| 2007-02-07 11:19:15 | *****DENIED***** |
| | |
| | |
| | 1.THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED. |
| | ADD TO APPLICABLE CODES, SHEET SP-1 |
| | |
| | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.ADD |
| | TO NOTES, SHEET D-1 |
| | |
| | 3.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR |
| | INTERFERE WITH ACCESS TO OR EXIT FROM THE STRUCTURE, OR |
| | THE VICINITY OF THE STRUCTURE (INCLUDING FIRE LANES). |
| | ADD TO NOTES, SHEET D-1 |
| | |
| | 4.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR |
| | ELEVATION THAT FRONTS SOUTH DIXIE HIGHWAY.AS PER WEST |
| | PALM BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO LESS |
| | THAN 6" IN HEIGHT AND 1" IN WIDTH.IN ADDITION THE |
| | APPROPIATE UNIT/TENANT NUMBER (NO LESS THAN 3" IN |
| | HEIGHT) SHALL BE DISPLAYED.ADD TO PROPOSED EAST |
| | (FRONT) ELEVATION, SHEET A-3 |
| | |
| | 5.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR |
| | WALL AND CEILINGS IN THE PROPOSED STRUCTURE. |
| | |
| | 6.WILL THE BUILDING/STRUCTURE BE EUIPPED WITH A FIRE |
| | ALARM AND/OR FIRE SPRINKLER SYSTEM? |
| | |
| | 7.INDICATE THE LOCATION OF THE 2A:10BC FIRE |
| | EXTINGUISHER(S) FOR EACH TENANT SPACE.ADD TO SHEET |
| | LS-1 |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |