| 2007-08-28 13:54:21 | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, |
| | FLORIDA33401 |
| | |
| | PERMIT NO. 06120362 |
| | PROJECT NAME THE GUARANTY BUILDING |
| | ADDRESS 120 SOUTH OLIVE AVENUE |
| | CONTRACTOR: L. DAVIS CONSTRUCTION, INC. |
| | DATE: AUGUST28,2007 |
| | |
| | PLANREVIEW |
| | JAMES JOHNSTON CBO |
| | BUILDING PLANS EXAMINER LL |
| | TEL:561-805-6713FAX: |
| | 561-805-6731 |
| | [email protected] |
| | |
| | |
| | (1) SUBMITTING PLAN CORRECTIONS: |
| | WHEN RE-SUBMITTING PLANS WITH CORRECTIONS PLEASE |
| | PROCEED AS FOLLOWS: |
| | A.INDICATE THE CORRECTED ITEMS BY CLOUDING ON THE |
| | NEW CORRECTED SHEET |
| | B.REMOVE THE OLD SHEET FROM THE PLAN AND INSERT |
| | THE NEWLY CORRECTED SHEET |
| | C.PUT OLD THE OLD SHEETS TOGETHER AS ONE SET AND |
| | SUBMIT TO THE BUILDING DEPT. ALONG |
| | WITH THE NEW CORRECTED PLANS. THIS IS NECESSARY |
| | FOR THE PLAN REVIEWER TO CRITIQUE |
| | THE CORRECTION REQUIRED FROM THE PREVIOUS PLAN |
| | REVIEW. |
| | D.SUBMIT A COVER LETTER IDENTIFYING THE CORRECTION |
| | MADE LISTING THE ITEM REFERENCED |
| | IN THE REVIEWER?S COMMENTS. |
| | |
| | (2) ADDRESS CHANGE: |
| | THE CORRECT ADDRESS OF THE PROPERTY IS ON THE |
| | ARCHITECTURAL SHEETS BUT, NOT ON THE |
| | ENGINEERING SHEETS. PLEASE NOTIFY THE ENGINEER TO MAKE |
| | THE REQUIRED CHANGE. |
| | |
| | THE PROPERTY CONTROL NUMBERS ON RECORD FOR THIS |
| | BUILDINGAT THE PALM BEACH COUNTY |
| | PROPERTY APPRAISAL?S OFFICE DO NOT HAVE A CONTROL |
| | NUMBER LISTED FOR THE EIGHTH FLOOR. |
| | THE NUMBERS STOP AT THE SEVENTH FLOOR.THEY ARE GOING |
| | TO ASSIGN A SEVENTH FLOOR NUMBER |
| | TO THE EIGHTH FLOOR. |
| | INCLUDED ARE THE FOLLOWING NUMBERS ASSIGNED TO GUARANTY |
| | NCP, LLC, THAT WILL BE SUITABLE TO INCLUDE THE EIGHTH |
| | FLOOR. PLEASE SELECT ONE. |
| | PROPERTY CONTROL NUMBERS THAT END IN:701,702,703, |
| | 705 |
| | CORRECT PERMIT APPLICATION TO REFLECT THE CONTROL |
| | NUMBER SELECTED. |
| | |
| | (3) PROJECT REQUIRED INFORMATION: |
| | THE COVER SHEET CS-1IN THE BLOCK TITLED ?SPECIFIC |
| | PROJECT REQUIREMENTS?. |
| | AND SHEET S-2STRUCTURAL NOTES |
| | PLEASE CORRECT /ADD THE INFORMATION LISTED HERE-IN. |
| | |
| | CODE:FBC2004 WITH 2006 SUPPLEMENTS AND FLORIDA |
| | BUILDING CODE 2004,FBC 2004 |
| | EXISTING BUILDINGS AND HISTORIC BUILDINGS |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE CHAPTER 1,2004 |
| | ALTERATION:LEVEL III |
| | INTERIOR RENOVATION OF THE SEVENTH AND EIGHTH FLOOR |
| | WITH ELEVATOR AND STAIRWAY |
| | CONSTRUCTION TYPE:I-B |
| | FBC TABLE 503NOTE: YOU CANNOT US E II-B BECAUSE IT IS |
| | ONLY GOOD FOR FOUR STORIES |
| | FIRE RATING FOR FRAMING MEMBERS |
| | |
| | |
| | |
| | (4) A. ALL FRAMING MEMBERS MUST BE TWO HOUR FIRE RATED |
| | BUT, BECAUSE OF THE FIRE SPRINKLER |
| | SYSTEM, YOU CAN REDUCE THE RATING BY ONE HOUR. |
| | |
| | B. PROVIDE A FIRE SPRINKLER PLAN OF THE HEADS AT THE |
| | SEVENTHFLOOR ALTERATION AREA. |
| | |
| | C. ADD TO PLAN ?8TH FLOOR COMPLETE ALTERATION WITH |
| | CHANGE OF OCCUPANCY FROM STORAGE TO |
| | BUSINESS? |
| | SUBMIT A PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION FOR THE EIGHTH FLOOR IMPACT FEES |
| | THAT WILL BE DUE WITH THIS CHANGE OF OCCUPANCY AND |
| | ALTERATION. |
| | PROPERTY APPRAISER?S OFFICE TEL:561-233-5025 FOR |
| | INFORMATION. |
| | |
| | D. PLEASE NOTE: FLORIDA STATUTE399 ?CHANGE OF |
| | OCCUPANCY? FOR THE EIGHTH FLOOR. |
| | |
| | WINDOW AND DOOR ANCHORAGE |
| | (7) A. PROVIDE DOOR /JAMB / HEADER DETAIL FOR FASTENING |
| | TO POURED CELLS. |
| | |
| | STAIRS |
| | (8) FBC 1009.3STAIR RISER MINIMUM 7?.SEE PLAN |
| | SHEET A-4 DETAIL 4 CHANGE RISER HEIGHT |
| | |
| | WIND LOADS |
| | (11) FBC1609.1THE BUILDING IS MORE THAN 60 FEET |
| | TO THE MEAN ROOF HEIGHT (SEE SURVEY). |
| | PLEASE FURNISHTHE WIND LOADS ON THE ROOFPER THIS |
| | SECTION.CHANGE BUILDING HEIGHT |
| | ON SHEET S-2 BUILDING DETAIL AND NOTES BELOW ?WIND |
| | LOAD SCHEDULE? THAT STATE 2001 |
| | FLORIDA BUILDING CODE.SEE TABLE 1609.6.2.1(1). ALSO |
| | ASCE 7 2002 SHOULD BE USED AS A |
| | DESIGN. |
| | PLEASE SEE THE ATTACHED (2) COPIES MEMO FROM THE |
| | BUILDING OFFICIAL FOR WIND BORN |
| | DEBRIS / IMPACT PROTECTION FOR ARCHITECT / ENGINEER?S |
| | USE. |
| | |
| | PRODUCT APPROVALS |
| | (12) PRODUCT APPROVALS ARE REQUIRED FOR WINDOWS / |
| | DOORS/MULLIONS/ROOFING ASSEMBLIES |
| | WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE |
| | 9B-72 |
| | SUBMIT TWO COPIES OF EACH APPROVAL WITH THE |
| | ARCHITECT?S AND ENGINEER?S SIGNATURE |
| | STATING ?TO THE BEST OF THEIR KNOWLEDGE THE PRODUCT |
| | APPROVAL COMPLIES WITH THE PLANS |
| | AND SPECIFICATIONS.SEE WEB SITEWWW.FLORIDABUILDING |
| | |
| | (16) FIRE SAFETY STANDARDS |
| | WPB ADMINISTRATIVE CODE 105.13.4.4 |
| | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT AND ENGINEER OF |
| | RECORD SHALL STATE THE FOLLOWING? TO THE BEST OF THE |
| | ARCHITECT AND ENGINEERS KNOWLEDGE THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND FLORIDA STATUE 633. |
| | |
| | (17) SPECIAL INSPECTOR |
| | WPB AMENDMENT105.13.6REQUEST FOR A SPECIAL |
| | INSPECTOR AS REQUIRED BY FLORIDA STATUE |
| | 553.79(5)TO THE MINIMUMINSPECTIONS REQUIRED BY |
| | THIS CODE. CONTACT HAROLD PISKURA, |
| | MANAGER OF THE SPECIAL INSPECTOR?S PROGRAM |
| | (561)-805-6711 BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | (18) LOOSE MATERIAL DURING A HURRICANE |
| | FBC109.3.10WHEN A HURRICANE WATCH HAS BEEN |
| | ISSUED, ALL LOOSE CONSTRUCTION MATERIAL |
| | AND EQUIPMENT MUST BE SECURED FOR 24 HOURS OR UNTIL |
| | THE WATCH HAS BEEN LIFTED. |
| | |
| | (19) PROVIDE SPECIFICATIONS FOR HILTIPRODUCT HIT-HY |
| | 20330 ML/1 |
| | PIN INFORMATION AS TO: |
| | SIZE,TYPE,LENGTH,CHEMICAL COMPOUND,SLEEVE |
| | |
| | (20) FBC707.4DOES ELEVATOR GO TO TOP FLOOR AND IS |
| | THE SHAFT RATED TWO HOUR?PLEASE STATE ON PLAN |
| | |
| | (21) IDENTIFY THE SUPPORTING COLUMN LOCATIONS ON THE |
| | SEVENTH FLOOR THAT ASSUME THE LOAD OF |
| | THE STEEL TUBE COLUMNS ON THE EIGHTH FLOOR. |
| | |
| | (22) PROVIDE THICKNESS OF FLOOR SLAB ON ENGINEERING |
| | PLAN |
| | |
| | |
| | |
| | |
| | |
| | |
| | |