| Date |
Text |
| 2007-01-26 18:02:40 | DENIED BY BUILDING |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3)BASED ON THE 2006 SUPPLEMENT TO THE 2004 FBC |
| | RESIDENTIAL EFFECTIVE DECEMBER 8, 2006, THE EXPOSURE |
| | CATEGORY FOR THIS PROJECT IS EXPOSURE C. PLEASE MAKE |
| | ALL NECESSARY CORRECTIONS. |
| | |
| | 4)SUBMIT A SUBSURFACE SOIL REPORT. FBC 1802.2.1 |
| | QUESTIONABLE SOILS, |
| | 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 5)THE PROPERTY IS LOCATED IN AN A5 FLOOD ZONE. THE |
| | MINIMUM ELEVATION FOR THE FINISHED FLOOR IS 7' 6", |
| | WHICH INCLUDES THE 6" FREEBOARD REQUIRED BY THE CITY OF |
| | WEST PALM BEACH. AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | 6)PLEASE UPDATE THE STRUCTURAL NOTES ON SHEET A0. THE |
| | 2006 AMENDMENTS TO THE 2004 FBC WILL APPLY TO THIS |
| | PROJECT. ALSO, THE 2002 EDITIONS OF ACI- 315, 318 AND |
| | 530 APPLY PER THE REFERENCED STANDARDS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 7)ROOF SHEATHING FASTENER SPACING IS REQUIRED TO |
| | COMPLY WITH FBC R803.2.3.1 (2006 AMENDMENTS) . WOOD |
| | STRUCTURAL PANELS SHALL BE FASTENED TO ROOF FRAMING |
| | WITH 8D RING- SHANK AT 6 INCHES ON CENTER AT EDGES AND |
| | 6 INCHES ON CENTER AT INTERMEDIATE FRAMING. SPACING OF |
| | RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN |
| | NAILING ZONE 3FOR 130MPH OR GREATER DESIGN WIND |
| | SPEEDS. PLEASE REVISE NOTE ON A6. |
| | |
| | 8) PLEASE SPECIFY THE NUMBER OF FASTENERS AND CORRECT |
| | THE FASTENER TYPE FOR THE SIMPSON HETAL 20 CONNECTORS |
| | IN THE TRUSS ANCHOR SCHEDULE ON A6. |
| | |
| | 9) SHOW COMPLIANCE WITHR320.1. |
| | TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED |
| | TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, |
| | BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR |
| | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| | FOR USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION |
| | (SEE SECTION 202 , REGISTERED TERMITICIDE). UPON |
| | COMPLETION OF THE APPLICATION OF THE TERMITE PROTECTIVE |
| | TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL BE ISSUED |
| | TO THE BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL |
| | COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE |
| | BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE |
| | PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN |
| | ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE |
| | FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER |
| | SERVICES.? |
| | |
| | 10) SUBMIT TRUSS DRAWINGS AS REQUIRED BY R802.10.1. |
| | TRUSS DESIGN DRAWINGS. |
| | TRUSS DESIGN DRAWINGS, PREPARED IN CONFORMANCE WITH |
| | SECTION R802.10.1 , SHALL BE PROVIDED TO THE BUILDING |
| | OFFICIAL AND APPROVED PRIOR TO INSTALLATION. THE TRUSS |
| | LAYOUT AND TRUSS DRAWING ARE REQUIRED TO BE SIGNED, |
| | SEALED AND DATED BY THE TRUSS ENGINEER AND REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE |
| | PROJECT. |
| | |
| | 11) SPECIFY THE TRUSS DEAD AND LIVE LOADS FOR THE TOP |
| | AND BOTTOM CORDS AND TOTAL LOADS ON THE PLANS. |
| | |
| | 12)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 13) THE PRODUCT APPROVAL FOR THE POLYGLASS MODIFIED |
| | BITUMEN ROOF SYSTEM ON PAGE 37 OF NOA 06-0410.06 HAS A |
| | MAXIMUM DESIGN PRESSURE OF -45 WITH LIMITATION NUMBER |
| | 9. THIS LIMITATION DOES NOT ALLOW ENHANCED FASTENING |
| | WHICH IS REQUIRED TO ACHIEVE THE UPLIFT PRESSURES OF |
| | ROOF ZONES 2 AND 3. PLEASE ALSO NOTE THAT LIMITATION |
| | NUMBER 7 OF THIS NOA REQUIRES SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR ENHANCED FASTENING. |
| | |
| | 14)SPECIFYTHE METHOD OF ATTACHMENT THAT WILL BE |
| | USED TO INSTALL THE MONIER CONCRETE ROOF TILE. PLEASE |
| | CIRCLE THE APPROPRIATE FASTENER OR ADHESIVE SYSTEM ON |
| | THE NOA. PLEASE BE SURE THAT THE ATTACHMENT SELECTED |
| | WILL PROVIDE ADEQUATE RESISTANCE FOR A MOMENT BASED |
| | SYSTEM. |
| | |
| | NOTE: SEE MARKS ON THE PLAN. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |