Plan Review Notes
Plan Review Notes For Permit 06120401
Permit Number 06120401
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-18 08:27:09BUILDING PLAN REVIEW
 PERMIT: 06120401
 ADD: 3415 S DIXIE HWY
 CONT: R&D CONSTRUCTORS
 TEL: (561)889-1751
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLEASE PROVIDE A SURVEY,
  
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3 . DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 3202.2.2 ARCHITECTURAL FEATURES.
 COLUMNS OR PILASTERS, INCLUDING BASES AND MOLDINGS
 SHALL NOT PROJECT MORE THAN 12 INCHES (305 MM). BELT
 COURSES, LINTELS, SILLS, ARCHITRAVES, PEDIMENTS AND
 SIMILAR ARCHITECTURAL FEATURES SHALL NOT PROJECT MORE
 THAN 4 INCHES (102 MM).
  
 4) NEW ADDITION,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 5) SHEET SP-1 THE DESIGNER HAS NOT PROVIDED THE MINIMUM
 BUILDING TYPE SEE TABLE 503. PLEASE PROVIDE THE
 FOLLOWING DESIGN CRITERIA:
 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 6 ) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 7 ) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 8) SHEET A-2 EXISTING ROOF PLAN, THE MAIN ROOF
 INDICATES THE USE OF (3) 4" ROOF DRAINS, THE PLANS
 INDICATE (1) DRAIN IS TO BE CLOSED UP. THE DRAINS ARE
 AT THE LOW POINT IN THE ROOF. THE EMERGENCY OVER FLOWS
 ARE AT THE HIGH POINT IN THE ROOF , A NOT ON THE PLAN
 INDICATES THERE TO BE 12" OF SLOPE ON THE ROOF. IN
 OTHERWORDS IF THE 2 DRAINS GET PLUGGED 12"OF WATER
 WILL POND ON THE ROOF BEFORE WATER WILL BEGIN TO
 CASCADE OVER THE EMERGENCY OVERFLOWS!!!!
 1503.4.2 SCUPPER.
 WHERE REQUIRED FOR ROOF DRAINAGE, A SCUPPER SHALL BE
 PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR
 PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY
 THE SLOPE AND THE CONTRIBUTING AREA OF THE ROOF. THE
 EXTERIOR FACING OR LINING OF A SCUPPER, IF METAL, SHALL
 BE THE SAME AS FLASHING MATERIAL REQUIRED BY SECTIONS
 1503 THROUGH 1510 FOR THE PARTICULAR TYPE OF COVERING
 SPECIFIED FOR THE BUILDING. FOR OTHER TYPE MATERIALS,
 FOLLOW MANUFACTURER?S SPECIFICATIONS.
  
 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 9) SHEET A-2 ON THE NEW ROOF THE SAME SITUATION APPEARS
 OVERFLOWS ARE SHOWN ON THE WEST SIDE OF THE BUILDING
 WITH 8" OF SLOPE BEFORE WATER HITS THE EMERGENCY
 OVERFLOW.
  
 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 10) 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 11) DISCUSSING THIS PROJECT WITH THE PLANNEER ERIC
 SCHNEIDER HE INDICATED ALL A/C CONDENSORS WILL BE
 REQUIRED TO BE INSTALLED ON THE ROOF, PLEASE NOTE:
 11A)1503.5 ROOF VENTILATION.
 INTAKE AND EXHAUST VENTS SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 1203.2 AND THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
 11B) PROVIDE ENGINEERS CALS ARE OK FOR THE ADDITIONAL
 ROOF LOADS.106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 11C) PRE-ENGINEERED A/C STANDS WILL REQUIRE FLORIDA
 PRODUCT APPROVAL RULE 9B-72 FL ADMINISTRATIVE CODE.
  
 11D) 13-404.1.ABC.1 ROOF/CEILING THERMAL ENVELOPES.
 THE ROOF OR CEILING WHICH FUNCTIONS AS THE BUILDING?S
 THERMAL ENVELOPE SHALL BE INSULATED TO AN R -VALUE OF
 AT LEAST R-10. ROOF INSULATION SHALL NOT BE INSTALLED
 ON A SUSPENDED CEILING WITH REMOVABLE CEILING PANELS.
 SEE SECTION 13-B-1.3 FOR INSULATION INSTALLATION
 REQUIREMENTS.
 PROVIDE THE INSULATION PRODUCT APPROVAL OR ROOFING
 PRODUCT APPROVAL. "HIGHLIGHT" WHICH SUBSYSTEM SHALL BE
 USED.
  
 12)1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 12A) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12B)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 12C)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT DOORS (GLAZED) SINGLE & DOUBLE DOORS
 B) EXTERIOR HOLLOW METAL DOORS
 C) STRUCTURAL COMPONENTS: WOOD CONNECTORS, BUCKETS
 AND OR STRAPS
 D) WALL LOUVERS
 E) ROOFING ASSEMBLIES
 F)PRE-ENGINEERED A/C STANDS
  
 13) THE PRODUCT APPROVALS FOR ARCH STOREFRONT , PLEASE
 HIGHLIGHT WHICH GLAZING TO BE INSTALLED AND ALSO
 HIGHLIGHT WHICH MULLIONS SHALL BE USED.
  
 14) SHEET A-10 DETAIL D-10 IS MISSING A LEDGER BOARD AT
 THE CORNER WHERE THE WALL AND CEILING MEET.
  
 15)S-1 PLANS DO NOT PROVIDE INFORMATION FOR TERMITE
 SOIL TREATMENT.
 1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.?
  
 16)IMPACT FEES: PLEASE SEND PLANS TO PALM BEACH
 COUNTY
 BUILDING DEPARTMENT FOR ASSESSMENT. NOTE THERE MAY BE A
  
 TAX DECREASE SINCE ZONING IS REQUIRING A 5'-0" SET BACK
 ON
 THE REBUILD PORTION OF THE PROJECT.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW