| Plan Review Notes For Permit 06120362 |
| Permit Number |
06120362 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-24 19:42:24 | *****UNSAT***** | | | | | | THE PREVIOUS FIRE PLAN REVIEW WHICH STILL NEED TO BE | | | ADDRESSED:(CAPS INDICATE HOW COMMENTS ARE TO BE | | | ADDRESSED) | | | | | | 04.CONSTRUCTION AND / OR DEMOLITION OPERATIONS SHALL | | | NOT INTERFERE OR HINDER WITH ACCESS TO OR EGRESS FROM | | | THE FLOOR(S) OR BUILDING.ADD COMMENT TO SHEET A-2 | | | | | | 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | ADD COMMENT TO SHEET A-2 | | | | | | 07. WHAT IS THE INTERIOR FINISH CLASSIFICATION FOR THE | | | WALLS SND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, | | | AND IN ALL OTHER AREA?ADD YOUR RESPONSE " ALL | | | INTERIOR FINISHES WILL MEET CLASS A FLAME SPREAD | | | RATING"TO SHEET CS-1 OR A-1 | | | | | | 09.ALTHOUGH THIS ELEVATOR WILL SERVE ONLY TWO FLOORS, | | | IT STILL SHALL CONFORM TO THE REQUIREMENTS OF ASME | | | A17.1ADD TO SHEET A-4 - ELEVATORS TO CONFORM TO | | | THE REQUIREMENTS OF ASME A17.1 | | | | | | NEW COMMENT | | | | | | A.ON SHEET CS-1 UNDER THE DRAWING LIST, IT STATES | | | THAT THERE IS A SHEET NUMBER A-1 HOWEVER, NO SUCH SHEET | | | IS INCLUDED IN THE SUBMITTED PLANS.PLEASE ADD SHEET | | | A-1 OR AMEND SHEET CS-1 | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|