2007-08-28 13:54:21CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
  
 PERMIT NO. 06120362
 PROJECT NAME THE GUARANTY BUILDING
 ADDRESS 120 SOUTH OLIVE AVENUE
 CONTRACTOR: L. DAVIS CONSTRUCTION, INC.
  DATE: AUGUST28,2007
  
 PLANREVIEW
 JAMES JOHNSTON CBO
 BUILDING PLANS EXAMINER LL
 TEL:561-805-6713FAX:
 561-805-6731
 [email protected]
  
  
 (1) SUBMITTING PLAN CORRECTIONS:
 WHEN RE-SUBMITTING PLANS WITH CORRECTIONS PLEASE
 PROCEED AS FOLLOWS:
  A.INDICATE THE CORRECTED ITEMS BY CLOUDING ON THE
 NEW CORRECTED SHEET
  B.REMOVE THE OLD SHEET FROM THE PLAN AND INSERT
 THE NEWLY CORRECTED SHEET
  C.PUT OLD THE OLD SHEETS TOGETHER AS ONE SET AND
 SUBMIT TO THE BUILDING DEPT. ALONG
 WITH THE NEW CORRECTED PLANS. THIS IS NECESSARY
 FOR THE PLAN REVIEWER TO CRITIQUE
 THE CORRECTION REQUIRED FROM THE PREVIOUS PLAN
 REVIEW.
 D.SUBMIT A COVER LETTER IDENTIFYING THE CORRECTION
 MADE LISTING THE ITEM REFERENCED
 IN THE REVIEWER?S COMMENTS.
  
 (2) ADDRESS CHANGE:
  THE CORRECT ADDRESS OF THE PROPERTY IS ON THE
 ARCHITECTURAL SHEETS BUT, NOT ON THE
 ENGINEERING SHEETS. PLEASE NOTIFY THE ENGINEER TO MAKE
 THE REQUIRED CHANGE.
  
  THE PROPERTY CONTROL NUMBERS ON RECORD FOR THIS
 BUILDINGAT THE PALM BEACH COUNTY
 PROPERTY APPRAISAL?S OFFICE DO NOT HAVE A CONTROL
 NUMBER LISTED FOR THE EIGHTH FLOOR.
 THE NUMBERS STOP AT THE SEVENTH FLOOR.THEY ARE GOING
 TO ASSIGN A SEVENTH FLOOR NUMBER
 TO THE EIGHTH FLOOR.
 INCLUDED ARE THE FOLLOWING NUMBERS ASSIGNED TO GUARANTY
 NCP, LLC, THAT WILL BE SUITABLE TO INCLUDE THE EIGHTH
 FLOOR. PLEASE SELECT ONE.
 PROPERTY CONTROL NUMBERS THAT END IN:701,702,703,
 705
 CORRECT PERMIT APPLICATION TO REFLECT THE CONTROL
 NUMBER SELECTED.
  
 (3) PROJECT REQUIRED INFORMATION:
  THE COVER SHEET CS-1IN THE BLOCK TITLED ?SPECIFIC
 PROJECT REQUIREMENTS?.
  AND SHEET S-2STRUCTURAL NOTES
 PLEASE CORRECT /ADD THE INFORMATION LISTED HERE-IN.
  
 CODE:FBC2004 WITH 2006 SUPPLEMENTS AND FLORIDA
 BUILDING CODE 2004,FBC 2004
 EXISTING BUILDINGS AND HISTORIC BUILDINGS
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE CHAPTER 1,2004
 ALTERATION:LEVEL III
 INTERIOR RENOVATION OF THE SEVENTH AND EIGHTH FLOOR
 WITH ELEVATOR AND STAIRWAY
 CONSTRUCTION TYPE:I-B
 FBC TABLE 503NOTE: YOU CANNOT US E II-B BECAUSE IT IS
 ONLY GOOD FOR FOUR STORIES
  FIRE RATING FOR FRAMING MEMBERS
  
  
  
 (4) A. ALL FRAMING MEMBERS MUST BE TWO HOUR FIRE RATED
 BUT, BECAUSE OF THE FIRE SPRINKLER
 SYSTEM, YOU CAN REDUCE THE RATING BY ONE HOUR.
  
  B. PROVIDE A FIRE SPRINKLER PLAN OF THE HEADS AT THE
 SEVENTHFLOOR ALTERATION AREA.
  
  C. ADD TO PLAN ?8TH FLOOR COMPLETE ALTERATION WITH
 CHANGE OF OCCUPANCY FROM STORAGE TO
  BUSINESS?
  SUBMIT A PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION FOR THE EIGHTH FLOOR IMPACT FEES
  THAT WILL BE DUE WITH THIS CHANGE OF OCCUPANCY AND
 ALTERATION.
  PROPERTY APPRAISER?S OFFICE TEL:561-233-5025 FOR
 INFORMATION.
  
  D. PLEASE NOTE: FLORIDA STATUTE399 ?CHANGE OF
 OCCUPANCY? FOR THE EIGHTH FLOOR.
  
  WINDOW AND DOOR ANCHORAGE
 (7) A. PROVIDE DOOR /JAMB / HEADER DETAIL FOR FASTENING
 TO POURED CELLS.
  
  STAIRS
 (8) FBC 1009.3STAIR RISER MINIMUM 7?.SEE PLAN
 SHEET A-4 DETAIL 4 CHANGE RISER HEIGHT
  
  WIND LOADS
 (11) FBC1609.1THE BUILDING IS MORE THAN 60 FEET
 TO THE MEAN ROOF HEIGHT (SEE SURVEY).
  PLEASE FURNISHTHE WIND LOADS ON THE ROOFPER THIS
 SECTION.CHANGE BUILDING HEIGHT
  ON SHEET S-2 BUILDING DETAIL AND NOTES BELOW ?WIND
 LOAD SCHEDULE? THAT STATE 2001
  FLORIDA BUILDING CODE.SEE TABLE 1609.6.2.1(1). ALSO
 ASCE 7 2002 SHOULD BE USED AS A
 DESIGN.
 PLEASE SEE THE ATTACHED (2) COPIES MEMO FROM THE
 BUILDING OFFICIAL FOR WIND BORN
 DEBRIS / IMPACT PROTECTION FOR ARCHITECT / ENGINEER?S
 USE.
  
  PRODUCT APPROVALS
 (12) PRODUCT APPROVALS ARE REQUIRED FOR WINDOWS /
 DOORS/MULLIONS/ROOFING ASSEMBLIES
  WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE
 9B-72
  SUBMIT TWO COPIES OF EACH APPROVAL WITH THE
 ARCHITECT?S AND ENGINEER?S SIGNATURE
 STATING ?TO THE BEST OF THEIR KNOWLEDGE THE PRODUCT
 APPROVAL COMPLIES WITH THE PLANS
 AND SPECIFICATIONS.SEE WEB SITEWWW.FLORIDABUILDING
  
 (16) FIRE SAFETY STANDARDS
 WPB ADMINISTRATIVE CODE 105.13.4.4
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT AND ENGINEER OF
 RECORD SHALL STATE THE FOLLOWING? TO THE BEST OF THE
 ARCHITECT AND ENGINEERS KNOWLEDGE THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND FLORIDA STATUE 633.
  
 (17) SPECIAL INSPECTOR
 WPB AMENDMENT105.13.6REQUEST FOR A SPECIAL
 INSPECTOR AS REQUIRED BY FLORIDA STATUE
  553.79(5)TO THE MINIMUMINSPECTIONS REQUIRED BY
 THIS CODE. CONTACT HAROLD PISKURA,
  MANAGER OF THE SPECIAL INSPECTOR?S PROGRAM
 (561)-805-6711 BEFORE THE PERMIT MAY BE ISSUED.
  
 (18) LOOSE MATERIAL DURING A HURRICANE
  FBC109.3.10WHEN A HURRICANE WATCH HAS BEEN
 ISSUED, ALL LOOSE CONSTRUCTION MATERIAL
  AND EQUIPMENT MUST BE SECURED FOR 24 HOURS OR UNTIL
 THE WATCH HAS BEEN LIFTED.
  
 (19) PROVIDE SPECIFICATIONS FOR HILTIPRODUCT HIT-HY
 20330 ML/1
  PIN INFORMATION AS TO:
  SIZE,TYPE,LENGTH,CHEMICAL COMPOUND,SLEEVE
  
 (20) FBC707.4DOES ELEVATOR GO TO TOP FLOOR AND IS
 THE SHAFT RATED TWO HOUR?PLEASE STATE ON PLAN
  
 (21) IDENTIFY THE SUPPORTING COLUMN LOCATIONS ON THE
 SEVENTH FLOOR THAT ASSUME THE LOAD OF
  THE STEEL TUBE COLUMNS ON THE EIGHTH FLOOR.
  
 (22) PROVIDE THICKNESS OF FLOOR SLAB ON ENGINEERING
 PLAN
  
  
  
  
  
  
  