| Plan Review Notes For Permit 06120398 |
| Permit Number |
06120398 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-26 14:18:40 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN | | | REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL | | | THE PERMIT APPLICATION HAS BEEN | | | APPROVED BY ZONING FOR | | | THE PROPOSED 300# LP TANKLOCATION. PLEASE NOTE THAT | | | ZONING COMMENTS STATE PROPOSED TANK SHALL NOT BE CLOSER | | | THAN 4.5FT FROM PROPERTY LINE TO SIDE OF TANK, THE TANK | | | WIDTH IS 24 INCHES THAT LEAVES ABOUT 24 TO 21 INCHES TO | | | THE STRUCTURE. PLEASE CLARIFY THE EXACT LOCATION OF THE | | | PROPOSED TANK ON THE RESUBMITTAL AND ADJUST THE | | | RESUBMITTED GAS DRAWINGS ACCORDINGLY. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | |
|