| 2007-02-05 14:43:12 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT A-2 ROOF PLAN, NEW ROOF SHOWS THE EMERGENCY |
| | OVERFLOW SCUPPER AT THE SOUTHEAST CORNER OF THE ROOF, |
| | BUT THE PRIMARY ROOF DRAIN IS LOCATED ON THE WEST SIDE |
| | OF THE ROOF. SECTION 1503.4.3 STATES THAT OVERFLOW |
| | SCUPPERS SHALL BE LOCATED AS CLOSE AS PRACTICAL TO THE |
| | REQUIRED VERTICAL LEADERS, DOWNSPOUTS, OR WALL/PARAPET |
| | SCUPPERS. PLEASE COMPLY WITH THIS SECTION. |
| | |
| | 2. SHT A-2 EXISTING ROOF SHOW AN EXISTING ROOF DRAIN & |
| | SCUPPER TO BE CLOSED UP. AS SHOWN ON THE ROOF PLAN, 2/3 |
| | OF THE ROOF AREA, (APPROX. 4511SF),WILL DRAIN TO THE |
| | EXISTING ROOF DRAIN IN THE MIDDLE OF THE EAST SIDE OF |
| | THE EXISTING ROOF. 1/3 OF THE AREA WILL BE DRAINED BY |
| | THE DRAIN ON THE NORTHEAST CORNER OF THE ROOF. |
| | CALCULATIONS INDICATE THAT THE TOTAL AREA WILL BE |
| | DIVIDED BY 2 AND SPLIT UP EVENLY. A 5" DRAIN WILL BE |
| | REQUIRED FOR THE DRAIN THAT IS DRAINING 2/3 OF THE |
| | AREA, AND THE EXISTING PIPE FOR THAT RWL WILL HAVE TO |
| | BE VERIFIED TO SEE IF THE SIZE IS SUFFICIENT TO DRAIN |
| | THE ADDED LOAD TO THAT DRAIN. PLEASE INDICATE THE SIZE |
| | OF THE EXISTING RWL SIZE FOR THE DRAINAND INDICATE IF |
| | THERE ARE ANY HORIZONTAL OFFSETS. INDICATE THIS SIZE OF |
| | THE HORIZONTAL BUILDING STORM DRAIN AT THE BASE OF THE |
| | RWL TO VERIFY IF THE PIPE SIZE MEETS CODE REQUIREMENTS. |
| | TABLE 1106.3.--PLEASE SUBMIT NEW CALCULATIONS FOR |
| | THE ROOF DRAIN SHOWING THE TOTAL AREA BEING DRAINED BY |
| | EACH DRAIN. SECTION 106.1.1. |
| | |
| | 3. SHT A-2 EXISTING ROOF, THE EMERGENCY OVERFLOW |
| | SCUPPERS ARE LOCATED ON THE WEST SIDE OF THE ROOF, AND |
| | THE PRIMARY ROOF DRAINS ARE SHOWN ON THE EAST SIDE. |
| | SCUPPERS SHALL BE LOCATED AS CLOSE AS PRACTICAL TO THE |
| | REQUIRED VERTICAL LEADERS, DOWNSPOUTS OR WALL SCUPPERS. |
| | SECTION 1503.4.3. |
| | |
| | 4. SHT P-2 DOMESTIC WATER RISER DIAGRAM SHOWS THE P/T |
| | DISCHARGE LINE TRAPPED UNDER THE SLAB. THIS IS NOT |
| | APPROVED PER SECTION 504.6.--THERMAL EXPANSION |
| | CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE |
| | INDICATE THE METHOD USED TO COMPLY. |
| | |
| | REVIEW BY KEN STEVENS |