| Date |
Text |
| 2007-01-14 10:41:15 | ** UNSAT ** |
| | |
| | ** PLEASE SEE THE PERMIT NUMBER BEING REFERENCED ON |
| | PERMIT APPLICATION IS FOR DEMO WORK ONLY AND IS NOT FOR |
| | ANY PART OF BUILD OUT. |
| | |
| | 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| | PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. |
| | PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| | DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| | RELEVANT. |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 |
| | (NEC). |
| | PLEASE SEE THE OTHER CODES WHICH ARE STATED ON PLANS |
| | FOR ELECTRICAL SHEETS WHICH ARE ALREADY STATED ARE: |
| | 2002 NFPA-72 AND 2003 NFPA-101. |
| | |
| | 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER |
| | 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2. |
| | THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE |
| | DESIGNER OF RECORD. |
| | PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES |
| | TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION |
| | ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE |
| | PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS. |
| | PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR LIGHTING |
| | ALLOWANCE AND SHOW COMPLIANCE. |
| | NOT ENOUGH INFORMATION ON LIGHTING ALLOWANCES IS |
| | PROVIDED. |
| | |
| | 3) NOTE: PLEASE SUBMIT AND INDICATE THE ACTUAL WIND |
| | LOAD DESIGNS FOR LIGHT POLES TO BE INSTALLED. (FBC |
| | 140MPH) PLEASE INDICATE THE EPA FOR POLE(S) AND PROVIDE |
| | INFORMATION FOR THIS TO BE REVIEWED BY THE BUILDING |
| | REVIEWER. |
| | FBC 106.1.2 ADMIN SECTION. |
| | THIS SCOPE WILL NOT BE REVIEWED BY THE ELECTRICAL |
| | REVIEWER; HOWEVER THIS IS REQUIRED ON PLANS FOR CODE |
| | COMPLIANCE. |
| | |
| | 4) NOTE: PLEASE CLARIFY SERVICE AND SERVICE RISER AS |
| | SHOWN. |
| | PLEASE INDICATE THE PHASES BEING USED TO EACH OF THE |
| | PANELS AS PANELS IN SPACES ARE BEING SHOWN AS SINGLE |
| | PHASE AND SERVICE IS 3-PHASE. |
| | PLEASE INDICATE DOUBLE LUGS FOR SERVICE TENANT MAINS |
| | FOR TAPS FOR CU'S. |
| | 215.5, 230, 240.4 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING METHOD |
| | AFTER THE FIRST MEANS OF DISCONNECT. PLEASE SEE MISSING |
| | EQUIPMENT GROUNDING CONDUCTOR AFTER THE MAINS. |
| | PLEASE ALSO INDICATE A "FLOATING NEUTRAL" AT THE TENANT |
| | METERS. (THIS CAN BE DONE BY A NOTE). |
| | 250.6, 250.24, 250.110, 250.122 ETC |
| | |
| | 6) NOTE: PLEASE INDICATE ON THE ELECTRICAL PLANS THE |
| | COMPLIANCE FOR THE STATED 240.21B5. PLEASE SEE THE |
| | PREVIOUS ELECTRICAL SHEET E-2 DOES NOT INDICATE THE |
| | REQUIRED TERMINATION IN OVER CURRENT PROTECTION AS |
| | REQUIRED PER SECTION AS STATED ON PLANS. |
| | 240.4, 310.16, 240.21 ETC. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE CLARIFY LOAD ON AHU WHICH IS BEING |
| | SHOWN ON THE PANEL AS 14KW ON 20AMP BREAKER AND #12. |
| | PLEASE SEE MECHANICAL PLANS INDICATE THIS OCP YET, IF |
| | THE LOAD IS 14KW, THEN THE RATING OF THE CIRCUIT IS |
| | EXCEEDED? |
| | 240.4, 310.16 ETC. |
| | IT IS NOT CLEAR IF HEAT LOADS EXISTS WHICH SEEM TO AS |
| | THE LOAD IS 14KW, IF THIS IS THE CASE PLEASE SEE |
| | 424.3B. |
| | |
| | 8) NOTE: PLEASE SUBMIT AND SHOW ALL CIRCUITING ON PLANS |
| | AND CORRELATE WITH A PANEL SCHEDULE WHICH IS REQUIRED |
| | TO BE SUBMITTED.PLEASE SEE SOME CIRCUITS ARE MISSING |
| | FROM ELECTRICAL DEVICES AND FIXTURES. |
| | PLEASE SEE SOME CIRCUITING WHICH IS SHOWN ON PLANS DOES |
| | NOT CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. |
| | (CIRCUITS ON PLANS ARE BLANK/SPACE ON SCHEDULE). |
| | PLEASE SEE THAT SOME ITEMS FOR CODE COMPLIANCE CAN NOT |
| | BE VERIFIED AT THIS TIME. |
| | 408.4, 310.16, 240.4 |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | |
| | 9) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | EACH SPACE AND CORRELATE WITH THE LOADS ON PANEL |
| | SCHEDULES. PLEASE CORRELATE LOADS FOR A/C'S. PLEASE |
| | ALSO CORRELATE UNIT LOADS ON THE BUILDING SERVICE LOAD |
| | CALCULATIONS. THIS IS A COMMERCIAL BUILDING AND |
| | COMPLETE LOADS CAN NOT BE VERIFIED AT THIS TIME. |
| | PLEASE SEE NEC 220.12, 220.14, 220.43(A) & (B), 220.44 |
| | ETC. |
| | PLEASE ALSO SEE THAT ALL CONTINUOUS LOADS AND LARGEST |
| | MOTOR LOAD SHALL BE SHOWN AT 125% 215.3, 230.42 ETC. |
| | (SOME CONTINUOUS LOADS ARE SHOWN AT 125%) |
| | |
| | 10) NOTE: PLEASE STATE ON PLANS THE INTENDED |
| | OCCUPANCIES. PLEASE KNOW BASED ON THE DESCRIPTION |
| | ALREADY ON ARCHITECTURAL SHEETS; PLEASE SEE MISSING |
| | SHOW WINDOW RECEPTACLES PER 210.62 AND LOADS PER |
| | 220.43. |
| | |
| | 11) NOTE: PLEASE SEE 2006 REVISIONS TO THE 2004 FBC |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE INDICATE |
| | COMPLIANCE FOR INTERIOR LIGHTING CONTROLS. |
| | |
| | 12) NOTE: PLEASE SEE 700.12E FOR CIRCUITING EXIT AND |
| | EMERGENCY LIGHTING. PLEASE SEE SOME OF THESE MEET THE |
| | CODE, HOWEVER AS SOME CIRCUITS ARE MISSING VERIFICATION |
| | CAN NOT BE MADE. |
| | PLEASE SEE SOME FIXTURES ARE SHOWN CIRCUITED TO THE |
| | RECEPTACLE CIRCUITS. |
| | |
| | 13) NOTE: PLEASE CLARIFY ROOF TOP GFI RECEPTACLE(S) FOR |
| | A/C UNITS. 210.63, 210.8B2 |
| | |
| | 14) NOTE: PLEASE STATE THE COLOR CODING FOR SERVICE |
| | CONDUCTOR ON RISER. (CAN BE DONE AS A NOTE) BLACK, |
| | ORANGE, RED AND WHITE. |
| | 110.15 |
| | |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY BE NEW COMMENTS ON NEXT |
| | REVIEW BASED ON REVISED PLANS AND/OR INFORMATION TO BE |
| | SUBMITTED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |