Plan Review Notes
Plan Review Notes For Permit 06120401
Permit Number 06120401
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-14 10:41:15** UNSAT **
  
 ** PLEASE SEE THE PERMIT NUMBER BEING REFERENCED ON
 PERMIT APPLICATION IS FOR DEMO WORK ONLY AND IS NOT FOR
 ANY PART OF BUILD OUT.
  
 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER.
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC).
 PLEASE SEE THE OTHER CODES WHICH ARE STATED ON PLANS
 FOR ELECTRICAL SHEETS WHICH ARE ALREADY STATED ARE:
 2002 NFPA-72 AND 2003 NFPA-101.
  
 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER
 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2.
 THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE
 DESIGNER OF RECORD.
 PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES
 TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION
 ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE
 PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS.
 PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR LIGHTING
 ALLOWANCE AND SHOW COMPLIANCE.
 NOT ENOUGH INFORMATION ON LIGHTING ALLOWANCES IS
 PROVIDED.
  
 3) NOTE: PLEASE SUBMIT AND INDICATE THE ACTUAL WIND
 LOAD DESIGNS FOR LIGHT POLES TO BE INSTALLED. (FBC
 140MPH) PLEASE INDICATE THE EPA FOR POLE(S) AND PROVIDE
 INFORMATION FOR THIS TO BE REVIEWED BY THE BUILDING
 REVIEWER.
 FBC 106.1.2 ADMIN SECTION.
 THIS SCOPE WILL NOT BE REVIEWED BY THE ELECTRICAL
 REVIEWER; HOWEVER THIS IS REQUIRED ON PLANS FOR CODE
 COMPLIANCE.
  
 4) NOTE: PLEASE CLARIFY SERVICE AND SERVICE RISER AS
 SHOWN.
 PLEASE INDICATE THE PHASES BEING USED TO EACH OF THE
 PANELS AS PANELS IN SPACES ARE BEING SHOWN AS SINGLE
 PHASE AND SERVICE IS 3-PHASE.
 PLEASE INDICATE DOUBLE LUGS FOR SERVICE TENANT MAINS
 FOR TAPS FOR CU'S.
 215.5, 230, 240.4
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING METHOD
 AFTER THE FIRST MEANS OF DISCONNECT. PLEASE SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR AFTER THE MAINS.
 PLEASE ALSO INDICATE A "FLOATING NEUTRAL" AT THE TENANT
 METERS. (THIS CAN BE DONE BY A NOTE).
 250.6, 250.24, 250.110, 250.122 ETC
  
 6) NOTE: PLEASE INDICATE ON THE ELECTRICAL PLANS THE
 COMPLIANCE FOR THE STATED 240.21B5. PLEASE SEE THE
 PREVIOUS ELECTRICAL SHEET E-2 DOES NOT INDICATE THE
 REQUIRED TERMINATION IN OVER CURRENT PROTECTION AS
 REQUIRED PER SECTION AS STATED ON PLANS.
 240.4, 310.16, 240.21 ETC.
 FBC 106.1.2
  
 7) NOTE: PLEASE CLARIFY LOAD ON AHU WHICH IS BEING
 SHOWN ON THE PANEL AS 14KW ON 20AMP BREAKER AND #12.
 PLEASE SEE MECHANICAL PLANS INDICATE THIS OCP YET, IF
 THE LOAD IS 14KW, THEN THE RATING OF THE CIRCUIT IS
 EXCEEDED?
 240.4, 310.16 ETC.
 IT IS NOT CLEAR IF HEAT LOADS EXISTS WHICH SEEM TO AS
 THE LOAD IS 14KW, IF THIS IS THE CASE PLEASE SEE
 424.3B.
  
 8) NOTE: PLEASE SUBMIT AND SHOW ALL CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE WHICH IS REQUIRED
 TO BE SUBMITTED.PLEASE SEE SOME CIRCUITS ARE MISSING
 FROM ELECTRICAL DEVICES AND FIXTURES.
 PLEASE SEE SOME CIRCUITING WHICH IS SHOWN ON PLANS DOES
 NOT CORRELATE WITH THE PANEL SCHEDULES SUBMITTED.
 (CIRCUITS ON PLANS ARE BLANK/SPACE ON SCHEDULE).
 PLEASE SEE THAT SOME ITEMS FOR CODE COMPLIANCE CAN NOT
 BE VERIFIED AT THIS TIME.
 408.4, 310.16, 240.4
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 9) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 EACH SPACE AND CORRELATE WITH THE LOADS ON PANEL
 SCHEDULES. PLEASE CORRELATE LOADS FOR A/C'S. PLEASE
 ALSO CORRELATE UNIT LOADS ON THE BUILDING SERVICE LOAD
 CALCULATIONS. THIS IS A COMMERCIAL BUILDING AND
 COMPLETE LOADS CAN NOT BE VERIFIED AT THIS TIME.
 PLEASE SEE NEC 220.12, 220.14, 220.43(A) & (B), 220.44
 ETC.
 PLEASE ALSO SEE THAT ALL CONTINUOUS LOADS AND LARGEST
 MOTOR LOAD SHALL BE SHOWN AT 125% 215.3, 230.42 ETC.
 (SOME CONTINUOUS LOADS ARE SHOWN AT 125%)
  
 10) NOTE: PLEASE STATE ON PLANS THE INTENDED
 OCCUPANCIES. PLEASE KNOW BASED ON THE DESCRIPTION
 ALREADY ON ARCHITECTURAL SHEETS; PLEASE SEE MISSING
 SHOW WINDOW RECEPTACLES PER 210.62 AND LOADS PER
 220.43.
  
 11) NOTE: PLEASE SEE 2006 REVISIONS TO THE 2004 FBC
 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE INDICATE
 COMPLIANCE FOR INTERIOR LIGHTING CONTROLS.
  
 12) NOTE: PLEASE SEE 700.12E FOR CIRCUITING EXIT AND
 EMERGENCY LIGHTING. PLEASE SEE SOME OF THESE MEET THE
 CODE, HOWEVER AS SOME CIRCUITS ARE MISSING VERIFICATION
 CAN NOT BE MADE.
 PLEASE SEE SOME FIXTURES ARE SHOWN CIRCUITED TO THE
 RECEPTACLE CIRCUITS.
  
 13) NOTE: PLEASE CLARIFY ROOF TOP GFI RECEPTACLE(S) FOR
 A/C UNITS. 210.63, 210.8B2
  
 14) NOTE: PLEASE STATE THE COLOR CODING FOR SERVICE
 CONDUCTOR ON RISER. (CAN BE DONE AS A NOTE) BLACK,
 ORANGE, RED AND WHITE.
 110.15
  
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY BE NEW COMMENTS ON NEXT
 REVIEW BASED ON REVISED PLANS AND/OR INFORMATION TO BE
 SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]