARE DONE. |
| | |
| | E) TYPICAL WALL SECTION: |
| | * WHAT IS D-30 INSULATION? |
| | ** WHAT IS 6 MIL JISQUEEN? |
| | *** WHAT IS 1/2" DRYWALL STRIPS AT 16"O.C.? |
| | **** WHAT IS 2"X4" STRIP?. IS IT FIREBLOCKING?. ALSO, |
| | VERIFY SIZE WITH SIZE OF FURRING STRIPS FOR DRYWALL |
| | INSTALLATION. |
| | ***** WHAT IS 325# SHINGLES? |
| | ****** ROOF SHEATHIG SIZE AND TYPE TO MATCH INFORMATION |
| | ON SHEET A-3 AFTER APPROPRIATE REVISIONS ARE DONE. |
| | ******* TRUSS CONNECTOR TO MATCH INFORMATION ON SHEET |
| | A-3 AFTER APPROPRIATE REVISIONS ARE DONE. |
| | ******** SPECIFY FOOTING MIN. DEPTH AS REQUIRED BY SEC. |
| | R 403.1.4 2004 FLORIDA RESIDENTIAL CODE. |
| | ********* SPECIFY MINIMUM FINISH FLOOR AS REQUIRED BY |
| | SEC. R404.1.6 2004 FLORIDA RESDIENTIAL CODE. |
| | |
| | 14- ENERGY CALCULATIONS:A) PROVIDE COMPLETE |
| | INFORMATION ON TOP OF FORM. |
| | |
| | B) THIS IS A MULTIFAMILY BUILDING, NOT SINGLE |
| | FAMILY. SEE DEFINITIONS ON SUBCHAPTER13-2 OF 2004 |
| | FBC. REVISE AS REQUIRED. THEREFORE SEPARATE ENERGY |
| | CALCULATIONS ARE REQUIRED. SEE SEC. 15-101.2.5.1 FBC |
| | 2004. |
| | |
| | C) IF CALCULATIONS ARE NOT DONE FOR WORST CASE |
| | SCENARIO, THEN THEY SHALL BE DONE ON ACTUAL BUILDING |
| | ORIENTATION.ENERGY CALCULATIONS SUBMITTED ARE NOT FOR |
| | WORST CASE SCENARIO AND BUILDING ORIENTATION DON'T |
| | MATCH ACTUAL BUILDING ORIENTATION. SEE SURVEY AND |
| | REVISE AS REQUIRED. |
| | |
| | D) OVERHANG LENGTH AND HEIGHT ARE INCORRECT.THEY |
| | CAN'T BE ZERO. REVISE AS REQUIRED. |
| | |
| | 16- ENERGY CALCULATIONS ARE TAKINGTHE CEILING FAN |
| | CREDIT. THEREFORE NEED TO SPECIFY CEILING FAN SIZE IN |
| | ALL ROOMS AS REQUIRED BY TABLE 13-607.1.A.1 FBC 2004. |
| | |
| | 17- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) SINGLE HUNG WINDOWS.TWO DIFFERENT PRODUCT |
| | APPROVALS WERE SUBMITTED. ONLY THE ONE FOR LARGE |
| | MISSILE IMPACT CAN BE USED FOR OPENINGS BELOW 30'-0" |
| | HIGH. PROVIDE 2 COPIES. |
| | |
| | B) SHINGLES. |
| | |
| | C) BAHAMA SHUTTERS AND COLONIAL SHUTTERS SHOWN ON |
| | EXTERIOR ELEVATIONS. AND PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED INSTALLATION SCHEDULE SAMPLE. |
| | PROVIDE ALL REQUIRED INFORMATION. |
| | |
| | D) PRECAST LINTELS. |
| | |
| | E) ENTRY DOORS. |
| | |
| | F) REAR DOORS. |
| | |
| | G) ALL STRUCTURAL SIMPSON OR USP CONNECTORS |
| | SPECIFIED ON PLANS ANDDETAILS. |
| | |
| | H) WINDOW MULLIONS AND SPECIFY FASTENING. |
| | |
| | 18- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |