| Date |
Text |
| 2006-12-27 19:13:40 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER |
| | THE NEW 2005 NEC. |
| | THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON |
| | ELECTRICAL SHEETS. |
| | 2005 NFPA-2005 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE FBC R313, PLEASE SHOW ALL EXISTING |
| | OR NEW TO BE INSTALLED SMOKE ALARMS AS REQUIRED PER |
| | NFPA-72 11-5.1.1, 11.8.3 |
| | |
| | 3) NOTE: PLEASE VERIFY RECEPTACLE SPACING FOR NEW WALL |
| | AREAS IN ADDITION AREA OF KITCHEN/BREAKFAST AREA PER |
| | 210.52. PLEASE SEE WALLS 2FT OR MORE. |
| | |
| | 4) NOTE: PLEASE SEE 210.52B1 WHICH REQUIRES ALL |
| | RECEPTACLE CIRCUITS IN DINING, KITCHEN, BREAKFAST AREAS |
| | AND AREAS OF THE LIKE TO BE ON ONE OR MORE OF THE SMALL |
| | APPLIANCE CIRCUITS. |
| | PLEASE SEE PANEL SCHEDULES DO NOT INDICATE THESE. ? |
| | PLEASE SEE LOAD CALCULATIONS FOR SERVICE SEEM TO SHOW |
| | 3- SMALL APPLIANCE CIRCUITS, HOWEVER THESE ARE NOT |
| | LISTED ON EITHER PANEL SCHEDULE? |
| | PLEASE KNOW IF THERE ARE MORE THAN 3, THEN THE LOADS |
| | SHALL BE FIGURED ACCORDINGLY. |
| | PLEASE SEE THE FOLLOWING SECTIONS. 210.52B1, 210.11B1, |
| | 220.52A |
| | |
| | 5) NOTE: PLEASE INDICATE A NEW OR EXISTING GFI RECEPT |
| | LOCATED AT THE NEW CONDENSING UNIT BEING ADDED AT THE |
| | SIDE OF DWELLING. PLEASE SEE 210.63 AND 210.8A3. |
| | |
| | 6) NOTE: PLEASE SEE NEW LIVING ROOM WHICH WILL REQUIRE |
| | A LIGHT FIXTURE OF SOME KIND TO BE INSTALLED. PLEASE |
| | SEE OTHER EXCEPTIONS IN 210.70 WHICH WILL PERMIT THE |
| | SWITCHING OF ? SWITCHED RECEPT ? OR RECESSED LTS. |
| | PLEASE SEE LS 101 7.8 |
| | |
| | 7) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS WHEN |
| | ADDING HEAT LOAD TO AN EXISTING DWELLING. PLEASE SEE |
| | THE HEAT LOADS FOR UNITS SHALL BE FIGURED AT 100% AS |
| | SHOWN ON PANEL B. |
| | THIS DOES PERMIT THE FIRST 8KVA AT 100% REMAINDER AT |
| | 40%,INSTEAD OF THE FIRST 10KVA AT 100% ,THEN HEAT AT |
| | 100%. |
| | |
| | 8) NOTE: PLEASE SEE 220.14D WHICH IF THE AMOUNT OF |
| | RECESSED LIGHTS IN DWELLING ARE ABOVE 20, THEN THE |
| | TOTAL NUMBER SHALL BE BASED ON THE MAXIMUM WATTAGE PER |
| | FIXTURE TIMES THE AMOUNT OF FIXTURES ADDED TO THE 3VA |
| | PER SQ FT. |
| | PLEASE SEE THE 2002 NEC SECTION 220.3(B)(4) |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |