2007-01-16 15:12:58*** DENIED ***
 1) SEE PAGE M-1 OUTSIDE AIR TABULATION AS PER ASHRAE
 62-1989, PER 2004 (2006 REV.) FBC/M CH.15 ASHRAE
 62.1-2004.
  
 2) PLEASE SHOW OUTSIDE AIR CALCULATIONS FOR EACH UNIT,
 SHOW CALCULATIONS EITHER BY ASHRAE 62.1-2004 OR 2004
 FBC/M 403.1.
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.3 .
  
 4) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.