Text |
| 2007-08-27 18:33:44 | | | | *** DENIED REVIEW *** | | | | | | 1) NOTE: PLEASE SUBMIT PLANS WHICH CORRELATE. PLEASE | | | SEE EACH SHEET CONTAINS TWO COMPLETELY DIFFERENT PANEL | | | SCHEDULES FOR CIRCUITING. | | | PLEASE SEE EACH SHEET FOR POWER AND LIGHTING ALSO | | | CONTAINS ITEMS WHICH ARE BEING FED FROM SEPARATE | | | CIRCUITS TO THE SAME ITEMS DEPENDING ON THE PANEL | | | SCHEDULE YOU LOOK AT. | | | 408.4, 310.16, 240.4 | | | FBC 106.1.3, 106.3.5.4 | | | | | | 2) NOTE: PLEASE SEE THE RE-LOCATED OVEN MENTIONS THIS | | | WILL HAVE A BREAKER LOCK OFF DEVICE. ** IMPORTANT, | | | PLEAS KNOW THAT THE TYPE OF DEVICE MUST HAVE THE LOCK | | | OFF MECHANISM PERMANENTLY A PART OF THE BREAKER. *SNAP | | | OR CLIP ON TYPE DEVICES ARE NOT ACCEPTABLE AND A | | | DISCONNECTING MEANS WILL BE REQUIRED. | | | ** 110.3, 90.4, 422.30, 422.31 | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|