2007-02-05 14:43:12DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
  
 1. SHT A-2 ROOF PLAN, NEW ROOF SHOWS THE EMERGENCY
 OVERFLOW SCUPPER AT THE SOUTHEAST CORNER OF THE ROOF,
 BUT THE PRIMARY ROOF DRAIN IS LOCATED ON THE WEST SIDE
 OF THE ROOF. SECTION 1503.4.3 STATES THAT OVERFLOW
 SCUPPERS SHALL BE LOCATED AS CLOSE AS PRACTICAL TO THE
 REQUIRED VERTICAL LEADERS, DOWNSPOUTS, OR WALL/PARAPET
 SCUPPERS. PLEASE COMPLY WITH THIS SECTION.
  
 2. SHT A-2 EXISTING ROOF SHOW AN EXISTING ROOF DRAIN &
 SCUPPER TO BE CLOSED UP. AS SHOWN ON THE ROOF PLAN, 2/3
 OF THE ROOF AREA, (APPROX. 4511SF),WILL DRAIN TO THE
 EXISTING ROOF DRAIN IN THE MIDDLE OF THE EAST SIDE OF
 THE EXISTING ROOF. 1/3 OF THE AREA WILL BE DRAINED BY
 THE DRAIN ON THE NORTHEAST CORNER OF THE ROOF.
 CALCULATIONS INDICATE THAT THE TOTAL AREA WILL BE
 DIVIDED BY 2 AND SPLIT UP EVENLY. A 5" DRAIN WILL BE
 REQUIRED FOR THE DRAIN THAT IS DRAINING 2/3 OF THE
 AREA, AND THE EXISTING PIPE FOR THAT RWL WILL HAVE TO
 BE VERIFIED TO SEE IF THE SIZE IS SUFFICIENT TO DRAIN
 THE ADDED LOAD TO THAT DRAIN. PLEASE INDICATE THE SIZE
 OF THE EXISTING RWL SIZE FOR THE DRAINAND INDICATE IF
 THERE ARE ANY HORIZONTAL OFFSETS. INDICATE THIS SIZE OF
 THE HORIZONTAL BUILDING STORM DRAIN AT THE BASE OF THE
 RWL TO VERIFY IF THE PIPE SIZE MEETS CODE REQUIREMENTS.
 TABLE 1106.3.--PLEASE SUBMIT NEW CALCULATIONS FOR
 THE ROOF DRAIN SHOWING THE TOTAL AREA BEING DRAINED BY
 EACH DRAIN. SECTION 106.1.1.
  
 3. SHT A-2 EXISTING ROOF, THE EMERGENCY OVERFLOW
 SCUPPERS ARE LOCATED ON THE WEST SIDE OF THE ROOF, AND
 THE PRIMARY ROOF DRAINS ARE SHOWN ON THE EAST SIDE.
 SCUPPERS SHALL BE LOCATED AS CLOSE AS PRACTICAL TO THE
 REQUIRED VERTICAL LEADERS, DOWNSPOUTS OR WALL SCUPPERS.
 SECTION 1503.4.3.
  
 4. SHT P-2 DOMESTIC WATER RISER DIAGRAM SHOWS THE P/T
 DISCHARGE LINE TRAPPED UNDER THE SLAB. THIS IS NOT
 APPROVED PER SECTION 504.6.--THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE THE METHOD USED TO COMPLY.
  