| Date |
Text |
| 2006-12-27 21:11:59 | ** UNSAT ** |
| | |
| | |
| | ** PLEASE KNOW, ANY REFERENCES TO THE FBC CHAPTER 1 IN |
| | THE FOLLOWING NOTES THE ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK |
| | BASED ON THE REMODEL AND 1200 SQ FT ADDITION OF $25K IS |
| | EXTREMELY LOW. PLEASE KNOW AN APPROPRIATE VALUE WILL BE |
| | ASSESSED AS REQUIRED USING THE FBC TABLES AS REQUIRED |
| | PER FBC ADMINISTRATIVE SECTION 108.3. |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER |
| | THE NEW 2005 NEC. |
| | THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON |
| | ELECTRICAL SHEETS. |
| | 2005 NFPA-2005 |
| | 2002 NFPA-72 |
| | PLANS MAY NOT REFERENCE LATEST EDITION AS THE STATE OF |
| | FLORIDA ONLY JUST ADOPTED THE NEW REVISIONS TO THE 2004 |
| | FBC AND THE 2005 NEC. |
| | |
| | 2) NOTE: PLEASE SEE2004 FBC R313, PLEASE SHOW ALL |
| | EXISTING OR NEW TO BE INSTALLED FOR SMOKE ALARMS AS |
| | REQUIRED PER NFPA-72 11-5.1.1, 11.8.3 PLEASE SEE THE |
| | EXISTING DWELLING SHALL BE BROUGHT UP TO THE CURRENT |
| | CODE AS REQUIRED BY THE SECTIONS GIVEN. |
| | PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR |
| | SMOKE DETECTORS, HOWEVER NOTES ON PLANS ALSO CALL FOR |
| | THESE TO BE 120V HARDWIRED W/ BATTERY BACK UP WHICH IS |
| | OK, HOWEVER PLEASE KNOW IF THESE ARE INDEED SMOKE |
| | DETECTORS AS DEFINED IN NFPA72, THESE WOULD BE DEVICES |
| | WHICH ONLY DETECT AND WOULD SIGNAL TO OTHER ALARM/HORN |
| | DEVICES. PLEASE KNOW AS PERSECTIONS GIVEN IF THESE |
| | ARE INDEED DEVICES WHICH DETECT AND ALSO SOUND AN |
| | ALARM, THEN THEY WOULD BE LABELED AS SA FOR SMOKE |
| | ALARMS. |
| | PLEASE ADJUST PLANS AND NOTES. |
| | PLEASE ALSO SEE NOTES ON PLANS CALL FOR THESE TO BE |
| | WIRED TO THE KITCHEN/BATH LIGHTS CIRCUIT AHEAD OF ANY |
| | SWITCHES WHICH IS ALSO OK, HOWEVER AS PER 210.12 THESE |
| | LIGHTING CIRCUITS WOULD NOW BE REQUIRED TO BE ARC FAULT |
| | PROTECTED. PLEASE SEE THE FOLLOWING COMMENT#3. |
| | PLEASE SEE THE SMOKE DEVICE LOCATED IN FAMILY ROOM |
| | SHALL BE LOCATED WITHIN 12INCHES OF THE HIGHEST POINT |
| | ON A FLAT CEILING. PLEASE SEE IF THE TRAY CEILING AS |
| | SHOWN IS 12 INCHES OR MORE THEN THE DEVICE NEEDS TO BE |
| | RELOCATED TO THIS HIGHEST POINT. |
| | |
| | 3) NOTE: PLEASE SEE 210.12 AS THIS REQUIRES ARC FAULT |
| | PROTECTION FOR ALL OUTLETS IN SLEEPING ROOMS. PLEASE |
| | LIST ALL THE REQUIRED CIRCUITS ON PANEL SCHEDULE. |
| | 408.4 |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE SERVICE RISER AND PANEL SCHEDULE |
| | MENTIONS FOR PANEL TO BE UPGRADED, HOWEVER RISER AND |
| | PANEL ALSO SHOWS PANEL AT 200 AMPS? PLEASE EXPLAIN |
| | THIS. |
| | PLEASE SEE IF THE PANEL IS INDEED BEING UPGRADED TO |
| | 225AMPS THEN PLEASE SEE THE FOLLOWING SECTIONS FOR THE |
| | CORRECT CONDUCTORS NEEDED. |
| | 310.15B6,310.16, 240.4 |
| | PLEASE CORRELATE AND ADJUST. |
| | PLEASE ALSO KNOW AS LOAD CALCULATIONS ARE NOT COMPLETE |
| | AT THIS TIME WITH ALL AS REQUIRED THE SIZE OF THE |
| | SERVICE CAN NOT BE VERIFIED. |
| | |
| | 5) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM |
| | DETAIL NOTES SECTIONS OF CODE FROM THE 1996 NEC. PLEASE |
| | KNOW IF PLANS ARE GOING TO REFERENCE CODES, PLEASE BE |
| | SURE TO USE THE 2005 NEC. |
| | |
| | 6) NOTE: PLEASE SEE MISSING THE FOOTER STEEL FROM THE |
| | REQUIRED PART OF THE GROUNDING ELECTRODE SYSTEM PER |
| | 250.50. ALL NEW FOOTER STEEL SHALL BE PART OF THE NEW |
| | SYSTEM. |
| | |
| | 7) NOTE: PLEASE SHOW THE LOCATIONS OF ALL SERVICE |
| | EQUIPMENT ON PLANS. METER/MAIN/PANEL ETC, UNABLE TO |
| | REVIEW LOCATIONS FOR CODE COMPLIANCE AT THIS TIME. |
| | 110.26, 240.24, 408.7, |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM MAIN DISCONNECT TO PANEL. PLEASE SEE |
| | RISER MENTIONS THIS IS GOING TO BE RIGID STEEL CONDUIT. |
| | PLEASE KNOW THIS IS NOT LIKELY AND THE USE OF PVC WILL |
| | MOST LIKELY BE INSTALLED WHICH WILL REQUIRE THIS |
| | EQUIPMENT GROUNDING CONDUCTOR. PLEASE SEE 250.24, |
| | 250.110 AND 250.122 FOR SIZING. |
| | |
| | 9) NOTE: PLEASE SEE PANEL SCHEDULE AND LOAD |
| | CALCULATIONS ARE VERY SMALL AND UNCLEAR. PLEASE SEE FBC |
| | ADMIN SECTION 106.1 AS THIS REQUIRES A MIN SCALE AND |
| | PLANS SHALL BE CLEAR AND VISIBLE WITH DRAFTSMAN LIKE |
| | QUALITY. |
| | PLEASE KNOW THERE ARE NUMEROUS ITEMS WHICH ARE LEFT |
| | BLANK. |
| | FBC 106.3.5.4 ADMIN SECTION. |
| | |
| | 10) NOTE: PLEASE SUBMIT THE AIC RATING FOR THE NEW |
| | PROPOSED MAIN DISCONNECT. THE 10K AS SHOWN ON THE SUB |
| | PANEL WAS NOTED; HOWEVER THE RATING FOR THE MAIN IS |
| | REQUIRED. |
| | 110.9 |
| | |
| | 11) NOTE: PLEASE SEE THERE ARE NUMEROUS CIRCUITS ON THE |
| | PANEL SCHEDULE WHICH ARE SHOWING LOADS WHICH FAR EXCEED |
| | THE RATINGS OF THE BRANCH CIRCUIT BEING SHOWN AND/OR |
| | PROVIDED. |
| | PLEASE SEE SOME OF THE FOLLOWING; HOWEVER THIS WILL NOT |
| | BE ALL AS THE PANEL SCHEDULE SHOWS MORE THAN LISTED |
| | BELOW |
| | DISHWASHER, 2KW ON A 20A CIRCUIT? |
| | REFRIGERATOR, 2KW SAME? |
| | DISPOSAL, 2KW SAME? |
| | LIGHTING CIRCUIT 5 KW ON EACH OF THEM?? |
| | RANGE 20KW? |
| | SMALL APPLIANCE CIRCUITS 5KW? |
| | WASHER AT 5KW? |
| | ETC. |
| | PLEASE SEE THE NEC 2005 210, 220, 240, ETC AS THERE ARE |
| | TOO MANY SECTIONS OF THE CODE TO LIST. |
| | PLEASE BE SURE TO CORRELATE ALL OF THE OVER CURRENT |
| | PROTECTION DEVICES, CONDUCTORS SIZES AND LOADS. |
| | 240.4, 310.16, 210.21, 210.23, 210.24 ETC |
| | |
| | 12) NOTE: PLEASE SEE THERE ARE AREAS OF THE LOAD |
| | CALCULATIONS AT THE BOTTOM OF THE PANEL SCHEDULE WHICH |
| | DOES NOT INDICATE ANY LOAD. THE SPACE IS ACTUALLY SHOWN |
| | AS OO? |
| | PLEASE SHOW COMPLETE LOAD CALCULATIONS PER THE 2005 |
| | NEC. PLEASE SEE 220.14, 220.52, 220.82, 220.83 ETC ONLY |
| | SOME SECTIONS ARE NOTED. |
| | |
| | 13) NOTE: PLEASE CORRELATE A/C SYSTEMS ON PLANS. PLEASE |
| | SEE TWO AIR HANDLER UNITS ARE SHOWN HOWEVER ONLY ONE |
| | CONDENSING UNIT IS SHOWN? |
| | PLEASE SEE PANEL SCHEDULE ONLY LIST ONE AHU AT 6KW WITH |
| | 50A OVER CURRENT PROTECTION? |
| | PLEASE VERIFY AS THE COOLING LOAD ON THE ONLY A/C |
| | SYSTEM SHOWN ON THE PANEL SCHEDULE. PLEASE SEE 424.3B |
| | FOR THE MINIMUM SIZING FOR OCP. PLEASE SEE SECTIONS |
| | GIVEN ABOVE FOR LOADS AND HOW THEY ARE TO BE FIGURED IN |
| | LOAD CALCULATIONS. 220.18A |
| | PLEASE SEE 7.5KW LOAD ON 30A BREAKER FOR CU WHICH |
| | EXCEEDS RATING OF BREAKER. |
| | |
| | 14) NOTE: PLEASE SEE MISSING DISCONNECT REQUIRED FOR |
| | WHAT APPEARS TO BE THE ONE NEW AHU IN CLOSET. 440.11. |
| | (110.26 WHERE APPLICABLE IN DESIGN) |
| | |
| | 15) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS ON |
| | PLANS WHICH INDICATE 2KW LOAD WITH 5(FIVE) AMP |
| | BREAKERS? |
| | PLEASE CLARIFY FIRST THE LOAD AND THE REQUIRED MINIMUM |
| | CIRCUIT OVER CURRENT PROTECTION SIZE AND PLEASE ADJUST |
| | PANEL SCHEDULE AS SUBMITTED. |
| | PLEASE KNOW THIS REVIEWER HAS NOT SEEN 5AMP BREAKERS |
| | FOR BREAKER PANELS? |
| | |
| | 16) NOTE: PLEASESEE PLANS INDICATES A NEW JACUZZI |
| | TUB, IF THIS IS ELECTRIC PLEASE INDICATE ON PANEL |
| | SCHEDULE, PLEASE INDICATE IN LOAD CALCULATIONS AND |
| | PLEASE SEE 680.71 FOR INDICATION OF THE REQUIRED GFI |
| | PROTECTION. |
| | |
| | 17) NOTE: PLEASE SEE PLANS WHICH INDICATE SEVERAL ROOMS |
| | WHICH SHOW MORE THAN ONE SWITCH CONTROLLING LIGHTING |
| | ETC. PLEASE INDICATE THE DEVICES AS 3-WAY OR 4-WAY |
| | SWITCHES. PLEASE ALSO CORRELATE WITH THE SYMBOL |
| | LEGEND. |
| | PLEASE SEE THE SYMBOL LEGEND CONTAINS THESE SYMBOLS; |
| | HOWEVER THE PLANS DO NOT SHOW. |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 18) NOTE: PLEASE SEE PLANS INDICATE NEW LOCATION FOR |
| | POOL EQUIPMENT; HOWEVER PLEASE SEE PANEL SCHEDULE LIST |
| | ONLY ONE PUMP. PLEASE SEE MISSING DISCONNECTING MEANS |
| | AS REQUIRED PER 680.21 OR MEETING EXCEPTIONS. |
| | |
| | 19) NOTE: PLEASE SEE PLANS INDICATE A SPRINKLER PUMP, |
| | HOWEVER NO DISCONNECT NO LISTING ON PANEL SCHEDULE AND |
| | NO LOADS ARE INCLUDED IN LOAD CALCULATIONS FOR THIS. |
| | THESE ITEMS CAN NOT BE REVIEWED AS NOTHING WAS SHOWN. |
| | 240.4, 310.16, 430.6 ETC |
| | FBC 106.1.2 ADMIN SECITON. |
| | |
| | 20) NOTE: PLEASE SEE ALL CONDUCTOR SIZES AS SHOWN ON |
| | PANEL SCHEDULE SEEM TO BE MISSING THE NUMBER ONE IN |
| | FRONT OF ALL WIRE SIZES. PLEASE SEE WHAT SHOULD BE A |
| | #10 IS #0, A #12 IS #2, ETC |
| | PLEASE COMPLETE PANEL SCHEDULE. 106.1.2, 106.3.5.4 |
| | NEC 240.4, 310.16, 408.4 |
| | |
| | 21) NOTE: PLEASE PLACE ROOM DESIGNATIONS ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULE WHICH IS TO BE |
| | REVISED. IE: BEDROOM #1 RECEPTS, BEDROOM #2 LTS, |
| | KITCHEN LTS ETC |
| | 408.4, 240.4, 310.16 |
| | UNABLE TO REVIEW FOR CIRCUITS, ALSO AS NOTED ABOVE WITH |
| | RESPECT TO 5KW LOADS ON LIGHTING CIRCUITS. |
| | |
| | 22) NOTE: PLEASE SEE MISSING THE DEDICATE BATH |
| | RECEPTS/BATH ROOM CIRCUIT(S) PER 210.52D, 210.11C3. |
| | |
| | 23) NOTE: PLEASE SEE ONE OF THE NEW BATHROOMS IS |
| | MISSING THE REQUIRED GFI WHICH IS TO BE LOCATED WITHIN |
| | 3FT OF LAVATORY/SINK'S EDGE. |
| | PLEASE SEE 210.52D, 210.8A2 |
| | |
| | 24) NOTE: PLEASE SEE 410.8 AS THE LIGHT FIXTURE IN THE |
| | BATHROOM CLOSET APPEARS TO BE TOO CLOSE TO THE |
| | SHELVING. |
| | |
| | 25) NOTE: PLEASE SEE 210.52 FOR SEVERAL MISSING |
| | REQUIRED RECEPTACLE FOR WALL SPACES 2FT OR MORE. PLEASE |
| | SEE ONE SET OF PLANS ARE REDLINED FOR MOST LOCATIONS. |
| | |
| | 26) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.52A FOR |
| | MISSING DINING AND OTHER SIMILAR AREAS AND CIRCUITING, |
| | LOADS AS REQUIRED. |
| | |
| | 27) NOTE: PLEASE SEE OTHER REVIEWER COMMENTS ALSO; |
| | HOWEVER PLEASE SEE THE PERMIT APPLICATION PACKAGE IS |
| | MISSING ENERGY CALCULATIONS AS REQUIRED PER FBC CHAPTER |
| | 13. |
| | PLEASE ALSO SEE 13-103.1.1.1 FOR LISTING FOR TYPE OF |
| | RECESSED LIGHTING FIXTURE TO BE NOTED ON PLANS. |
| | |
| | 28) NOTE: PLEASE SEE ONE OF THE NEW BEDROOMS WHICH SHOW |
| | TWO SWITCHES LOCATED ON THE WALL WHICH DO NOT SHOW |
| | CONTROL FOR ANYTHING? |
| | PLEASE COMPLETE OR REMOVE. |
| | FBC 106.1.2, 106.3.5.4 ADMIN SECTION. |
| | |
| | 29) NOTE: PLEASE SEE FLORIDA STATUTES 471.025(3). |
| | PLEASE KNOW DUE TO EXTENT OF THE ELECTRICAL COMMENTS, |
| | ONE SET OF ELECTRICAL PLANS ARE BEING RETAINED BY THIS |
| | OFFICE FOR POSSIBLE REVIEW BY THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS. |
| | PLEASE ALSO KNOW AT THE END OF THE REVIEW PROCESS FROM |
| | ALL TRADES, IF COMMENTS FOR OTHER TRADES ARE AS |
| | ELECTRICAL, ONE ENTIRE SET MAY BE RETAINED. |
| | PLEASE KNOW THAT NOTICES HAVE BEEN GIVEN TO THIS DESIGN |
| | PROFESSIONAL ON SEVERAL OTHER PROJECTS WHICH HAVE BEEN |
| | SIGNED, DATED AND SEALED BY THIS ENGINEER FOR |
| | ELECTRICAL AND AS PER THE SECTION IN THE FLORIDA |
| | STATUTES ABOVE: |
| | (3)NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED |
| | HIS OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY |
| | PLAN, SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR |
| | OTHER DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT |
| | LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER |
| | PROFESSION OR SPECIALTYTHEREIN. |
| | |
| | 30) NOTE: PLEASE KNOW ALSO DUE TO THE EXTENT OF THE |
| | ELECTRICAL COMMENTS THERE MAY BE NEW COMMENTS ON THE |
| | FOLLOWING REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |