| 2007-07-31 20:22:02 | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS DUE TO |
| | INFORMATION NOW SUBMITTED OR CHANGES MADE TO PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THAT THIS BUILDING IS STILL IN |
| | QUESTION FOR THE SERVICE, METERING, ADDRESSING ETC. |
| | AT THIS TIME AS THIS HAS BEEN CHANGE TO A *CONDO* THIS |
| | WOULD APPEAR TO BE A CHANGE IN OCCUPANCY WHICH WOULD |
| | NOT ONLY REQUIRE A PERMIT FOR THE CHANGE IN OCCUPANCY |
| | IT WOULD ALSO REQUIRE BUILDING ELECTRICAL SYSTEMS TO BE |
| | BROUGHT UP TO CODE FOR COMPLETE ELECTRICAL CODE |
| | COMPLIANCE UNDER THE CURRENT CODES AND STANDARDS. |
| | THIS WOULD INCLUDE ELECTRICAL, FIRE SYSTEMS, FLORIDA |
| | BUILDING CODE AND OTHER TRADES. THIS INFORMATION IS |
| | CURRENTLY BEING CONFIRMED. |
| | PLEASE SEE FBC FOR CHANGES IN OCCUPANCY. |
| | FBC 106.1, CHAPTER 13, CHAPTER 27 ETC. |
| | |
| | 2) NOTE: PLEASE SEE SOME SUPPORTING DOCUMENTATION STILL |
| | CONTAINS AN ADDRESS OF 106 S OLIVE. |
| | PLEASE KNOW AS THE COMMENT ABOVE STATES THE ADDRESS, |
| | THE BUILDING AND USE WILL NEED TO BE VERIFIED. |
| | FAC 61G15-23, 61G1-16 |
| | |
| | 3) NOTE: PLEASE KNOW AS THE PREVIOUS REVIEW CONTAINED |
| | NOTES FOR SPECIFIC CODES, THIS COMMENT WILL REMAIN OPEN |
| | UNTIL CHANGE IN OCCUPANCY IS CLARIFIED. |
| | |
| | 4) NOTE:PLEASE CLARIFY IF THERE IS AN EQUIPMENT ROOM |
| | FOR ELEVATOR EQUIPMENT. PLEASE ALSO SEE 620.22, 23 AND |
| | 24. RESPONSE MENTIONS THIS IS A LULA UNIT? PLEASE |
| | SUBMIT MANUFACTURES SPECS/CUT SHEETS ON THIS UNIT WHICH |
| | CONTAINS THIS INFORMATION. 110.3,90.7 |
| | IF THERE IS AN EQUIPMENT ROOM AND EMERGENCY BATTERY |
| | BACK UP LIGHT OF SOME KIND WILL BE REQUIRED. |
| | LS 101 7.8, 700.16 ETC |
| | |
| | 5) NOTE:PLEASE SEE THE PREVIOUS REVIEW NOTES WITH |
| | RESPECT TO LIGHTING CONTROLS. PLEASE SEE THAT EACH |
| | FLOOR IS REQUIRED TO CONTAIN A SEPARATE SYSTEM. |
| | PLEASE SEE THE NOTES ON PLANS MENTIONS A *TIME CLOCK |
| | WILL OVER RIDE THE LCP FOR A TIME OF 10HRS*? PLEASE |
| | SPECIFY THE TIME SCHEDULING FOR THE LCP. PLEASE SEE THE |
| | RESPONSE LETTER APPEARS TO REFERENCE THE CORRECT TIMES, |
| | HOWEVER PLEASE EXPAND ON THE MAXIMUM PERMITTED OVER |
| | RIDE TIMES ON PLANS. |
| | PLEASE CLARIFY THE LIGHTING CONTROL PANELS AS PLANS |
| | SEEM TO SHOWN ONE BRAND AND RESPONSE LETTER MENTIONS A |
| | DIFFERENT PANEL. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE SEE |
| | IF INSTALLING A SYSTEM TO SEE REQUIREMENTS FOR MULTIPLE |
| | FLOORS. PLEASE SEE THAT IF USING ALL OCCUPANCY SENSOR |
| | TYPE DEVICES PLEASE STATE THE MAXIMUM TIMES, OR MAXIMUM |
| | TIMES ON ANY OVER RIDE DEVICES. |
| | PLEASE SEE THAT THE ENERGY CALCULATIONS ARE THE SAME AS |
| | PREVIOUSLY SUBMITTED. PLEASE SEE THE VERSION OF THE |
| | CALCULATIONS IS NOT CORRECT. PLEASE KNOW THE VERSION AS |
| | SUBMITTED IS FROM THE PREVIOUS CODE CHANGE BEFORE THE |
| | REVISIONS DATED DECEMBER 8TH, 2006. PLEASE SEE THE |
| | LIGHTING CONTROL METHODS ARE STILL SHOWN AS *MANUAL |
| | ON/OFF* WHICH IS NOT POSSIBLE WHEN THE PLANS CONTAIN |
| | AUTOMATED MEANS. |
| | THIS INCLUDES RELOCATED LIGHTING WHICH MAY OR MAY NOT |
| | BE USED BASED ON WHETHER OR NOT THEY MEET THE NEW |
| | CODE(S). |
| | PLEASE SEE 13-415.1.AB.1, 13-415.1.A,13-415.2,AND |
| | 13-415.2.ABC.1 AND TABLES FOR USE ETC. |
| | |
| | 6) NOTE: PLEASE SEE THE PHOTO-METRICS AS SUBMITTED. |
| | PLEASE CLARIFY WHERE THE EMERGENCY LEVELS ARE SHOWN. |
| | BASED ON THE FIXTURES AS SHOWN THE LEVELS APPEAR TO |
| | MORE THAN ADEQUATE FOR EM LEVELS, HOWEVER PLEASE KNOW |
| | THE RECORD PLANS SHOULD STATE EACH AS REQUIRED PER FAC |
| | 61G15-33.004 AND THE LS SECTIONS AS GIVEN ON PREVIOUS |
| | REVIEW. |
| | PLEASE SEE 7.8.1.3, AND 7.9.2.2 WHICH REQUIRES A |
| | MINIMUM OF 10FT CANDLES UNDER NORMAL AND 1FT CANDLE |
| | UNDER EMERGENCY. |
| | PLEASE SEE CONTROLS FOR LIGHTING SHALL ALSO BE |
| | INDICATED, AND ANY OVER RIDES DEVICES OR NIGHT LIGHTS. |
| | |
| | 7) NOTE: PLEASE SHOW ALL EXISTING ELECTRICAL IN THE 7TH |
| | FLOOR AREA FOR ELECTRICAL. THIS WOULD INCLUDE POWER AND |
| | LIGHT EVEN IN ROOMS NO WORK IS BEING DONE.THE SCOPE |
| | OF WORK BASE DON THE EXISTING BUILDING CODE AND CHANGE |
| | IN OCCUPANCY REQUIRES ALL TO MEET CODE EVEN IF NOT |
| | DOING WORK IN A PARTICULAR ROOM(S) AS SHOWN ON THE 7TH |
| | FLOOR. |
| | PLEASE KNOW THE LIGHTING WILL BE REQUIRED TO MEET |
| | CHAPTER 13 OF THE FBC FOR CONTROLS AND PERFORMANCE |
| | CALCULATIONS AS THIS SPACE IS BEING INCLUDED INTO THE |
| | NEW SINGLE TENANT. |
| | |
| | 8) NOTE: PLEASE SEE BOTH THE AHU AND THE ELEVATOR |
| | EQUIPMENT IS BEING SHOWN CONNECTED TO A RECEPTACLE |
| | WHICH IS NOT PERMITTED. |
| | PLEASE SEE THESE ARE REQUIRED TO BE HARDWIRED AND |
| | DISCONNECTS. |
| | 422.30,31, 440.11, 620.51 ETC. |
| | |
| | 9) NOTE: PLEASE KNOW THE CONTRACTOR OWES FEES AS THE |
| | VALUE ON PERMIT APPLICATION WAS INCREASED. |
| | FEE OWES IS CURRENTLY AT $1665.00. |
| | |
| | 10) NOTE: PLEASE SEE AS SOME COMMENTS ARE REPEATED FROM |
| | PREVIOUS REVIEW, PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO DESIGN PROFESSIONALS AND REPEATED CODE |
| | COMPLIANT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |