Plan Review Notes
Plan Review Notes For Permit 06120362
Permit Number 06120362
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-31 20:22:02** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS DUE TO
 INFORMATION NOW SUBMITTED OR CHANGES MADE TO PLANS.
  
  
 1) NOTE: PLEASE SEE THAT THIS BUILDING IS STILL IN
 QUESTION FOR THE SERVICE, METERING, ADDRESSING ETC.
 AT THIS TIME AS THIS HAS BEEN CHANGE TO A *CONDO* THIS
 WOULD APPEAR TO BE A CHANGE IN OCCUPANCY WHICH WOULD
 NOT ONLY REQUIRE A PERMIT FOR THE CHANGE IN OCCUPANCY
 IT WOULD ALSO REQUIRE BUILDING ELECTRICAL SYSTEMS TO BE
 BROUGHT UP TO CODE FOR COMPLETE ELECTRICAL CODE
 COMPLIANCE UNDER THE CURRENT CODES AND STANDARDS.
 THIS WOULD INCLUDE ELECTRICAL, FIRE SYSTEMS, FLORIDA
 BUILDING CODE AND OTHER TRADES. THIS INFORMATION IS
 CURRENTLY BEING CONFIRMED.
 PLEASE SEE FBC FOR CHANGES IN OCCUPANCY.
 FBC 106.1, CHAPTER 13, CHAPTER 27 ETC.
  
 2) NOTE: PLEASE SEE SOME SUPPORTING DOCUMENTATION STILL
 CONTAINS AN ADDRESS OF 106 S OLIVE.
 PLEASE KNOW AS THE COMMENT ABOVE STATES THE ADDRESS,
 THE BUILDING AND USE WILL NEED TO BE VERIFIED.
 FAC 61G15-23, 61G1-16
  
 3) NOTE: PLEASE KNOW AS THE PREVIOUS REVIEW CONTAINED
 NOTES FOR SPECIFIC CODES, THIS COMMENT WILL REMAIN OPEN
 UNTIL CHANGE IN OCCUPANCY IS CLARIFIED.
  
 4) NOTE:PLEASE CLARIFY IF THERE IS AN EQUIPMENT ROOM
 FOR ELEVATOR EQUIPMENT. PLEASE ALSO SEE 620.22, 23 AND
 24. RESPONSE MENTIONS THIS IS A LULA UNIT? PLEASE
 SUBMIT MANUFACTURES SPECS/CUT SHEETS ON THIS UNIT WHICH
 CONTAINS THIS INFORMATION. 110.3,90.7
 IF THERE IS AN EQUIPMENT ROOM AND EMERGENCY BATTERY
 BACK UP LIGHT OF SOME KIND WILL BE REQUIRED.
 LS 101 7.8, 700.16 ETC
  
 5) NOTE:PLEASE SEE THE PREVIOUS REVIEW NOTES WITH
 RESPECT TO LIGHTING CONTROLS. PLEASE SEE THAT EACH
 FLOOR IS REQUIRED TO CONTAIN A SEPARATE SYSTEM.
 PLEASE SEE THE NOTES ON PLANS MENTIONS A *TIME CLOCK
 WILL OVER RIDE THE LCP FOR A TIME OF 10HRS*? PLEASE
 SPECIFY THE TIME SCHEDULING FOR THE LCP. PLEASE SEE THE
 RESPONSE LETTER APPEARS TO REFERENCE THE CORRECT TIMES,
 HOWEVER PLEASE EXPAND ON THE MAXIMUM PERMITTED OVER
 RIDE TIMES ON PLANS.
 PLEASE CLARIFY THE LIGHTING CONTROL PANELS AS PLANS
 SEEM TO SHOWN ONE BRAND AND RESPONSE LETTER MENTIONS A
 DIFFERENT PANEL.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE
 IF INSTALLING A SYSTEM TO SEE REQUIREMENTS FOR MULTIPLE
 FLOORS. PLEASE SEE THAT IF USING ALL OCCUPANCY SENSOR
 TYPE DEVICES PLEASE STATE THE MAXIMUM TIMES, OR MAXIMUM
 TIMES ON ANY OVER RIDE DEVICES.
 PLEASE SEE THAT THE ENERGY CALCULATIONS ARE THE SAME AS
 PREVIOUSLY SUBMITTED. PLEASE SEE THE VERSION OF THE
 CALCULATIONS IS NOT CORRECT. PLEASE KNOW THE VERSION AS
 SUBMITTED IS FROM THE PREVIOUS CODE CHANGE BEFORE THE
 REVISIONS DATED DECEMBER 8TH, 2006. PLEASE SEE THE
 LIGHTING CONTROL METHODS ARE STILL SHOWN AS *MANUAL
 ON/OFF* WHICH IS NOT POSSIBLE WHEN THE PLANS CONTAIN
 AUTOMATED MEANS.
 THIS INCLUDES RELOCATED LIGHTING WHICH MAY OR MAY NOT
 BE USED BASED ON WHETHER OR NOT THEY MEET THE NEW
 CODE(S).
 PLEASE SEE 13-415.1.AB.1, 13-415.1.A,13-415.2,AND
 13-415.2.ABC.1 AND TABLES FOR USE ETC.
  
 6) NOTE: PLEASE SEE THE PHOTO-METRICS AS SUBMITTED.
 PLEASE CLARIFY WHERE THE EMERGENCY LEVELS ARE SHOWN.
 BASED ON THE FIXTURES AS SHOWN THE LEVELS APPEAR TO
 MORE THAN ADEQUATE FOR EM LEVELS, HOWEVER PLEASE KNOW
 THE RECORD PLANS SHOULD STATE EACH AS REQUIRED PER FAC
 61G15-33.004 AND THE LS SECTIONS AS GIVEN ON PREVIOUS
 REVIEW.
 PLEASE SEE 7.8.1.3, AND 7.9.2.2 WHICH REQUIRES A
 MINIMUM OF 10FT CANDLES UNDER NORMAL AND 1FT CANDLE
 UNDER EMERGENCY.
 PLEASE SEE CONTROLS FOR LIGHTING SHALL ALSO BE
 INDICATED, AND ANY OVER RIDES DEVICES OR NIGHT LIGHTS.
  
 7) NOTE: PLEASE SHOW ALL EXISTING ELECTRICAL IN THE 7TH
 FLOOR AREA FOR ELECTRICAL. THIS WOULD INCLUDE POWER AND
 LIGHT EVEN IN ROOMS NO WORK IS BEING DONE.THE SCOPE
 OF WORK BASE DON THE EXISTING BUILDING CODE AND CHANGE
 IN OCCUPANCY REQUIRES ALL TO MEET CODE EVEN IF NOT
 DOING WORK IN A PARTICULAR ROOM(S) AS SHOWN ON THE 7TH
 FLOOR.
 PLEASE KNOW THE LIGHTING WILL BE REQUIRED TO MEET
 CHAPTER 13 OF THE FBC FOR CONTROLS AND PERFORMANCE
 CALCULATIONS AS THIS SPACE IS BEING INCLUDED INTO THE
 NEW SINGLE TENANT.
  
 8) NOTE: PLEASE SEE BOTH THE AHU AND THE ELEVATOR
 EQUIPMENT IS BEING SHOWN CONNECTED TO A RECEPTACLE
 WHICH IS NOT PERMITTED.
 PLEASE SEE THESE ARE REQUIRED TO BE HARDWIRED AND
 DISCONNECTS.
 422.30,31, 440.11, 620.51 ETC.
  
 9) NOTE: PLEASE KNOW THE CONTRACTOR OWES FEES AS THE
 VALUE ON PERMIT APPLICATION WAS INCREASED.
 FEE OWES IS CURRENTLY AT $1665.00.
  
 10) NOTE: PLEASE SEE AS SOME COMMENTS ARE REPEATED FROM
 PREVIOUS REVIEW, PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND REPEATED CODE
 COMPLIANT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  